Hitzer Energy Master II 710 Owner'S Manual Download Page 9

Page 9 

Supply Duct: 

In order to achieve maximum performance it is important to have the correct size of duct work that 
corresponds with your Hitzer ENERGY MASTER Stoker Furnace. Your furnace is equipped with a 1009 
CFM Blower. In order to achieve maximum performance and heat, it is important to make sure the duct 
work is sized properly and not too small for the blower assembly. If the duct work is too small your furnace 
won’t achieve full potential. Duct sized excessively large will also be detrimental to the operation of your 
furnace. NOTE: These calculations are based on a .10 static pressure. 
 
Supply Duct Size  

 

 

Shape   

 

Approximate Capacity(CFM) 

6” 

 

 

 

 

round   

 

 

 

120 

8

” 

 

 

 

 

round   

 

 

 

240 

10” 

 

 

 

 

round   

 

 

 

420 

12” 

 

 

 

 

round   

 

 

 

680 

14”                                                           round                                                      1000  
8”x12”   

 

 

            rectangle 

 

 

            480 

8”x16”   

 

                        rectangle  

 

 

            700 

8”x 20”   

 

 

           rectangle  

 

 

            910 

8”x 22”   

 

 

           rectangle  

 

 

          1000 

8”x 24”   

 

 

           rectangle  

 

 

          1200 

 

Return Air: 

Return air is very important and 

MUST BE

 incorporated into the system.  Without adequate return air 

supplied to your furnace the warm air distributed into your home will be restricted. This will decrease the 
efficiency of your furnace. You could also cause the furnace to overheat because of reduced air flow 
causing damage to your unit and voiding your warranty. If your furnace is installed in a basement or utility 
room that is fairly air tight the blowers on the furnace could depressurize the room and pull toxic flue 
gasses from the furnace or other burning appliance in the area. These toxic fumes could then be 
distributed throughout the house causing a very dangerous situation. 
 
The return air can be provided by installing a separate duct system or by tying into the cold air return duct 
of the existing furnace.  Without a return air system warm air will be drawn into your basement, 
unnecessarily heating unused portions of your home. 

The return duct should be a minimum of 16” x 20” 

or equivalent (320sq.in.). The return duct may be attached to the rear of the stoker furnace. Make sure if 
you are attaching the duct to the rear of the furnace you do not inhibit the removal and replacement of the 
furnace filters. These filters should be checked and cleaned/replaced regularly to maintain the proper air 
flow.   
   

Combustion Air: 

All fires need air to burn. The incomplete combustion that takes place 

in an “air starved” situation causes 

carbon monoxide (CO) to be produced in quantities that can be dangerous inside a well sealed house. 
Having a source of combusti

on air from outside the home will prevent “air starvation” of the furnace. You 

must provide enough fresh air to assure proper combustion. Outside air is required to replace air used to 
take the byproducts of combustion out the chimney. Outside air is also required to replace air exhausted 
by kitchen/bathroom fans, and any other furnace, or water heater chimneys or fans. 

Outside air may be needed if: 

 

The solid-fuel-fired appliance does not draw steadily, smell, experiences smoke roll-out, burns 
poorly, or back-drafts whether or not there is combustion present.

 

 

Any of the above symptoms are alleviated by opening a window slightly on a calm day. 

 

The house is equipped with a well-sealed vapor barrier and tight fitting windows and/or has any 
powered devices which exhaust house air. 

 

There is excessive condensation on windows in the winter.

 

 

A ventilation system is installed in the house.

 

 
 

Installation In A Confined Space: 

When the furnace is installed in a utility/storage room or other enclosed areas you must install two open 
grills. They should be placed in a wall or door opening into the rest of the house. One will supply 
combustion air. Locate it near the floor. The other is for ventilation and be located near the ceiling.  Each 

Summary of Contents for Energy Master II 710

Page 1: ...SONAL INJURY OR EVEN DEATH REFER TO MARKINGS ON THE FURNACE FOR ADDITIONAL INFORMATION CARBON MONOXIDE AND SMOKE DETECTORS ALARMS MUST BE INSTALLED IN THE HOME AND WORKING PROPERLY DANGER RISK OF FIRE OR EXPLOSION DO NOT BURN GARBAGE GASOLINE DRAIN OIL OR OTHER FLAMMABLE LIQUIDS DO NOT USE CHEMICALS OR FLUIDS TO START FIRE BURN RICE SIZE ANTHRACITE COAL ONLY STOVE SURFACES MAY BE HOT WHILE IN OPER...

Page 2: ...eturn Air D Combustion Air E Installation In A Confined Space IV Flue Systems A Masonry System B Factory Built Systems C Chimney Requirements D Flue Size E Chimney Height Requirements F Power Vent System V Basic Regulations for Safe Operations A Cautions B Local Codes VI Stove Start Up Operation A Install Coal Trol Thermostat B Start Up C Adjusting Chimney Draft D Measuring Furnace Compatibility V...

Page 3: ...fire follow the installation instructions carefully Failure to follow these instructions may result in property damage bodily injury or even death Contact your local building inspector or fire officials about the need for a permit restrictions or installation inspection required in your area Refer to makings on your furnace for more information Save these instructions for future reference Safety N...

Page 4: ... Once it is determined your existing furnace will accept an add on installation a parallel installation with return air outlined later in this manual is recommended 3 Can the furnace be vented properly a Is the chimney appropriate for this installation This furnace requires installation in a masonry chimney with a clay flue liner or a metal all fuel chimney listed to UL103 CAN ULC S629 M87 Type HT...

Page 5: ...ated and make placement of the Energy Master Furnace to achieve maximum heat benefit it can produce Clearances To Combustibles Floor Protection This furnace must be placed on a non combustible floor If the floor is a combustible material floor protection must be placed underneath it and extend at least 8 inches on each side of the fuel or ash door It must also extend 16 inches out from the front o...

Page 6: ...ter Furnace to the chimney should be made as direct as possible It is not recommended to use more then 2 elbows for venting The pipe connecting the furnace to the chimney should be at least 24 gauge single wall pipe Thicker gauges and double wall pipe may be used A inch slope back toward the furnace per foot of horizontal run is required This allows any condensation forming in the pipe to flow bac...

Page 7: ...Page 7 ...

Page 8: ...are drawn with a masonry chimney Manufactured metal chimney listed to UL 103 CAN ULC S629 M87 Type HT or a Hitzer approved power vent system may also be used Follow manufacturer s instructions guidelines when using these products ...

Page 9: ...our basement unnecessarily heating unused portions of your home The return duct should be a minimum of 16 x 20 or equivalent 320sq in The return duct may be attached to the rear of the stoker furnace Make sure if you are attaching the duct to the rear of the furnace you do not inhibit the removal and replacement of the furnace filters These filters should be checked and cleaned replaced regularly ...

Page 10: ... Supplemental add on Furnace Installations Do not use duct elbows having an inside radius of less than 6in 150mm on the oil gas electric furnace Do not connect to a down flow furnace Do not connect ductwork so that a reverse flow is possible Operate the gas oil electric furnace periodically to ensure it will operate satisfactorily when needed Certified for installation with the ductwork configurat...

Page 11: ... only have one appliance per chimney and it is not permissible to connect your Hitzer Energy Master II furnace to a chimney that is servicing another appliance Flue Requirements It is required to have a chimney that is built according to the chimney manufacturer s specifications and meets local building codes It is also required to have your chimney inspected and cleaned by a certified chimney pro...

Page 12: ...our draft A few of these include wind speed and direction obstructions diverting winds barometric pressure and humidity This is why it is essential to have a barometric damper and carbon monoxide detectors alarms installed and working properly Power Vent System A Hitzer approved power vent may be used in place of a chimney BE SURE TO READ YOUR POWER VENTER INSTALLATION AND OPERATION INSTRUCTION MA...

Page 13: ...he properly constructed and in good top of the fire box When the door is condition Chimney must be at least 15 opened oxygen combines with gases high and exceed the roof a minimum of and ignites 3 feet unless using Power Vent System WARNING Risk of Fire WARNING Over Fire Unit Comply with all minimum clearances to Do NOT over fire your unit combustibles as specified This will cause warping of fire ...

Page 14: ... hole to read the chimney draft Adjust the barometric damper so that your manometer reads between 03 and 06 inches of water column following the instructions provided with the damper Do not run at a draft above 06 inches of water column as this could cause your stoker to over fire Over firing can cause a dangerous fire hazard It would be best to set it with a manometer if available The settings on...

Page 15: ...amount of coal burned ash content of the coal the burn rate and draft of the chimney Allow stoker to run out of coal go out and cool down Remove chimney connector pipes and check and remove any fly ash accumulation This will mainly be at the bottom of elbows and horizontal runs Remove all fly ash from heat exchanger plates inside and below the flue collar and on the floor of the stoker around the ...

Page 16: ...Page 16 VI Troubleshooting ...

Page 17: ...rmined by the capacity and condition of the battery and the amount of heat needed Some generators will also work however the output of either must be a pure sine wave Other outputs can cause the Coal Troll Digital to not work You may also contact your Hitzer dealer or Hitzer Inc for questions or more information regarding stove installation and operation Hitzer Inc 269 E Main St Berne IN 46711 260...

Reviews: