HK Instruments DPT100 Manual Download Page 3

 

 

 

Zero-point adjustment 

 

Note!

 Supply voltage must be connected one hour before the 0-point adjustment is carried out. 

 
 

1) Loose both tubes from the pressure  and – 
2) Push zero button until the red led turns ON. 

 

3) Wait until LED turns off and then install tubes again to the pressure inlets 

 
It is recommended to adjust the zero point every 12 months during normal operation 

* If the transmitter is equipped with automatic zero element the manual push button adjustment is not required. 

 
Optional auto zero element * 

 

Optional auto zero element makes the DPT transmitter maintenance free for 
periodical push button zeroing. Element automatically adjusts the transmitters 
zero point from time to time, this eliminates the zero point long term drift of the 
piezoresistive sensing element. 

 

 

 

Zero point adjustment is carried out every 10 minutes. During zero point 
adjustment the output and display values will freeze to the latest measured 
value. The automatic zero point adjustment takes 4 seconds. 

 

 

Dimensions 

 

   

 

 

 

   

 

 

 

 

   

HK INSTRUMENTS OY

FIN-40950 MUURAME FINLAND

Pa

DPT

7

1

.5

9

5

.0

90.0

36.0

Summary of Contents for DPT100

Page 1: ...500 Pa 0 1000 Pa 1 5 1 Pa 8 Pa DPT2 5K D AZ Q 0 1500 Pa 0 2500 Pa 1 5 1 Pa 24 Pa DPT5K D AZ Q 0 2500 Pa 0 5000 Pa 1 5 1 Pa 24 Pa 4 range model R4 for 4 measuring range D for display AZ for autozero element Q for square root output range 1 range 2 range 3 range 4 Accuracy FS over operation temp 10 50 C range 1 4 Long term stability typical 1 year AZ without AZ DPT1000 R4 D AZ Q 250Pa 500 Pa 750 Pa ...

Page 2: ...nnectors ABS Tubing PVC soft Connections Electrical connections 4 screw terminals max 1 5 mm2 Cable entry M16 Pressure connections Male 5 0 mm and 6 3 mm Weight 150 grams with accessories 290 grams Dimensions 90 0 x 71 5 x 36 0 mm General ambient condition Temperature range Operation 10 50 C 5 50 C for AZ model Storage 20 70 C Ambient humidity 0 to 95 RH Safety Protection standard IP54 Conformance...

Page 3: ...the manual push button adjustment is not required Optional auto zero element Optional auto zero element makes the DPT transmitter maintenance free for periodical push button zeroing Element automatically adjusts the transmitters zero point from time to time this eliminates the zero point long term drift of the piezoresistive sensing element Zero point adjustment is carried out every 10 minutes Dur...

Page 4: ...1000 The pressure values on the sticker depends on the model 500Pa 1000Pa 0 8s 4s jumper without jumper Jumpers 4 20mA ZERO 0 1 4s 500 1000 24VDC GND 0 10V Jumpers ZERO 0 8 4s Jumper 2 Jumper 3 4 range model e g DPT1000 R4 0 8s 4s 250Pa 500Pa 750Pa 1000Pa 250Pa 500Pa 750Pa 1000Pa The range sticker located inside the lid Pressure values depends on the model e g DPT1000 R4 Jumper 2 Jumper 3 Jumpers ...

Reviews: