INSTALLATION

INSTRUCTIONS

Indoor air quality transmitters

Siro series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.

•  Failure to observe safety information and comply with instructions 

can result in PERSONAL INJURY, DEATH AND/OR PROPERTY 

DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered system 

whose specifications and performance characteristics are not 
designed or controlled by HK Instruments. Review applications 
and national and local codes to assure that the installation will 
be functional and safe. Use only experienced and knowledgeable 
technicians to install this device.

Thank  you  for  choosing  an  HK  Instruments  Siro  series  indoor  air 
quality transmitter. The Siro series transmitters are intended for use 
in building automation systems in the HVAC/R industry.

Siro

 is an indoor air quality transmitter with a modern design. The 

transmitter is available with several optional air quality sensors. The 
modular device can be equipped with CO

2

 concentration and VOC 

(Volatile  Organic  Compounds)  measurements  or  alternatively  PM 
(Particulate Matter) measurement and in addition temperature and 
humidity measurements. It offers easy installation and adjustment, 
several different model options and various output signals that are 
configurable separately for each measurement parameter.

The Siro series devices are available with user interface that includes 
LCD display and buttons making the configuration of the device quick 
and easy. An external configuration tool is available for devices with

-

out user interface. Siro utilizes the industry standard NDIR measure

-

ment principle with self-calibrating ABC logic

TM

 for CO

2

 measurement.

•  PM concentration to measures the size and amount of particulates 

in the indoor air for example to assess the performance of air filters

•  temperature and humidity in HVAC/R environment

SPECIFICATIONS

Performance

Measurement ranges:

CO

2

:  

 

 

0–2000 ppm / 400–2000 ppm

  

 

(selectable via jumper)

VOC:    

 

CO₂eq: 400–2000 ppm

 

 

 

TVOC ppm: 0–30.0 ppm

 

 

 

TVOC µg/m

3

: 0–10000 µg/m

3

  

 

IAQ index:  1–5 (UBA rating)

 

PM1/PM2.5/PM10:  0–50 μg/m

³

 / 0–500 μg/m

³

 

 

 

(selectable via jumper)

 

 

 

IAQ index: 1-5 (WHO rating)

Temperature:    

0...50 °C

Relative humidity:  

0–100 %rH

Accuracy:

CO

2

:  

 

 

±33 ppm + 3 % of reading (typical),

 

 

 

additional ±60 ppm for first weeks

VOC*:    

 

15 % of reading (typical)

*VOC sensor is tuned for typical IAQ Mix of 22 VOCs as 
defined by Mølhave et al. (1997)

PM:    

0…100 µg/m3: 

PM2.5:   

 

±15 µg/m³ (at 25 ⁰C ±5 ⁰C)

PM1/PM10*: 

 

±25 µg/m³ (at 25 ⁰C ±5 ⁰C)

100…1000 µg/m3: 

PM2.5:   

 

±15 % (at 25 ⁰C ±5 ⁰C)

PM1/PM10*: 

 

±25 % (at 25 ⁰C ±5 ⁰C)

*PM1 and PM10 values are calculated from PM2.5 
measurement reading with the default particle distribution.

Temperature:    

±0.5 ⁰C (typical at 20 ⁰C)

Relative humidity:  

±2.4 %rH (typical at 20 ºC, 30 %rH)

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

CO₂:  

 

 

ppm

VOC:    

 

CO

2

eq: ppm

 

 

 

TVOC: ppm, µg/m

³

PM: 

 

 

PM1/PM2.5/PM10: µg/m

³

Temperature:    

°C/°F

Relative humidity:  

%rH

Measuring element:

CO

2

:

Non-dispersive infrared (NDIR)

VOC:

Complementary Metal Oxide Semiconductor 

(CMOS)

PM:

 

Laser-based light scattering particle sensing

Temperature:

Integrated to CMOS

Relative humidity:

Thermoset polymer capacitive sensing element

Calibration:

 

Automatic self-calibration ABC Logic

TM 

for CO

measurement

Environment:

Operating temperature: 0...50 °C

Storage temperature: -20...70 °C

Humidity: 0 to 95 %rH, non condensing

Physical

Dimensions: 

Case: 95 x 103 x 30 mm

(width x height x depth)

Weight: 

130 g

Mounting: 

2 screw holes slotted, distance c/c 60 mm

Materials: 

Case: ABS

Protection standard: 

IP20

Display (optional)

Monochrome LCD, 38 x 23 mm

Electrical connections:

  

8-pin spring loaded terminal block

0.2...1.5 mm² (16-24 AWG)

Electrical

Input:

  

24 VAC or VDC, ±10 %

Power consumption: 2 W max + 25 mW for each 

voltage output or 50 mW for each current output

Outputs: 

4 outputs, have to select voltage or current

Voltage outputs:

 

0–10 V

 

2–10 V / 0–5 V (optional, display or   

 

configuration tool required)

Current output:

 

4–20 mA (optional)

Output signal limits:

 

Voltage outputs: R > 1 kΩ

 

Current output: R > 20 Ω, R < 500 Ω

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

Siro series devices are commonly used to monitorand control:
•  indoor air quality in offices, public spaces, meeting rooms and

 

classrooms

•  CO

2

 and VOC concentration to regulate demand-controlled 

ventilation and to keep the indoor air quality in a good level

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

RoHS 2

2011/65/EU

Summary of Contents for SIRO Series

Page 1: ...00 ppm 400 2000 ppm selectable via jumper VOC CO eq 400 2000 ppm TVOC ppm 0 30 0 ppm TVOC µg m3 0 10000 µg m3 IAQ index 1 5 UBA rating PM1 PM2 5 PM10 0 50 μg m 0 500 μg m selectable via jumper IAQ index 1 5 WHO rating Temperature 0 50 C Relative humidity 0 100 rH Accuracy CO2 33 ppm 3 of reading typical additional 60 ppm for first weeks VOC 15 of reading typical VOC sensor is tuned for typical IAQ...

Page 2: ...TOR 2 1 5 4 TEMP OR rH TEMP SENSOR 3 mA MODULE Pin header Description Open Connected Open Connected CO2 PM output range selection 400 2000 ppm CO2 models 0 2000 ppm CO2 models 0 500 μg m3 PM models 0 50 μg m3 PM models Pin header Description Open Connected Menu lock Menu lock disabled Menu lock enabled 1 2 Connector Description A B RS485 Modbus RTU slave optional DATA DATA 24 V GND GND Power suppl...

Page 3: ...ill be responsive to changes to the room conditions The Siro should be mounted on a flat surface Do not locate the Siro where it can be affected by Direct sunlight Drafts or dead areas behind doors Radiant heat from appliances Concealed pipes or chimneys Outside walls or unheated uncooled areas 2 Use the device as a template and mark the screw holes 3 Mount the wall plate with screws CAUTION Incor...

Page 4: ...ry and stated in the contract The seller will give a new warranty for goods that have been replaced or repaired within the warranty how ever only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or exchange costs Under no circumstance is the seller liable for damages compe...

Reviews: