HK Instruments DPT-CR-MOD Series Installation Instructions Download Page 2

Copyright HK Instruments 2022

www.hkinstruments.fi

Installation version 1.0 2022

SCHEMATICS

DIMENSIONAL DRAWINGS

INSTALLATION

Figure 1a - Surface mounting

STEP 1: MOUNTING THE DEVICE

1) Mount the device in the desired location (see step 1).
2) Open the lid and route the cable through the strain relief and 

connect the wires to the terminal block(s) (see step 2).

3) The device is now ready for configuration.

 

  WARNING! Apply power only after the device is properly wired.

1) Select the mounting location (duct, wall, panel).
2) Use the device as a template and mark the screw holes.
3) Mount with appropriate screws.

Figure 1b - Mounting orientation

Figure 1c - Application connections

DPT

4.3

DPT

Display connection

       A

24 V

GND

LEDs

Joystick 1

Joystick 2

Joystick 3

Select

Up

Down

Menu buttons

Terminal 

blocks

Pressure

sensor

Input terminal

configuration

jumpers

Input 1

Input 2

GND

GND

Input

Output

       B

YES

NO

NO

Static pressure

Filter/Damper

monitoring

Fan/Blower

monitoring

Not

connected

Summary of Contents for DPT-CR-MOD Series

Page 1: ...y monitoring in cleanrooms SPECIFICATIONS Performance Measurement range 250 2500 Pa Accuracy from applied pressure Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Including general accuracy linearity hysteresis long term stability and repetition error Input accuracy Temperature 0 25 C typical 25 C accuracy of external transmitter Humidity 0 5 rH typical 25 C accuracy of external transmitter Overpres...

Page 2: ...for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections DPT 4 3 DPT Display connection A 24 V GND LEDs Joystick 1 Joystick 2 Joystick 3 Select Up Down Menu buttons Terminal block...

Page 3: ...ample 2 rH Temp transmitter connected to DPT CR MOD rH Temp transmitter rH 0 10 V Jumper settings Temp 0 10 V 1 Activate the device Menu by pushing the the select button for 2 seconds 2 Select the address for Modbus 1 247 BAUD RATE 9600 SELECT UP DOWN ADDRESS 99 SELECT UP DOWN PARITY BIT NONE SELECT UP DOWN 3 Select the baud rate 9600 19200 38400 4 Select the parity bit None Even Odd 9 Push the se...

Page 4: ...pair of a defective part or device or if needed a new part or device but not installation or exchange costs Under no circumstance is the seller liable for damages compensation for indirect damage Register Parameter description Data Type Value Range 3x0001 Program version 16 bit 0 1000 0 00 99 00 3x0002 0004 Not in use 3x0005 Temperature Celsius Pt1000 16 bit 500 500 50 0 50 0 C 3x0006 Temperature ...

Reviews: