OM-192 440 Page 14
2-10. Positioning Jumper Links
Ref. 802 285-B
Check input voltage available at
site.
1
Jumper Links Access Door
Open door.
2
Jumper Link Label
Check label – only one is on unit.
3
Input Voltage Jumper Links
Move jumper links to match input
voltage.
Close and secure access door.
3
Tools Needed:
2
1
3/8 in
200 VOLTS
230 VOLTS
S-153 980
2-11. Electrical Service Guide
Input Voltage
200
230
Input Amperes At Rated Output
40
35
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
50
40
Normal Operating 3
60
50
Min Input Conductor Size In AWG/Kcmil
8
10
Max Recommended Input Conductor Length In Feet (Meters)
108
(33)
94
(29)
Min Grounding Conductor Size In AWG/Kcmil
10
10
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
Y
Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.