14 (70)
linking device is online or offline. The linking device configuration cannot be changed when the
connection is online.
See
Linking Device Configuration Manager Interface, p. 38
for a description of the menu options.
4.4
Modbus-TCP Client Configuration
The EtherNet/IP to Modbus-TCP linking device has a built-in Modbus—TCP client configuration
manager. The following system requirements must be met to access the configuration manager:
•
Javascript enabled
•
HTTP access from the computer with Studio 5000 and the linking device
Consider the following when configuring Modbus-TCP servers and transactions:
•
When you have saved data to the configuration but not yet applied it, this will appear top of
the configuration manager:
•
A changed configuration must be applied in order to take effect.
•
A maximum of 64 Modbus-TCP servers can be added to the configuration.
•
A maximum of 64 transactions can be set up to the servers in the configuration.
•
The data limit is 4096 bytes input data and 4096 bytes output data, including optional
control/status word and live list.
•
Modbus transactions are assembled in up to 10 Ethernet/IP Class 1 Exclusive Owner (IO)
Connections.
•
Each Ethernet/IP Class 1 Exclusive Owner (IO) connection holds one input assembly of 500
bytes and one output assembly of 496 bytes.
•
Only as many Ethernet/IP Class 1 Exclusive Owner (IO) connections as needed are defined
and used.
Linking Device User Manual
scm-1202–181 2.0 en-US
Summary of Contents for Anybus HMS-EN2MB-R
Page 1: ...Linking Device EtherNet IP to Modbus TCP USER MANUAL scm 1202 181 2 0 en US ENGLISH...
Page 5: ...Linking Device User Manual scm 1202 181 2 0 en US H Copyright Notices 67...
Page 6: ...This page intentionally left blank...
Page 34: ...This page intentionally left blank...