Hochiki America FN-400ULX Installation Manual Download Page 2

- 2 - 

 

140 58th St. 

Overview: 

The FN-400ULX is a power supply that converts a 115VAC / 60Hz input to a 12VDC or 24VDC regulating output 

(see specifications below)

 

Agency Listings:

 

 

UL File # S4707: 

UL Listed for Access Control 

Specifications: 

Altronix Corp . 

Output 

(cont’d)

 

Short circuit and thermal overload  protection. 

Battery Backup: 

System Units (UL 294), UL Listed Standard for Power 

Supplies for Use with Burglar-Alarm Systems (UL 603), 

UL Listed Hospital Signaling and Nurse Call Equipment 

(UL 1069), UL Listed Standard for Safety for Fire 

Protective Signaling Systems (UL 1481). 

 

MEA - NYC Department of Buildings  Approved. 

 

CSFM - California State Fire Marshal  Approved. 

 

FM Approved. 

Input: 

 

Input 115VAC, 60Hz, 3 amp. 

 

AC input and DC output LED  indicators. 

Output: 

 

Class 2 Rated power-limited output. 

 

12VDC or 24VDC selectable output. 

 

4 amp total supply current at  12VDC 

or 3 amp total supply current at 24VDC. 

 

Filtered and electronically regulated outputs. 

 

Built-in charger for sealed lead acid or gel type  batteries. 

 

Automatic switch over to stand-by battery when 

AC fails. 

 

Maximum charge current 0.7 amp. 

 

Zero voltage drop when switched over to battery  backup. 

Supervision: 

 

AC fail supervision (form “C” contacts). 

 

Low battery supervision (form “C” contacts). 

 

Battery presence supervision (form “C” contacts). 

Additional Features:

 

 

Power supply, enclosure, cam lock and battery  leads. 

Enclosures: 

FN-400ULX-R (Red) 

FN-400ULX-C (Charcoal Grey) 

Enclosure Dimensions 

(H x W x D)

13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm) 

Power Supply Voltage Output Selections: 

 

Switch Detail 

 

OPEN SWITCH 

Fig. 1 

 

 

CLOSED SWITCH 

 

Stand-by  Specifications:

 

Output 

4 hr. of Stand-by & 

5 Minutes of Alarm 

24 hr. of Stand-by & 

5 Minutes of Alarm 

60 hr. of Stand-by & 

5 Minutes of Alarm 

12VDC / 40AH Battery 

Stand-by = 4.0 amp 

Alarm = 4.0 amp 

Stand-by = 1.0 amp 

Alarm = 4.0 amp 

Stand-by = 300mA 

Alarm = 4.0 amp 

24VDC / 12AH Battery 

-------- 

Stand-by = 200mA 

Alarm = 3.0 amp 

-------- 

24VDC / 40AH Battery 

Stand-by = 3.0 amp 

Alarm = 3.0 amp 

Stand-by = 1.0 amp 

Alarm = 3.0 amp 

Stand-by = 300mA 

Alarm = 3.0 amp 

Installation Instructions: 

The unit should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all 

applicable Local Codes. 

1.

 

Mount unit in the desired location

Mark and predrill holes in the wall to line up with the top two keyholes in the 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s 

upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the 

enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper 

screws. Install the two lower screws and make sure to tighten all screws 

(Enclosure Dimensions, pg. 4)

2.

 

Set the FN-400ULX to the desired DC output voltage by setting SW1 

(Fig. 1, pg. 2, Fig. 2c, pg. 3) 

to the appropriate 

position (

refer to Power Supply Voltage Output Selections  chart

). 

3.

 

Connect AC power (115VAC 60Hz) to terminals marked [L, G, N] 

(Fig. 2, pg. 3)

. Use 14 AWG or larger for all 

power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits 

(AC Fail/Low Battery reporting). 

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires). 

Minimum 0.25” spacing must be provided. 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel. 

  

 

Opened - 24V 

Closed - 12V 

SW1 

Output 

Switch Position 

12VDC 

SW1 - CLOSED 

(Fig. 1, on right) 

24VDC 

SW1 - OPEN 

(Fig. 1, on right) 

 