INMBSFGL016O000
Fujitsu VRF to Modbus Slave gateway
Order Code:
INMBSFGL016O000
** stands for the Intesis capacity and varies depending on the specific gateway acquired
Installation Sheet rev.1.0
HMS Industrial Networks S.L.U ©
SAFETY INSTRUCTIONS
!
WARNING
Follow carefully this safety and installation instructions.
Improper work may lead to serious harmful for your health
and also may damage seriously the Intesis gateway and/or
any other equipment connected to it.
Intesis gateway must be installed by accredited electrician or similar
technical personnel, following all the safety instructions given here and
in accordance always with the country legislation for installation of
electric equipment.
Intesis gateway cannot be installed outdoors or exposed to direct solar
radiation, water, high relative humidity or dust.
Intesis gateway must only be installed in a restricted access location.
In case of wall mount, fix firmly Intesis gateway on a not vibrating
surface following the instructions next.
In case of DIN rail mount fix Intesis gateway properly to the DIN rail
following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to
earth is recommended.
Disconnect always power of any wires before manipulating and
connecting them to Intesis gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rated is to be used.
Respect always the expected polarity of power and communication
cables when connecting them to Intesis gateway.
Supply always a correct voltage to power Intesis gateway, see details
of voltage range admitted by the device in the technical characteristics
below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type.
Dispose of Used Batteries according to the instructions. Battery
replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without
routing to the outside plant, all communication ports are considered for
indoor only and can be connected SELV circuits only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels
above 4 kV, precautions should be taken when the device is mounted
outside an enclosure. When working in an enclosure (ex. making
adjustments, setting switches etc.) typical anti-static precautions
should be observed before touching the unit.
Safety instructions in other languages can be found at:
https://intesis.com/docs/manuals/v6-safety
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to Intesis
gateway.
Disconnect power of any bus or communication cable before
connecting it to Intesis gateway.
Mount Intesis gateway on the wall or DIN rail following the instruction
given below, respecting the safety instructions given above.
Connect a NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply to Intesis gateway, respect the polarity if DC power
or Line and Neutral if AC power. Apply always a voltage within the
range admitted by Intesis gateway and of enough power (see technical
characteristics).
Circuit-breaker must be used before the power supply. Rating 250V-
6A.
Connect the communication cables to Intesis gateway, see details on
the user's manual.
Power Intesis gateway and the rest of devices connected to it.
NOTE:
The device cannot be installed in air-handling space.
Wall Mount
1. Separate the fixing clips in the bottom of the box, pushing
them to the outside until hear the "click" which indicates that
now the clips are in position for wall mount, see in the figure
below.
2. Use the holes of the to fix the box in the wall using screws.
Use the template below for the wall wholes.
Clips in their original position Clips in position for wall mount
(for DIN rail mount)
DIN Rail Mount
With the clips of the box in their original position, insert first the box
in the upper edge of the DIN rail and later insert the box in the down
part of the rail, using a small screwdriver and following the steps in
the figure below.
Press
Press
Press
CONFIGURATION
Use the
Configuration Tool
to configure the gateway.
See instructions to download and install the latest version at:
https://intesis.com/docs/software/intesis-maps-installer
Use the Ethernet connection or the Console Port (mini USB type B
connector included) to get communication between the gateway and
the configuration tool.
Follow instructions of the user's manual for more details.
Owner’s Record
The serial number is located at the rear of the gateway.
Record this information in the space provided below.
Refer to it whenever you contact upon your gateway
dealer or support team regarding this product.
Serial No.