background image

7. PLC Configuration  ................................................................................................................... 40

7.1. Export Product GSD File .................................................................................................... 40
7.2. Export Product EDS File  .................................................................................................... 41

8. Verify Operation ..................................................................................................................... 42

8.1. Communicator Status Monitor ........................................................................................... 42
8.2. Communicator LED Indicators  ............................................................................................ 44

9. Maintenance  ......................................................................................................................... 46

9.1. Configuration File Handling  ............................................................................................... 46

9.1.1. Export Configuration  ................................................................................................ 46
9.1.2. Import Configuration  ................................................................................................ 47

9.2. Clear and Revert Configuration  .......................................................................................... 48
9.3. Firmware Management  .................................................................................................... 49

9.3.1. View the Firmware Version  ........................................................................................ 49
9.3.2. Firmware and Configuration Compatibility
 .................................................................... 49
9.3.3. Firmware File Validation 
............................................................................................ 49
9.3.4. Update Firmware ..................................................................................................... 50

10. Troubleshooting  ................................................................................................................... 51

10.1. Diagnostics ................................................................................................................... 51

10.1.1. I/O Data  ............................................................................................................... 51
10.1.2. Event Log .............................................................................................................. 52

10.2. Reset to Factory Settings  ................................................................................................. 53
10.3. Firmware Upgrade Error Management ............................................................................... 55
10.4. Support  ....................................................................................................................... 57

10.4.1. Support Package  .................................................................................................... 57

11. Technical Data ...................................................................................................................... 58

11.1. Technical Specifications ................................................................................................... 58

Anybus

®

 Communicator

 - EtherNet/IP

 Adapter to PROFIBUS DP Device

SCM-1202-200 Version 1.0

Summary of Contents for Anybus Communicator ABC4014

Page 1: ...Anybus Communicator EtherNet IP Adapter to PROFIBUS DP Device USER MANUAL SCM 1202 200 Version 1 0 Publication date 2022 08 31 ENGLISH...

Page 2: ...and because of the many variables and requirements associated with any particular implementation HMS Networks cannot assume responsibility or liability for actual use based on the data examples or il...

Page 3: ...S Network 11 5 5 Rotary Switch Settings 12 5 5 1 Rotary Switches Default Setting 12 5 5 2 Set a Node Address with Rotary Switches 13 5 6 Connect to Power 17 5 7 Security Switch 18 5 8 Lock the Cables...

Page 4: ...tion 48 9 3 Firmware Management 49 9 3 1 View the Firmware Version 49 9 3 2 Firmware and Configuration Compatibility 49 9 3 3 Firmware File Validation 49 9 3 4 Update Firmware 50 10 Troubleshooting 51...

Page 5: ...eferences and Links Cross reference within this document Document Conventions page 1 External link URL www anybus com Safety Symbols DANGER Instructions that must be followed to avoid an imminently ha...

Page 6: ...r operation TIP Helpful advice and suggestions 1 3 Trademarks Anybus is a registered trademark of HMS Networks All other trademarks are the property of their respective holders Anybus Communicator Eth...

Page 7: ...N Ensure that the power supply is turned off before connecting it to the equipment CAUTION This equipment contains parts that can be damaged by electrostatic discharge ESD Use ESD prevention measures...

Page 8: ...ace can be accessed from the following standard web browsers Google Chrome Microsoft Edge Mozilla Firefox 3 3 Mechanical Tools and Equipment Have the following tools available Flat head screwdriver si...

Page 9: ...you can set a static IP address within the same IP address range as the Communicator IP address on the computer accessing the Communicator built in web interface NOTE IPconfig is only available for Wi...

Page 10: ...nnected to a EtherNet IP network and a Master device connected to a PROFIBUS network The Master device can for example be a PLC control system or a Gateway The Communicator main task is to transfer cy...

Page 11: ...input data Output Data The Output data area is read written by the EtherNet IP The Communicator can handle up to 1448 bytes output data 4 3 Data Integrity A snapshot of the process data buffer between...

Page 12: ...E Configuration port F EtherNet IP port x 2 G PROFIBUS DSUB connector H Cable tie mount I Laser engraved connectors designation J Security switch K Factory reset button L Laser engraved label with pr...

Page 13: ...rail and that the rail is properly grounded Figure 4 Attach the Communicator on the DIN rail To attach the Communicator on the DIN rail 1 Insert the upper end of the DIN rail clip into the DIN rail 2...

Page 14: ...herNet IP network To Do Next Connect the Communicator to the PROFIBUS network set the node address on the rotary switches and connect to power Check LED status refer to Communicator LED Indicators Any...

Page 15: ...3 Line B 4 RTS 5 GND Bus 6 5 V Bus Out 7 Not used 8 Line A 9 Not used Housing PE To Do Next Connect the Communicator to the EtherNet IP network set the node address on the rotary switches and connect...

Page 16: ...Default Setting By default the value on the three rotary switches are set to 000 Figure 7 Rotary switches default setting 000 Anybus Communicator EtherNet IP Adapter to PROFIBUS DP Device Rotary Switc...

Page 17: ...ing is 000 The node address values are set in hexadecimal hex Minimum value is 00 Each node address may only occur once in the network The node address is read from the center rotary switch x16 to the...

Page 18: ...re 8 Disconnect Communicator from power Procedure Use a screwdriver to change the rotary switch position Ensure that the rotary switches engage correctly Anybus Communicator EtherNet IP Adapter to PRO...

Page 19: ...y switch B to 1 hex 3 Set the front rotary switch C to 2 hex The center rotary switch B 1 hex 1 dec and the front rotary switch C 2 hex 2 dec The node address expressed in decimal numbers is therefore...

Page 20: ...address is active as soon as the Communicator is powered on NOTE Changing the address settings on the rotary switches during operation is ignored For a new address to take effect power cycle the Comm...

Page 21: ...power 1 Insert the cable wires to the terminal block and tighten the wire clamp screws Power port Pin Description 1 12 30 VDC Power Connector 2 Ground GND 3 Functional Earth FE 2 Connect the terminal...

Page 22: ...ed via the PLC is still available To Lock and Unlock the Security Switch Figure 11 Security switch in locked and unlocked position Use a pointed object such as a ballpoint pen To lock the security swi...

Page 23: ...the security switch is in its locked position the security switch status LED turn solid green unlocked position the security switch status LED is turned off Security Switch Anybus Communicator EtherN...

Page 24: ...gure 13 Lock the cables To strain relieve the cables place a cable tie in the holder and lock the cables Anybus Communicator EtherNet IP Adapter to PROFIBUS DP Device Lock the Cables Page 20 of 60 SCM...

Page 25: ...blade screwdriver size 5 5 mm available Procedure Remove the Communicator from the DIN Rail 1 Insert the screwdriver into the Communicator DIN rail locking mechanism 2 To unlock the Communicator DIN...

Page 26: ...DIN rail locking mechanism while you unhook the Communicator from the DIN rail Figure 15 Unhook the Communicator Anybus Communicator EtherNet IP Adapter to PROFIBUS DP Device DIN Rail Demount Page 22...

Page 27: ...work Network 1 EtherNet IP Network 2 PROFIBUS Connect to PC and Power 1 Connect an Ethernet cable between the Communicator and your PC 2 Connect the Communicator to a power supply Communicator Configu...

Page 28: ...rt Port 3250 UDP is open in your PC Windows Firewall NOTE Ensure that the security switch is unlocked HMS IPconfig cannot configure the Communicator if the security switch is locked Procedure 1 Instal...

Page 29: ...click Communicator Result You are redirected to the Communicator built in web interface Home page Access the Built In Web Interface From HMS IPconfig Anybus Communicator EtherNet IP Adapter to PROFIBU...

Page 30: ...ange to a static IP address on your computer internet access may be lost Procedure 1 On the PC accessing the Communicator built in web interface set a static IP address within the same IP address rang...

Page 31: ...the network settings for the PROFIBUS network I O configuration Configure input and output data sizes and endian conversion Files firmware Save settings in a configuration files upload configuration...

Page 32: ...Figure 17 IP Settings DHCP enabled By default the IP settings are provided by the high level network DHCP server The DHCP enabled checkbox is selected Anybus Communicator EtherNet IP Adapter to PROFI...

Page 33: ...ss The EtherNet IP network Gateway address in IPv4 dot decimal notation If there is no gateway available set the Gateway address to 0 0 0 0 Primary DNS server The EtherNet IP network Primary DNS in IP...

Page 34: ...n to the Communicator it specifies an I O data size By default the Communicator is set to Accept Only Matching I O Sizes The connections must match the I O size configured on the EtherNet IP page refe...

Page 35: ...the Communicator rotary switches are sett to 000 Figure 21 PROFIBUS address setting In the PROFIBUS address field enter the Communicator node address PROFIBUS Settings Anybus Communicator EtherNet IP...

Page 36: ...izes for the networks deselect the Same I O sizes for both networks checkbox Endian Swap Big endian The big endian format places the most significant byte of the data at the byte with the lowest memor...

Page 37: ...s Swap 2 bytes A B C D becomes B A D C Words Swap 4 bytes A B C D becomes C D A B Bytes and words A B C D becomes D C B A Detailed swap With Detailed swap you can select a Endian swap method for each...

Page 38: ...le 1 In the Endian swap drop down menu for the desired network s select Detailed swap 2 Build the detailed endian swap To add an endian swap object Drag and drop the desired endian swap object from th...

Page 39: ...can select multiple endian swap objects and duplicate the group Figure 26 Duplicate endian swap object To change the order of the endian swap objects drag and drop the endian swap objects in the list...

Page 40: ...Net IP network or the PROFIBUS network where the Communicator is connected Procedure To make the settings take effect download the configuration to the Communicator 1 In the web interface header click...

Page 41: ...1 To open the Configuration Notes window click on the comments icon Figure 29 Configuration note comment icon 2 To add a new configuration note click Add Figure 30 Add new configuration note Configur...

Page 42: ...e 6 9 2 View and Edit Configuration Notes To view and or edit a note click on the comments icon Figure 32 Example The comment icon indicates that there are three added notes The configuration notes ar...

Page 43: ...Figure 33 Example The Configuration Notes window with added notes Configuration Notes Anybus Communicator EtherNet IP Adapter to PROFIBUS DP Device SCM 1202 200 Version 1 0 Page 39 of 60...

Page 44: ...n be used on the high level network Figure 34 Export Product GSD File You find the PROFIBUS GSD file on the Communicator built in web interface PROFIBUS page Files firmware page and on the Support pag...

Page 45: ...mmunicator Figure 35 Export Product EDS File You find the EtherNet IP EDS file on the Communicator built in web interface EtherNet IP page Files firmware page and on the Support page To export the EDS...

Page 46: ...g status Figure 36 Home page Gateway status Overview the Communicator LED indications remotely Refer to Communicator LED Indicators Network Status and Settings Overview communication status and the cu...

Page 47: ...Specification Check Function Initial state where non network components are started and configured Network startup in progress Invalid configuration detected Normal operation Communicator Status Monit...

Page 48: ...reen flashing EtherCAT device in PRE OPERATIONAL state EtherNet IP online no connections established Modbus TCP online no messages received Used by engineering tools to identify the node on the networ...

Page 49: ...still represents the states described in the table above LED C PROFIBUS Lower connector Operation Status PROFIBUS Off No data exchange Green flashing Clear data exchange Green one flash N A Green Ope...

Page 50: ...the same settings to configure additional Communicator Figure 38 Files firmware page To export a configuration file In Files firmware click Export The configuration settings are stored in a conf file...

Page 51: ...he Communicator address settings window To import IP settings from the selected configuration file click Imported settings All configuration settings are imported To continue using the current IP sett...

Page 52: ...apply the change click Apply in the web interface header and follow the instructions To Revert the Configuration When you want to remove any configuration made in a current session and re load the con...

Page 53: ...irmware File Validation Before the firmware file is imported into the system the firmware upgrade function perform a validation of the file to ensure that the firmware is compatible with the Communica...

Page 54: ...box browse to and select the firmware file and click Open 4 To start the firmware upgrade click Update firmware The firmware file is validated and transferred Result If the firmware file pass the val...

Page 55: ...eached the oldest messages are discarded when new messages are added Switch between the OT networks To switch between the networks select EtherNet IP or PROFIBUS Select how data is displayed To choose...

Page 56: ...s ms The date and time when the event occurred Message A brief description of the event Severity The severity of the event occurred For description of the symbols see Communicator Status Monitor Sourc...

Page 57: ...e Communicator from power Figure 45 Disconnect power 2 Use a pointed object such as a ballpoint pen to press and hold the Reset button Figure 46 Press and hold Reset button Reset to Factory Settings A...

Page 58: ...ommunicator configuration is reset to the factory default configuration or the current configuration after firmware upgrade To Do Next To ensure that the Communicator built in web interface is synchro...

Page 59: ...king firmware is still available on the flash but it is not active Procedure To complete the interrupted firmware update 1 Disconnect the Communicator from power Figure 49 Disconnect power 2 Reconnect...

Page 60: ...irmware upgrade LED indication Result The Communicator recover and return to normal operation Figure 52 Recover and return to normal operation To Do Next To check LED status refer to Communicator LED...

Page 61: ...he information in the support package are available to open and read the files are not locked or encrypted Generate Support Package On the Support page click Generate A zip file with the support files...

Page 62: ...circuit protection Power consumption Typical 160 mA 24 V Max 400 mA 12 V Storage temperature 40 to 85 C Operating temperature 25 to 70 C Humidity EN 600068 2 78 Damp heat 40 C 93 humidity for 4 days E...

Page 63: ...This page is intentionally left blank...

Page 64: ...This page is intentionally left blank...