Configuration
2-7
Doc.Id. HMSI-168-77
Anybus® Modbus-TCP/RTU Gateway
Doc.Rev. 2.03
Internal Registers
If Gateway Registers are enabled, queries sent to those addresses will not be forwarded to the Serial
Modbus/RTU network, but handled by the gateway.
Register Name
Values
Options
Comment
1
Digital input 1 status
0 or 1
Read only
2
Digital input 2 status
0 or 1
Read only
3
Number of active connec-
tions MB/TCP
0 - 10
Read only
4
Number of active internal
connections
0 - 10
Read only
Serial status (Modbus/TCP)
5
Valid responses
0 - 65535
Can be cleared
6
Serial time outs
0 - 65535
Can be cleared
7
CRC errors
0 - 65535
Can be cleared
8
Input Buffer overruns
0 - 65535
Can be cleared
9
Frame errors
0 - 65535
Can be cleared
10
Exceptions responses
0 - 65535
Can be cleared
Serial status (buffered messages)
11
Valid responses
0 - 65535
Can be cleared
12
Serial time outs
0 - 65535
Can be cleared
13
CRC errors
0 - 65535
Can be cleared
14
Input Buffer overruns
0 - 65535
Can be cleared
15
Frame errors
0 - 65535
Can be cleared
16
Exceptions responses
0 - 65535
Can be cleared
Serial status (internal requests and web pages)
17
Valid responses
0 - 65535
Can be cleared
18
Serial time outs
0 - 65535
Can be cleared
19
CRC errors
0 - 65535
Can be cleared
20
Input Buffer overruns
0 - 65535
Can be cleared
21
Frame errors
0 - 65535
Can be cleared
22
Exceptions responses
0 - 65535
Can be cleared
Configuration registers
23
Modbus/TCP Port
1 - 65535
Default: 502
24
Gateway Modbus address
-1 - 255
-1
Disabled
Default
0 - 255
Enabled
25
Modbus/TCP idle time out 0 - 65535 (seconds)
Default: 60 seconds
0
Disabled
1 - 65535
Enabled
26
Baud rate
2400
2400 bps
4800
4800 bps
9600
9600 bps
Default
19200
19200 bps
38400
38400 bps
57600
57600 bps
115200
115200 bps
27
Parity
0 - 2
0
No parity
Default
1
Even parity
2
Odd parity