HK Instruments DPT-Dual-MOD Series Installation Instructions Download Page 1

Copyright HK Instruments 2014

www.hkinstruments.fi

Installation version 1.0 2014

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 
DPT-Dual-MOD Series

 WARNING

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 
PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national an local codes to assure that the 
installation will be functional and safe. Use only experienced 
and knowledgeable technicians to install this device.

SPECIFICATIONS

INTRODUCTION

Thank  you  for  choosing  an  HK  Instruments  DPT-Dual-MOD  se-
ries  differential  pressure  transmitter.  DPT-Dual-MOD  combines 
two  differential  pressure  transmitters  into  one  device.  It  offers  a 
possibility to measure pressure from two different points. It has a 
Modbus interface and an Input terminal. When using the Input ter-
minal, temperature transmitters can be replaced with temperature 
sensors. As a result you will save in costs of the devices and in the 
installation costs.

APPLICATIONS

DPT-Dual-MOD series devices are commonly used in HVAC/R
systems for:
•  fan, blower and filter monitoring
•  pressure and flow monitoring
•  valve and damper control
•  pressure monitoring in cleanrooms

SPECIFICATIONS

Performance

Accuracy

 (from applied pressure):

±1.5 % + 1 Pa  
(Including: general accuracy, temperature drift, linearity, 
hysteresis, long term stability and repetition error)

Response time:

1...20 s selectable via menu

Max pressure:

400 kPa

Communication

Protocol: MODBUS over Serial Line
Transmission Mode: RTU
Interface: RS485
Byte format (11 bits) in RTU mode:
 

Coding System: 8-bit binary

 

Bits per Byte:

 

 

1 start bit

 

 

8 data bits, least significant bit sent first

 

 

1 bit for parity

 

 

1 stop bit

Baud rate: selectable in configuration
Modbus address: 1−247 addresses selectable in
configuration menu

Zero point calibration options:

• Manual pushbutton autozero
• Via Modbus write coil
Response Time:
0.8 sec, 2.0 sec, or 10 sec selectable in configuration
menu

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units on display:

Selectable via menu (Pa, mbar, inchWC, mmWC, psi)

Measuring element:

Piezoresistive

Environment:

Operating temperature: -10...+50 

°C

Storage temperature: -20...+70 °C
Humidity: 0 to 95 % rH

Physical

Dimensions: 

Case:

 

102.0 x 71.5 x 36.0 mm 

Weight: 

150 g, with accessories 290 g

Mounting:

 

2 each 4.3 mm screw holes, one slotted

Materials:

   

Case: ABS
Lid: PC

Protection standard:

 

IP54

Display

:

2-line display (12 characters/line)
Line 1: active measurement, inlet A
Line 2: active measurement, inlet B

Electrical Connections:

4+3 spring load terminals, max 1.5 mm

2

Cable Entry: M20

Pressure connections:

Male    5,0 mm and 6,3 mm

Electrical

Supply voltage: 

24 VAC or VDC ± 10 %

Power consumption:

< 1.3 W

Output signal:

via Modbus

 

Conformance

Meets requirements for CE marking:
EMC directive 2004/108/EC
RoHS Directive 2002/95/EC

Summary of Contents for DPT-Dual-MOD Series

Page 1: ... series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control pressure monitoring in cleanrooms SPECIFICATIONS Performance Accuracy from applied pressure 1 5 1 Pa Including general accuracy temperature drift linearity hysteresis long term stability and repetition error Response time 1 20 s selectable via menu Max pres...

Page 2: ...WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws not included Figure 1b Mounting orientation Figure 1c Application connections Display connection A B 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal blocks Pressure sens...

Page 3: ...re Function 04 Read input register 3x0008 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 5 Select the pressure unit for display Pa inchWC mmWC psi mbar PRESS UNIT Pa SELE...

Page 4: ...correctly fulfilled his her duties arisen from the delivery and stated in the contract The seller will give a new warranty for goods that have been replaced or repaired within the warranty however only to the expiration of the original product s warranty time The warranty includes the repair of a defective part or device or if needed a new part or device but not installation or exchange costs Unde...

Reviews: