Doc: HMSI-27-262, Rev: 2.10
Anybus X-gateway User Manaul
Appendix B
B. Technical Specifications
Power
The gateway requires a regulated 24V±20% DC Class 2 power source. Maximum power consumption
is 400mA at 24VDC. Typical consumption is 200mA at 24VDC.
Protective Earth and Shielding
The product must be connected to protective earth (PE) via the DIN-rail connector in order to achieve
proper EMC behaviour.
Temperature
Operating
Profinet IRT Fibre Optic: -25 to +50 degrees Celsius
All other models: -25 to +65 degrees Celsius. Test performed according to IEC-68-2-1 and IEC 68-2-2.
Non-operating
-40 to +85 degrees Celsius. Test performed according to IEC-68-2-1 and IEC 68-2-2.
Relative Humidity
The product is designed for a relative humidity of 5-95%, non-condensing.
Test performed according to IEC 68-2-30.
EMC Compliance
The onboard network interfaces are tested according to the following:
Electrostatic discharge
+/- 4 kV
EN 61000-4-2
Electromagnetic RF fields
10 V/m 80 MHz - 1 GHz
3 V/m 1,4 GHz - 2,0 GHz
1 V/m 2,0 GHz - 2,7 GHz
EN 61000-4-3
Fast Transients
+/- 1 kV
EN 61000-4-4
Surge protection
+/- 1 kV
EN 61000-4-5
RF conducted interference
10 V/ms
EN 61000-4-6
Emission (at 3 m)
50 dB 30 MHz - 230 MHz
57 dB 30 MHz - 1 GHz
EN 55016-2-3