Copyright HK Instruments 2019

www.hkinstruments.fi

Installation version 8.0 2019

STEP 2: WIRING DIAGRAMS

CONFIGURATION 

CONTINUED

For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable(s). 
2) Connect the wires as shown in figure 2a and 2b.
3) Tighten the strain relief.

Figure 2a - Wiring diagram

Figure 2b - Wiring diagram example for input signals

NOTE! Always zero the device before use.

Supply voltage must be connected one hour before the zero point 
adjustment is carried out. Access via Modbus or by push button.

1) Loose both tubes from the pressure  and -.
2) Press the select button briefly.

3) Wait until the LED turns off and then install tubes again for the 

pressure inlets.

 

STEP 3: CONFIGURATION

Input 1

Input 2

GND

GND

Pt1000

NTC10k

J1
J2
J3

IN1

IN2

Input 1 Pt1000 temperature:

Function 04 - Read input register 3x0005

Input 2 NTC10k temperature:

Function 04 - Read input register 3x0008

1) Activate the device Menu by pushing the the select button for 2 

seconds. 

2) Select the address for Modbus: 1...247

    

BAUD RATE

   9600

  

SELECT

UP

DOWN

       

ADDRESS

    99

  

SELECT

UP

DOWN

  

PARITY BIT

   NONE

  

SELECT

UP

DOWN

3) Select the baud rate: 9600/19200/38400.

4) Select the parity bit: None/Even/Odd

5) Select the pressure unit for display: Pa/inchWC/mmWC/psi/mbar

PRESS. UNIT

    Pa

  

SELECT

UP

DOWN

6) Select the response time: 1...20 s

RESPONSETIME

    20 s

SELECT

UP

DOWN

7) Push the select button to exit menu.

  SELECT

 EXIT MENU

SELECT

 

STEP 4: ZERO POINT ADJUSTMENT

SELECT

 

STEP 5: INPUT SIGNAL CONFIGURATION

Input signals can be read over Modbus via DPT MOD RS485 interface.

Signals

Accuracy for measurement

Resolution

0...10 V

< 0,5 %

0,1 %

NTC10k

< 0,5 %

0,1 %

Pt1000

< 0,5 %

0,1 %

Ni1000/(-LG)

< 0,5 %

0,1 %

BIN IN (potential free contact)

The jumpers should be set according to the instructions below and the 
value should be read from the right register. Both inputs can be config-
ured independently.

Figure 3 - Input signal configuration

J1
J2
J3

IN1

IN2

J1

J1

J1

J2

J2

J2

J3

J3

J3

NTC10k / BIN IN

Pt1000 / Ni1000(-LG)

0...10 V

A
B

24 V
GND

+ Power Supply

24VDC / 24VAC

Input 1

Input 2

GND

GND

Modbus

Summary of Contents for DPT-IO-MOD Series

Page 1: ...asurement points DPT IO MOD series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy from applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Including general ac...

Page 2: ...y for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections DPT DPT Display connection A B 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal block...

Page 3: ...er 3x0008 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 5 Select the pressure unit for display Pa inchWC mmWC psi mbar PRESS UNIT Pa SELECT UP DOWN 6 Select the response...

Page 4: ...y for goods that have been replaced or repaired within the warranty however only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or ex change costs Under no circumstance is the seller liable for damages compensation for indirect damage Register Parameter description Data ...

Reviews: