Section 3 – Installing the FNP-1127-SLC

3.1 Overview of the FNP-1127-SLC 

The FireNET Plus control panel is provided with one SLC Loop.  An additional SLC Loop may be added 
through the use of a FNP-1127-SLC loop expander board. 

The main control unit has terminations for connecting the first SLC loop. The connections for the second 
loop are located on the FNP-1127-SLC expander board. 

3.1.1 Installation of the FNP-1127-SLC 

1.  To install the additional SLC Loop, the control panel must have its AC and battery power 

removed.

Do not attempt to install the SLC expander board while the FireNET Plus panel is 

powered!

2.  Remove the screw on the front display panel and open the panel to the left, exposing the back of 

the circuit board.  

3.  The circuit board containing the additional loop circuit is supplied in a static dissipative bag and 

should remain in this bag until it is to be installed. 

NOTE:

 

As with all electronic components, this circuit board is very sensitive and can be easily 
damaged by electrostatic discharge.  

4.  The loop board mounts on the upper left hand side of the rear of the circuit board. Install the 

mounting standoffs to the main board then attach the expander board using the M3 screws and 
fiber washers. 

FNP-1127 SLC Loop 
Expander Board Location

5.  After ensuring that the new circuit board is properly installed and making good contact with its 

connectors close the front display panel and secure with the screw.  

6.  Connect the SLC loop wiring and then re-apply power to the control panel.  Note that class B SLC 

circuits require the installation of the supplied 0 ohm jumpers (HA part # 0400-01025) 

After the new SLC devices have been installed and connected, they may be automatically detected using 
the auto learn feature from the menu on the control panel.   

Please see the FireNET Plus Installation and Operation manual for more details on panel configuration 
and programming (HA part # 1700-10840) 

Summary of Contents for FireNET FNP-1127-SLC

Page 1: ...n and Operation Manual Hochiki America Corporation 7051 Village Drive Suite 100 Buena Park CA 90621 2268 714 522 2246 Corporate Headquarters 800 845 6692 Technical Support http www hochiki com Version...

Page 2: ...Table of Contents 2 Section 1 Introduction 3 1 1 Limitations of Fire Alarm Systems 3 Section 2 General Wiring Specifications 6 Section 3 Installing the FNP 1127 SLC 7 3 1 Overview of the FNP 1127 SLC...

Page 3: ...ication Systems All fire alarm systems require notification devices including sirens bells horns and or strobes In residential applications each automatic alarm initiating device when activated should...

Page 4: ...ector to falsely alarm If the location of a smoke detector causes an abundance of false alarms or nuisance alarms do not disconnect the smoke detector call a professional to analyze the situation and...

Page 5: ...l power If system batteries are not serviced or replaced regularly they may not provide battery backup when AC power fails x High Air Velocity or Dusty or Dirty Environments Environments with high air...

Page 6: ...ion is required between high and low voltage wiring x Identify which group each wire or cable is associated with from the list below Isolate each group s wiring as much as possible Avoid running a sin...

Page 7: ...ld remain in this bag until it is to be installed NOTE As with all electronic components this circuit board is very sensitive and can be easily damaged by electrostatic discharge 4 The loop board moun...

Page 8: ...t which has been repaired by others abused improperly installed altered or otherwise misused or damaged or exposed to conditions outside the products specifications in any way Unless previously contra...

Reviews: