5.2.15 Trend Log Multiple Object Type 

 

Property Identifier 

Property Datatype 

 Value 

ASHRAE  IBOX 

Object_Identifier 

BACnetObjectIdentifier

 

(Trend_Log_Multiple, 27)

 

R

 

R

 

Object_Name 

CharacterString 

Configurable through BACnet and Config 
Tool

 

R

 

R

 

Object_Type 

BACnetObjectType 

TREND_LOG_MULTIPLE (27)

 

R

 

R

 

Description 

CharacterString 

-  

O

 

-

 

Enable 

BOOLEAN 

 

Start_Time 

BACnetDateTime 

 

Stop_Time 

BACnetDateTime 

 

Log_DeviceObjectProperty 

BACnetARRAY[10] of 
BACnetDeviceObject 
PropertyReference 

 

Log_Interval 

Unsigned 

 

COV_Resubscription_Interval 

Unsigned 

 

Client_COV_Increment 

BACnetClientCOV 

 

Stop_When_Full 

BOOLEAN 

 

Buffer_Size 

Unsigned 

 

Log_Buffer 

List of BACnetLogRecord 

 

Record_Count 

Unsigned 

 

Total_Record_Count 

Unsigned 

 

Notification_Threshold 

Unsigned 

 

R* 

Records_Since_Notification 

Unsigned 

 

R* 

Last_Notify_Record 

Unsigned 

 

R* 

Event_State 

BACnetEventState 

 

Notification_Class 

Unsigned 

 

R* 

Event_Enable 

BACnetEventTransitionBits   

R* 

Acked_Transitions 

BACnetEventTransitionBits   

R* 

Notify_Type 

BACnetNotifyType 

 

R* 

Event_Time_Stamps 

BACnetARRAY[3] of 
BACnetTimeStamp 

 

R* 

EventMessageTexts 

BACnetARRAY[3] of 
CharacterString 

 

R* 

Profile_Name 

CharacterString 

 

Logging_Type 

BACnetLoggingType 

 

Status_Flags 

BACnetStatusFlags 

 

 

* Only available when specific object has a Notification Class configured 

Summary of Contents for Intesis BACnet

Page 1: ...BACnet Server PROFINET IO Device USER MANUAL Issue date 05 2020 r1 0 ENGLISH...

Page 2: ...s and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variabl...

Page 3: ...0 eng HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 3 46 Gateway to connect BACnet MSTP or BACnet IP installations wi...

Page 4: ...2 2 Analog Input Object Type 17 5 2 3 Analog Output Object Type 18 5 2 4 Analog Value Object Type 19 5 2 5 Binary Input Object Type 20 5 2 6 Binary Output Object Type 21 5 2 7 Binary Value Object Typ...

Page 5: ...rial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 5 46 9 2 5 Sending the configuration to Intesis 42 9 2 6 Diagnostic 42 Set up pro...

Page 6: ...sed control systems or devices merging both systems into one The gateway acts as a BACnet IP Server or BACnet MSTP device in its BACnet interface allowing other BACnet devices to perform subscription...

Page 7: ...ct has active subscriptions the new value will be sent to the subscripted BACnet device s From the BACnet system point of view after the start up process the gateway listens to any subscription COV re...

Page 8: ...L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actu...

Page 9: ...t all routing configurations e g ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign De...

Page 10: ...DS COVP A Data Sharing COVP A SubscribeCOVProperty ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP B Data Sharing COVP B SubscribeCOVProperty ConfirmedCOVNotification UnconfirmedCOVNotific...

Page 11: ...ends Inernal B ReadRange T VMT E B Trending Viewing and Modifying Trends External B ReadRange T ATR A Trending Automated Trend Retrieval A ConfirmedEventNotification ReadRange T ATR B Trending Automat...

Page 12: ...onfirmedTextMessage DM TS A Device Management TimeSynchronization A TimeSynchronization DM TS B Device Management TimeSynchronization B TimeSynchronization DM UTC A Device Management UTCTimeSynchroniz...

Page 13: ...Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple ReadRange WriteProperty WritePropertyMultiple Remote Device Managem...

Page 14: ...orted are shown in the table below Object Type ID Supported Management Point Analog Input 0 Analog Output 1 Analog Value 2 Averaging 18 Binary Input 3 Binary Output 4 Binary Value 5 Calendar 6 Command...

Page 15: ...ing O Protocol_Version Unsigned 1 R R Protocol_Revision Unsigned 14 R R Protocol_Services_ Supported BACnetServiceSupported Refer to section 4 Service Types R R Protocol_Object_Types_ Supported BACnet...

Page 16: ...OV_ Subscriptions List of BACnetCOVSubscription List of BACnetCOVSubscription O R Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_ Binding List of BACnetAddressBinding O Auto_Slave_...

Page 17: ...FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Un...

Page 18: ...0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits Configurable through BACnet and Config Tool R R Min...

Page 19: ...ALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits...

Page 20: ...RMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterString Configurable thr...

Page 21: ...ce BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable through BACnet and Conf...

Page 22: ...ity BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable th...

Page 23: ...String O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of...

Page 24: ...us_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Number_Of_...

Page 25: ...racterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN F...

Page 26: ...Object Type Property Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Calendar 6 R R Object_Name CharacterString Configurable through BACnet and Config Tool R R...

Page 27: ...ailySchedule R W Exception_Schedule BACnetARRAY N of BACnetSpecialEvent R W Schedule_Default Any R W List_Of_Object_Property_Refer ences BACnetLIST of BACnetDeviceObjectProper tyReference R R Priority...

Page 28: ...ty Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Notification_Class 15 R R Object_Name CharacterString Configurable through BACnet and Config Tool R R Object_Type BACnetObjectTyp...

Page 29: ...g_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log_Buffer List of BACnetLogRecord R R Record_Co...

Page 30: ...ropertyReference O R Log_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log_Buffer List of BACnet...

Page 31: ...the network is automatically scanned for Intesis BACnet PROFINET modules The network can be rescanned at any time by cliking Scan To change the network settings of a BACnet PROFINET module double clic...

Page 32: ...rt 80 The default web pages provide access to Network configuration parameters Network status information Access to the host application ADIs The network configuration page provides interfaces for cha...

Page 33: ...n unicast packets broadcast and multicast Out Discards Outgoing packets discarded due to no available memory buffers Out Errors Transmission errors Media Counters Description Alignment Errors Frames r...

Page 34: ...y Client MRC It also supports propagating link change to the Media Redundancy Master LED Indicators Network Status LED LED1 LED state Status Comments Off Offline No connection with IO controller Green...

Page 35: ...sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information With factory settings after powering up the gateway DHCP will be enabled for 30 se...

Page 36: ...ect a mini type B USB cable from your computer to the gateway to allow communication between the Configuration Software and the gateway Remember that Ethernet connection is also allowed Check the user...

Page 37: ...tive and reachable from the network connection used by Intesis Check the Intesis Ethernet interface sending Pings to its IP address using a PC connected to the same Ethernet network Check as well with...

Page 38: ...ice in a line topology either Port 1 or Port 2 can be used The cable to be used shall be a straight Ethernet UTP FTP CAT5 cable PROFINET interface contains a dual port Ethernet switch they both operat...

Page 39: ...Tx Rx Expansion Module communication Off There is no activity on this port Tx Blinking green Every data packet sent to Expansion module it blinks Rx Blinking yellow Every data packet received from Ex...

Page 40: ...to download the configuration tool USB Console cable to communicate with gateway Product documentation Intesis MAPS Configuration monitoring tool for Intesis BACnet series 9 2 1 Introduction Intesis M...

Page 41: ...e subsets of information are shown in this window General Gateway general parameters BACnet Server BACnet interface configuration and PROFINET interface parameters Figure 9 2 Intesis MAPS configuratio...

Page 42: ...e Intesis Communication Console window Intesis will reboot automatically once the new configuration is loaded Figure 9 4 Intesis MAPS Receive Send tab After any configuration change do not forget to s...

Page 43: ...ng HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 43 46 Figure 9 5 Diagnostic More information about the Diagnostic se...

Page 44: ...nected to it we strongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth 6 If...

Page 45: ...3 poles Positive Negative Earth 24VDC 10 Max 580mA Push Button Button A Check section 8 Button B Check section 8 Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet...

Page 46: ...reserved This information is subject to change without notice URL https www intesis com 46 46 11 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting w...

Reviews: