HK Instruments DPT-Dual-MOD Series Installation Instructions Download Page 3

Copyright HK Instruments 2014

www.hkinstruments.fi

Installation version 1.0 2014

STEP 2: WIRING DIAGRAMS

CONFIGURATION 

CONTINUED

For CE compliance, a properly grounded shielding cable is required.
1) Unscrew the strain relief and route the cable(s). 
2) Connect the wires as shown in figure 2a and 2b.
3) Tighten the strain relief.

Figure 2a - Wiring diagram

Figure 2b - Wiring diagram example for input signals

NOTE! Supply voltage must be connected one hour before the 
zero point adjustment is carried out. Access via Modbus or by 
push button.

1) Loose both tubes from the pressure  and -.
2) Press the select button briefly.

3) Wait until the LED turns off and then install tubes again for 

the pressure inlets.

It is recommended that the zero point is adjusted every 12 
months during normal operation.

 

STEP 3: CONFIGURATION

Input 1

Input 2

GND

GND

Pt1000

ntc10k

J1

J2

J3

IN1

IN2

Input 1 Pt1000 temperature:

Function 04 - Read input register 3x0005

Input 2 ntc10k temperature:

Function 04 - Read input register 3x0008

1) Activate the device Menu by pushing the the select button for 2 
seconds. 
2) Select the address for Modbus: 1...247

    

BAUD RATE

   9600

  

SELECT

UP

DOWN

       

ADDRESS

    99

  

SELECT

UP

DOWN

  

PARITY BIT

   NONE

  

SELECT

UP

DOWN

3) Select the baud rate: 9600/19200/38400.

4) Select the parity bit: None/Even/Odd

5) Select the pressure unit for display: Pa/inchWC/mmWC/psi/mbar

PRESS. UNIT

    Pa

  

SELECT

UP

DOWN

6) Select the response time: 1...20 s

RESPONSETIME

    20 s

SELECT

UP

DOWN

7) Push the select button to exit menu.

  SELECT

 EXIT MENU

SELECT

 

STEP 4: ZERO POINT ADJUSTMENT

SELECT

 

STEP 5: INPUT SIGNAL CONFIGURATION

Input signals can be read over Modbus via DPT MOD RS485 
interface.

Signals

Accuracy for measurement

Resolution

0...10 V

< 0,5 %

0,1 %

NTC10k

< 0,5 %

0,1 %

Pt1000

< 0,5 %

0,1 %

Ni1000/(-LG)

< 0,5 %

0,1 %

BIN IN (potential free contact)

The jumpers should be set according to the instructions below and 
the value should be read from the right register. Both inputs can be 
configured independently.

Figure 3 - Input signal configuration

J1

J2

J3

IN1

IN2

J1

J1

J1

J2

J2

J2

J3

J3

J3

NTC10k / BIN IN

Pt1000 / Ni10007(-LG)

0...10 V

A
B

24 V

GND

+ Power Supply

24VDC / 24VAC

Input 1

Input 2

GND

GND

Summary of Contents for DPT-Dual-MOD Series

Page 1: ... series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy from applied pressure 1 5 1 Pa Including general accuracy temperature drift linearity hysteresis long term stability and repetition error Response time 1 20 s selectable via menu Max pres...

Page 2: ...WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws not included Figure 1b Mounting orientation Figure 1c Application connections Display connection A B 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal blocks Pressure sens...

Page 3: ...re Function 04 Read input register 3x0008 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 5 Select the pressure unit for display Pa inchWC mmWC psi mbar PRESS UNIT Pa SELE...

Page 4: ...correctly fulfilled his her duties arisen from the delivery and stated in the contract The seller will give a new warranty for goods that have been replaced or repaired within the warranty however only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or exchange costs Unde...

Reviews: