HBU Series Braking Unit
8
Chapter 2 Product Models and Specification
2.1 Model Specifications
Table 2.1 Specifications of braking energy unit
Model
Specifications
Usage Occasion Power Range Rated
Current
Peak
Current
General Mode
HBU-1L
dynamic raking
0.75-18KW
6A
33A
HBU-1SA
dynamic raking
22-37 KW
9A
50A
HBU-3SA
dynamic raking
45-55 KW
10A
100A
HBU-3HA
dynamic braking 75-90KW
70A
150A
HBU-4HA
dynamic braking 110-132 KW
85A
200A
HBU-5HA
dynamic braking 160-200 KW
120A
300A
HBU-6HA
dynamic braking 220-280KW
160A
400A
Rated current is maximum average current when braking
unit working. Peak current is maximum current allowed during
working, its running time should last less than 20 seconds.
2.2 Product Tech Specification
Table 2.2 Product Technical Specification
item
specification
Power supply
Network
voltage
Tri-phase 220V/380V/460/660V
(
depend on models
)
Network
frequency
45Hz
~
65Hz
Summary of Contents for HBU Series
Page 1: ...HBU Series Braking Unit User s Manual HNC Electric Limited ...
Page 13: ...HBU Series Braking Unit 12 2 4 Product installation dimension HBU 1L dimension ...
Page 14: ...HBU Series Braking Unit 13 HBU 1SA 3SA dimension ...
Page 15: ...HBU Series Braking Unit 14 HBU 3HA 4HA 5HA 6HA dimension ...