Reviewing Commands | 25
Reset System
Press
Reset System
to clear latching events.
NOTE
Latching events remain active until a system reset is performed, even after resolving the cause of
the event. Non-latching events do not require a system reset and will clear after correcting the cause of the
event.
To reset the fire control panel from the latching input:
1. Clear alarm conditions from external devices.
2. Press Reset System to reset the latching events and restore the panel to the Normal Standby
Condition. After the system resets, the internal buzzer and external NACs of the fire control panel are
silenced, and panel returns to a quiescent state.
WARNING!
Alarm notification signals should not be silenced until all occupants have been evacuated.
Version 1.04 | May 2019 | MAN-1432HA