HK Instruments RHT DUCT Series Installation Instructions Download Page 1

Copyright HK Instruments 2017

www.hkinstruments.fi

Installation version 5.0 2017

INSTALLATION

INSTRUCTIONS

HUMIDITY TRANSMITTERS

RHT Duct Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank you for choosing an HK Instruments RHT Duct series relative 
humidity transmitter. The RHT series is intended for use in commer

-

cial environments in HVAC/R applications.

RHT Duct is a relative humidity transmitter with temperature out

-

put installed in air ventilation duct. Illuminated display ensures easy 
readability also from a distance. The RHT has a screwless lid and an 
easily adjustable mounting flange that make the installation of the 
device easy.

RHT Duct series devices are commonly used to monitor and control:
•  Relative humidity and temperature levels of incoming and return air 

in ventilation system

SPECIFICATIONS

Performance

Measurement ranges:

Temperature: 0...50 °

 

F

°

 

32...122

 

/

C

Relative humidity: 0–100 %

Accuracy:

Temperature: <0.5 º

°F

 

<0.9

 

/

C

Relative humidity: ±2...3 % at 0...50 °C and 10–90 % rH

Total error band includes accuracy, hysteresis and

temperature effect over 5...50 °C and 10–90 % rH.

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

°C and % rH

Measuring element:

Temperature: NTC10K

Relative humidity: Thermoset polymer capacitive

sensing element

Environment:

Operating temperature: 0...50 °

 

°F

 

32...122

 

/

C

Storage temperature: -20...70 °

 

°F

 

-4...158

 

/

C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 119 x 100 x 44.7 m

1.76"

 

x

 

3.94

 

x

 

4.68

 

/

m

Probe: L=188 mm, d=12 m

 

 

.47"

d=0

 

L=7.40",

 

/

m

Mounting:

With flange, adjustable 0...188 m

0...7.40"

 

/

m

Weight: 

150 

 oz

5.30

 

/

g

Materials: 

Case: ABS

Cover: PC

Probe: ABS

Mounting flange: LLPDP

Protection standard: 

IP54

Electrical connections:

4 spring loaded terminals

(24 V, GND, rH, T)

0.2–1.5 mm

2

 (12–24 AWG)

Electrical

Supply voltage: 24 VAC or VDC ±10 %

Current consumption: max 90 mA (at 24 V) + 10 mA for 

each voltage output

Output signals for every media:

0/2...5/10 VDC, Load R minimum 1 kΩ

Conformance

Meets requirements for CE marking:

EMC Directive: 2014/30/EU

RoHS Directive: 2011/65/EU

WEEE Directive: 2012/19/EU

INTRODUCTION

APPLICATIONS

WARNING

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL