Appendix A: Internal Registers
15 (20)
A
Internal Registers
Register
Name
Values
Options
Comment
1
Digital input 1 status
0 or 1
Read only
2
Digital input 2 status
0 or 1
Read only
3
Active MBTCP connections
0 - 10
Read only
4
Active internal connections
0 - 10
Read only
Serial status (Modbus TCP)
5
Valid responses
0 - 65535
Can be cleared
6
Serial time outs
0 - 65535
Can be cleared
7
CRC errors
0 - 65535
Can be cleared
8
Input buffer overruns
0 - 65535
Can be cleared
9
Frame errors
0 - 65535
Can be cleared
10
Exceptions responses
0 - 65535
Can be cleared
Serial status (buffered messages)
11
Valid responses
0 - 65535
Can be cleared
12
Serial time outs
0 - 65535
Can be cleared
13
CRC errors
0 - 65535
Can be cleared
14
Input Buffer overruns
0 - 65535
Can be cleared
15
Frame errors
0 - 65535
Can be cleared
16
Exceptions responses
0 - 65535
Can be cleared
Serial status (internal requests and web pages)
17
Valid responses
0 - 65535
Can be cleared
18
Serial time outs
0 - 65535
Can be cleared
19
CRC errors
0 - 65535
Can be cleared
20
Input Buffer overruns
0 - 65535
Can be cleared
21
Frame errors
0 - 65535
Can be cleared
22
Exceptions responses
0 - 65535
Can be cleared
Configuration registers
23
Modbus TCP Port
1 - 65535
Default: 502
24
Gateway Modbus address
-1 to 255
-1
Disabled
Default
0 - 255
Enabled
25
Modbus TCP idle time out
0 - 65535
Default: 60 seconds
0
Disabled
1 - 65535
Enabled
26
Baud rate
2400
2400 bps
4800
4800 bps
9600
9600 bps
Default
19200
19200 bps
38400
38400 bps
57600
57600 bps
115200
115200 bps
27
Parity
0 - 2
0
No parity
Default
1
Even parity
2
Odd parity
28
Number of stop bits
1 - 2
Default: 1 stop bit
29
Slave time out time
25 - 65535
Default: 1000 ms
30
Physical interface
0 - 2
0
EIA-485 (terminal)
Default
1
EIA-232 (DSUB)
2
EIA-232 (terminal)
Anybus
®
Modbus-TCP/RTU Gateway User Manual
HMSI-168-77 3.0