HMS Networks Intesis INMBSDAL0640500 Installation Sheet Download Page 2

 

 

 

 

 

 
 

© HMS Industrial Networks S.L.U - All rights reserved                

This information is subject to change without notice

 

 

  URL            http://www.intesis.com  

 
 

    Rev.1.2 

                2 / 2

 

 

 

 
 
 

 
 
 

 
 

 
 
 

 
 
 
 
 

 
 
 
 
 
 
 
 

Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 88x106x56 mm  

Recommended space for installation (d

x

w

x

h): 130x115x100mm 

Color: Light Grey. RAL 7035 

 

Push Button 

Button A: Check the user manual 
Button B: Check the user manual 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Operation 
Temperature 

0°C to +50°C 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

 

Operational 
Humidity 

5 to 95%, no condensation 

Power 

1 x Plug-in screw terminal block (3 poles) 

Positive, Negative, Earth 
24VDC/AC +/-10% 
6W(250mA) 

 

Protection  

IP20 (IEC60529) 

LED 
Indicators 

6 x On board LED indicators  

1 x Power LED (Green)  
1 x DALI (Yellow)  
1 x RX (Green)  
1 x TX (Yellow)  
1 x Button A indicator  

                 1 x Button B indicator  

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

DALI 

1 x DALI port (Plug-in screw terminal block 2 poles) 

1500VDC isolation from other communication ports 
DALI guaranteed power: 230mA 
DALI Maximum Power: 250mA 
Voltage rating: 16VDC 
 

 

 

 

 
 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTIONS 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. Respect polarity 

applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table 
below).  The  power  supply  can  be  connected  to  earth  but  only  through  the  negative  terminal,  never 
through the positive terminal. 

 

 
Ethernet / Modbus TCP / Console (UDP & TCP) 
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet 
CAT5 cable. If communicating through the LAN of the building, contact the network administrator and 
make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual 
for more information). With factory settings, after powering up the gateway, DHCP will be enabled for 30 
seconds. After that time, if no IP is provided by a DHCP server, the default IP 192.168.100.246 will be 
set. 
 
DALI 

 

Connect the DALI bus to connectors DA+, DA- 

of gateway’s DALI port. The Intesis gateway provides 

16VDC DALI voltage to the bus. Please, respect polarity when other DALI power supplies are connected 
in the same DALI bus. 

ELECTRICAL & MECHANICAL FEATURES 

This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic 
parts and they must be properly disposed of by following the instructions a

https://intesis.com/weee-regulation

  

 

100 mm (h) 

115 mm (w) 

130 mm (d) 