HK Instruments DPT-Ctrl-MOD Series Installation Instructions Download Page 3

Copyright HK Instruments 2022

www.hkinstruments.fi

Installation version 8.0 2022

7) Select the response time: 1...20 s.

 RESPONSETIME

     4 s

SELECT

UP

DOWN

      

BAUD RATE

    9600

  

SELECT

UP

DOWN

    

PARITY BIT

    NONE

  

SELECT

UP

DOWN

5) Select the baud rate: 9600/19200/38400.

6) Select the parity bit: None/Even/Odd

9) Select the input type.
Passive temperature sensors: PT1000 / Ni1000 / Ni1000LG / NTC10k
Voltage input: VINPUT
Switch input: BIN IN
No input: NONE

                

INPUT

    PT1000

SELECT

UP

DOWN

10) Select the setpoint of the controller (SP2 is only available with BIN IN switch 

information):

CONFIGURATION 

CONTINUED

NOTE! Always zero the device before use. 

Supply voltage must be connected one hour before the zero point adjust-

ment is carried out. Access via Modbus or by push button.

1) Loose both tubes from the pressure and -.

2) Activate the device menu by pushing the the select button for 2 

seconds. 

3) Select 

Zero sensor

 by pressing the select button.

4) Wait until the LED turns off and then install tubes again for the 

pressure inlets.

 

STEP 4: ZERO POINT ADJUSTMENT

SELECT

 

STEP 5: INPUT SIGNAL CONFIGURATION

Input signals can be read over Modbus via DPT-MOD RS485 interface.

Signals

Accuracy for measurement

Resolution

0...10 V

< 0,5 %

0,1 %

NTC10k

< 0,5 %

0,1 %

Pt1000

< 0,5 %

0,1 %

Ni1000/(-LG)

< 0,5 %

0,1 %

BIN IN (potential free contact)

The jumpers should be set according to the instructions below and the value 

should be read from the right register. 

Figure 3 - Input signal configuration

J1

J2

J3

IN

J1

J1

J1

J2

J2

J2

J3

J3

J3

NTC10k / BIN IN

Pt1000 / Ni1000/(-LG)

0...10 V

        

D-VALUE

    1.00 

 

SELECT

UP

DOWN

15) Push the select button to exit menu.

   

SELECT

  EXIT MENU

SELECT

12) Select proportional band according to your application 

specifications.

        

P-VALUE

    206 

 

SELECT

UP

DOWN

13) Select integral gain according to your application specifications.

        

I-VALUE

    4.00 

 

SELECT

UP

DOWN

14) Select derivation time according to your application 

specifications. 

STEP 6: TEMPERATURE COMPENSATION

The device includes an outdoor temperature compensation function   that can 

be enabled from the menu. When activated and an outdoor temperature sensor 

is attached, the effective set point of the device will be modified to compensate 

for the cold outdoor air. This may result in energy savings.

If temperature compensation is enabled, the device will linearly decrease the 

user’s  setpoint  (REF  FLOW/REF  PRESSURE)  by  0  %  to  TC  DROP  %  from  TC 

START TE to TC STOP TE.

The device enforces a +5 °C difference between the start and stop tempera-

tures. The start temperature must be higher than the stop temperature.

1) Connect and configure an outdoor air temperature sensor. See step 5.

2) Enable temperature compensation.

4) Set the stopping temperature for compensation.

TC STOP TE

   -15 °C

 

SELECT

UP

DOWN

   

TEMP COMP

     ON

 

SELECT

UP

DOWN

TC START TE

    5 °C

 

SELECT

UP

DOWN

3) Set the starting temperature for compensation. 

5) Set the maximum drop percentage for compensation.

 TC DROP %

    25.0

 

SELECT

UP

DOWN

8) Select the Fixed Output (OFF / 0...100%), (see step 7 Fixed Output).

10.1) If the CONTROL UNIT is selected PRESSURE.

SELECT

UP

DOWN

 REF PRES SP1

    10 Pa

 REF PRES SP2

    100 Pa

10.2) If the CONTROL UNIT is selected FLOW.

SELECT

UP

DOWN

 REF FLOW SP1

 25.000 m3/s

 REF FLOW SP2

 35.000 m3/s

11) Select the TEMP COMP (OFF/ON), (see step 6, Temperature Compensation).

Summary of Contents for DPT-Ctrl-MOD Series

Page 1: ...ed pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa Accuracy specifications include general accuracy linearity hysteresis long term stability and repetition error Overpressure Proof pressure 25 kPa Burst pressure 30 kPa Zero point calibration Manual pushbutton or Modbus Response time 1 0 20 s selectable via menu or Modbu...

Page 2: ...o a fan with pressure measurement taps Select Common probe when using DPT Ctrl MOD with a common measurement probe that follows the formula q k P i e FloXact MANUFACTURER Common probe SELECT UP DOWN Common probe Flakt Woods SELECT UP DOWN STEP 2 WIRING DIAGRAMS For CE compliance a properly grounded shielding cable is required 1 Unscrew the strain relief and route the cable s 2 Connect the wires as...

Page 3: ... 10 V D VALUE 1 00 SELECT UP DOWN 15 Push the select button to exit menu SELECT EXIT MENU SELECT 12 Select proportional band according to your application specifications P VALUE 206 SELECT UP DOWN 13 Select integral gain according to your application specifications I VALUE 4 00 SELECT UP DOWN 14 Select derivation time according to your application specifications STEP 6 TEMPERATURE COMPENSATION The...

Page 4: ...0 99 4x0021 Temp comp drop decimal part 16 bit 0 999 0 0 0 999 4x0022 PID Pressure Ref SP 1 16 bit 250 2500 model 2500 700 7000 model 7000 250 2500 model 2500 700 7000 model 7000 4x0023 PID Pressure Ref SP 2 16 bit 250 2500 model 2500 700 7000 model 7000 250 2500 model 2500 700 7000 model 7000 4x0024 PID Flow Ref SP 1 integer 16 bit 0 30000 0 30000 4x0025 PID Flow Ref SP 1 decimal 16 bit 0 999 0 9...

Reviews: