Installation version 2.0 2021

INSTALLATION
INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 
DPT-Priima Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank  you  for  choosing  an  HK  Instruments  DPT-Priima  differential 
pressure transmitter. DPT-Priima is a high-precision differential pres-
sure transmitter engineered especially for cleanrooms and other high 
accuracy applications. DPT-Priima has an automatic zero point calibra-
tion and is optionally available with span point calibration, local display 
and  calibration  certificate.  The  versatility  of  the  device  is  enhanced 
by eight selectable measuring ranges and by outputs with a voltage or 
current signal.

DPT-Priima is commonly used in applications requiring high 
measurement accuracy:
• monitoring pressure in cleanrooms
• monitoring pressure difference across the building envelope
• monitoring pressure and flow

SPECIFICATIONS

Performance

Measurement accuracy* (from applied pressure):

0.4 % ±0.4 Pa

(including: general accuracy, linearity, hysteresis, 

long term stability, and repetition error) 

Output accuracy*:

Voltage: 

±

 0.025 V at 25 

°C

Current: 

±

 0.04 mA typical, at 25 

°C

, load 100 Ω

 ±

 0.1 mA max, at 

25 

°C

, load 20–500 Ω

*after an half-hour warm-up time

Overpressure:

Proof pressure: 10 kPa

Burst pressure: 30 kPa

Zero point calibration:

Automatic autozero and manual pushbutton

Response time:

0.4 s or 8.0 s, selectable via jumper

(63 % of the change)

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Pa, kPa, mbar, inchWC, mmWC, psi, selectable 

via jumper

Measuring element:

MEMS, no flow-through

Environment:

Operating temperature: -5...50 °C, 

Temperature compensated range 0...50 °C

Storage temperature: -40...70 °C,

Humidity: 0 to 95 % rH, non-condensing

Physical

Dimensions: 

Case: 90.0 x 95.0 x 36.0 mm

Weight: 

140g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:  

Case: ABS

Lid: PC

Duct connectors: ABS 

Tubing: PVC

Protection standard: 

IP54

Display (Optional)

2-line display (12 characters/line)

Line 1: active measurement

Line 2: units

Electrical connections:

4-screw terminal block

Wire: 0.2–1.5 mm

2

  (12–24 AWG)

Cable entry: M16

Pressure fittings:

Male ø 5,2 mm

+ High pressure

− Low pressure

Electrical

Voltage:

Circuit: 3-wire (V Out, 24 V, GND)

Input: 24 VAC or VDC, ±10 %

Output: 0–10V / 2–10V

Power consumption: <1.0 W, 

Resistance minimum: 1 kΩ

Current:

Circuit: 3-wire (mA Out, 24 V, GND)

Input: 24 VAC or VDC, ±10 %

Output: 4–20 mA

Power consumption: <1.2 W,

Maximum load: 500 Ω

Minimum load: 20 Ω

 

Conformance

Meets the requirements for:

 

 

CE:    

UKCA:

EMC: 

 

2014/30/EU 

S.I. 2016/1091

RoHS:   

2011/65/EU 

S.I. 2012/3032

WEEE:   

2012/19/EU 

S.I. 2013/3113

INTRODUCTION

APPLICATIONS

WARNING

RoHS

COMPLIANT

Summary of Contents for DPT-Priima Series

Page 1: ...racy monitoring pressure in cleanrooms monitoring pressure difference across the building envelope monitoring pressure and flow SPECIFICATIONS Performance Measurement accuracy from applied pressure 0 4 0 4 Pa including general accuracy linearity hysteresis long term stability and repetition error Output accuracy Voltage 0 025 V at 25 C Current 0 04 mA typical at 25 C load 100 Ω 0 1 mA max at 25 C l...

Page 2: ...3 0 4 3 95 0 36 0 5 2 4 2 Figure 1a Surface mounting INSTALLATION 1 Mount the device in the desired location see step 1 2 Open the lid and route the cable through the strain relief and connect the wires to the terminal block s see step 2 3 The device is now ready for configuration WARNING Apply power only after the device is properly wired Figure 2b Wiring diagram current output A 0 10 V 2 10 V 4 ...

Page 3: ... Chart 2 STEP 5 SELECTING THE MEASUREMENT RANGE 1 Determine the range number a Find the measurment unit in Chart 1 selected in step 4 b Find the required measurement range on the same line as the measurement unit a above and determine the range number in the header STEP 4 SELECTING THE MEASUREMENT UNIT No jumper Circuit open Jumper stored Jumper installed Circuit closed Grey colour indicates that ...

Page 4: ...calibration The autozero adjustment takes 4 seconds after which the device returns to its normal measuring mode During the 4 second adjustment period the output and display values will freeze to the latest measured value Transmitters equipped with the autozero calibration are virtually main tenance free and manual zeroing is not required NOTE Always zero the device before use To zero the device tw...

Reviews: