(3) Overload module
The overload module is located inside the generator control box. This overload module
(5, Fig 7)
is a solid-state device designed to interpret a signal from the current transformers and to send a
signal to the protective monitor module
(7, Fig. 7)
when an overload condition exists in any gener-
ator output phase. A pull-apart electrical connector is mounted on the owerload module to provide
quick-disconnect facilities for all wiring to the module. The overload module is equipped with a
hermetically sealed, reed-type relay. Relay contacts are normally open. The solid-state circuitry is
designed to close relay contacts when output current in ANY phase reaches 125% of normal
rated output capacity. The closed relay sends a signal to the protective monitor. This signal
“gates” the overload SCR
(silicone-controlled rectifier)
in the protective monitor and interrupts the
load contactor holding circuit, allowing the load contactor to open.
The following is a list of overload module characteristics:
NOTE: The overload protective system will function when any phase carries 123% to 127% of
rated load.
At 125% load the module will function in 4 minutes.
At 150% load the module will function in 16 seconds.
At 200% load the module will function in 4 seconds.
NOTE: All times are plus or minus 25% and are nonadjustable.
(4) Rectifier
A diode bridge rectifier is located inside the generator control box.
(See Fig. 7, item 10)
. This di-
ode-bridge rectifier receives 400-Hz AC from phase C of the generator output an converts it to a
pulsating, direct current for energization of the load contactor coil only. This DC coil-holding circuit
is controlled indirectly be controlling the 400-Hz AC to the rectifier. The ground circuit for the recti-
fier’s AC supply must pass through the relay contacts in the protective monitor module to ground
cable N. Therefore, any time a protective device functions to open the protective monitor relay,
the rectifier’s AC circuit is opened. No DC is then available for the load contactor coil, hence, the
load contactor opens.
OM-2053
December 31/91 Revised
1-1
Page 17
Summary of Contents for 60PL20
Page 2: ...This page intentionally left blank ...
Page 6: ...This page intentionally left blank OM 2053 Introduction December 31 91 Revised Page 2 ...
Page 36: ...This page intentionally left blank OM 2053 1 2 March 20 89 Page 4 ...
Page 42: ...This page intentionally left blank OM 2053 1 3 December 31 91 Revised Page 6 ...
Page 53: ...Removable Rear Frame Cross Member Figure 3 OM 2053 December 31 91 Revised 2 1 Page 11 ...
Page 54: ...This page intentionally left blank OM 2053 2 1 December 31 91 Revised Page 12 ...
Page 78: ...This page intentionally left blank OM 2053 2 3 December 31 91 Revised Page 20 ...
Page 84: ...This page intentionally left blank OM 2053 3 1 December 31 91 Revised Page 6 ...
Page 106: ...Generator Set Figure 1 OM 2053 4 3 December 31 91 Revised Page 2 ...
Page 108: ...Canopy Assembly Figure 2 OM 2053 4 3 December 31 91 Revised Page 4 ...
Page 112: ...This page intentionally left blank OM 2053 4 3 December 31 91 Revised Page 8 ...
Page 114: ...Radiator and Cooling System Group Figure 4 OM 2053 4 3 December 31 91 Revised Page 10 ...
Page 116: ...Air Cleaner Assembly Figure 5 OM 2053 4 3 December 31 91 Revised Page 12 ...
Page 118: ...Electric Governor Kit Woodward Governor Figure 6 OM 2053 4 3 December 31 91 Revised Page 14 ...
Page 122: ...Fuel Lines Assembly Figure 7 OM 2053 4 3 December 31 91 Revised Page 18 ...
Page 124: ...Oil Line Assembly Figure 8 OM 2053 4 3 December 31 91 Revised Page 20 ...
Page 128: ...Control Box Assembly Figure 10 OM 2053 4 3 December 31 91 Revised Page 24 ...
Page 130: ...This page intentionally left blank OM 2053 4 3 December 31 91 Revised Page 26 ...
Page 132: ...Engine Control Panel Assembly Figure 11 OM 2053 4 3 December 31 91 Revised Page 28 ...
Page 134: ...4 3 Revised Page 30 March 30 93 Contactor Panel Assembly Figure 12 OM 2053 ...
Page 136: ...Generator Group Figure 13 OM 2053 4 3 December 31 91 Revised Page 32 ...
Page 138: ...Trailer Assembly Figure 14 OM 2053 4 3 December 31 91 Revised Page 34 ...
Page 140: ...This page intentionally left blank OM 2053 4 3 December 31 91 Revised Page 36 ...
Page 142: ...This page intentionally left blank OM 2053 4 3 December 31 91 Revised Page 38 ...
Page 152: ...This page intentionally left blank OM 2053 5 0 March 20 89 Page 2 ...
Page 154: ...This page intentionally left blank OM 2053 6 0 December 31 91 Revised Page 2 ...
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......
Page 164: ......
Page 165: ......
Page 166: ......
Page 167: ......
Page 168: ......
Page 169: ......
Page 170: ......
Page 171: ......
Page 172: ......
Page 173: ......
Page 174: ......
Page 178: ...This page intentionally left blank Wetstacking December 31 91 Revised Page 2 ...