background image

i1 HOCHIKI  CORPORATION 

INSTALLATION  INSTRUCTIONS  FOR HOCHIKI HEAT DETECTOR TYPE:DCD, DFJ 

INTRODUCTION 

Combined Type Heat Detector  : 

DCD-1 E  (EN-54-5 Grade 1)

DCD-2E  (EN-54-5 Grade 2)

DCD-R1E (EN-54-8 Range1)

DCD-1EF  (NF S61-950 Grade 1)

DCD-A

DCD-C

DCD-135

DCD-190

Fixed- Temperature Heat Detector : 

DFJ-60E  (EN-54-5 Grade 2) 

I

DFJ-608 

DFJ-90E  (EN-54-8 Range1)  DFJ-90D 

(AS ISO7240.5 Class A1R) 

(AS ISO7240.5 Class CR ) 

(UL-521 Ordinary) 

(UL-521 Intermediate) 

(AS ISO7240.5 ClassA1S ) 

(AS ISO7240.5 Class CS) 

DCD-2C (GB-4716-93 Grade 2)

DCD-3C (GB-4716-93 Grade 3)

I

DFJ-60C (GB-4716-93 Grade  2) 

DFJ-70C (GB-4716-93 Grade  3) 

Base  :  YBN-R/4,  YBN-R/4A,  YBN-R/48,  YBN-R/4C,  YBO-R/4A,  YBO-R/5 series 

NOTE :  These detectors are NOT compatible with bases 

YBC(except YBC-R/3), YBF, YBK, YCA, AMU-B2 and AMU-MB 

Other combinations of detector and base are also possible. 

Please confirm with Hochiki or the appointed sales agent. 

Ensure  that  the  following  items  are  observed  before  installation  and  maintenance.  Hochiki  cannot 

warrant a detector's performance if such  items are neglected. 

CAUTION 

1. This detector is used to detect conditions and changes in temperature  and cannot detect smoke  or

other phenomena.

2. This detector cannot be used to prevent FIRE itself,  it is  only intended to detect a certain

characteristic of fire.

3. When installing this detector, ensure that the location of each detector has been planned in

accordance with appropriate local and National fire regulations or recommendations.

4. These detectors are suitable for IN DOOR USE ONLY.

5. The detector shall not be installed in the following environmental conditions:

Situations in which condensation exists. 

Situations in which corrosive gases exist. 

Situations in  which dust or steam exist. 

Situations in which obstacles exist,  which could  impede airflow to the detector. 

6. Certain actions can cause permanent damage to the detector and therefore if the detector is

subjected to any of the following actions it should not be used :

Disassembly and reassembly. 

Impact or shock. 

Touching the thermistor of the detector (the thermistor is black  and located in the 

centre of the detector ) . 

7. The  detector is  expected to be used to  detect only one real fire situation and could suffer damage

during a fire condition.  It should therefore be replaced if damaged during a fire or at any other time.

8. After installation,  all detectors on the fire alarm system should be tested to verify correct operation.
9. Installation and maintenance should only be carried out by suitably trained personnel.
10. The detector must be subject to periodic maintenance during regular service visits,  which should be

as recommended by appropriate local and National Standards or recommendations.  In the event of

no such Standards existing,  Hochiki recommend that the minimum period of maintenance should

be 1 year and that the following items should be taken into account  :

In case where there is an excess build-up of dust on the thermistor, the sensitivity of the 

detector could be affected. 

A regular operational test should be performed. 

A visual check for staining and mechanical damage. 

11. Detector operation should not be verified by the use of a naked flame or open fire. Operation

should only be checked by equipment that is capable of exceeding the required detection threshold

by small amount, sufficient to guarantee a fire signal is produced by the detector.

Reviews: