hitin RTT8 Quick Start Manual Download Page 3

 

6.

 

Operation 

 

Up to 5 sensors can be connected to the input contacts (always one sensor to one contact!). 

The device can be connected with a computer equipped with serial interface RS232. Maximum 255 
devices can be connected to one interface. 
 

RTT  8  is  equipped  with  5  outgoing  relays  with  switching  contacts  connected  to  the  output 

connectors. 
At picture 1. the switching connectors have been shown in the power-off position. The condition of the 
first three relays (P1, P2, P3) depends on the temperature of the sensors (K1, K2, K3, respectively). 
The threshold temperatures TxH and TxL for each relay can be adjusted from the keyboard or an out-
side computer. 
If sensor temperature exceeds TxH, relay will be automatically switched off. After the temperature has 
dropped below TxL, relay will be switched on again. If the input sensor is short connected or has been 
torn out, RTT8 reacts as if the temperature has been exceeded and switches the relay off. 
 
Relay 4. 
Functioning of the relay 4  depends on the operating mode set.  
In  the  temperature  control  mode  the  relay  operates  identically  to  the  first  three  ones  (P1,P2,P3,).  It 
controls sensor K4. 
In the maximum temperature control mode the device compares the highest value measured  on  the 
sensors  K1,  K2  and  K3  to  the  threshold  temperatures  T4H  and  T4L,  switching    relay  4  on  or  off 
respectively. 
In  the  timing  mode  the  relay  will  be  switched  on  after  a  desired  period.  The  previously  set  time 
interval  is  counted  down  after  the  testing  procedures,  initialised  when  power  is  on,  have  been 
completed. 
 
Relay 5. 
Functioning of the relay 5  depends on the operating mode set.  
In  the  temperature  control  mode  the  relay  operates  identically  to  the  first  three  ones  (P1,P2,P3,).  It 
controls sensor K5. 
In the timing mode relay 5 is being switched off simultaneously with relay 3. Relay 5 will be switched 
on after time delay set, counted down from the moment of switching on relay 3. 
In the parallel mode relay 5 operates identically to relay 2. 
 
Operation  of  the  relays  4  and  5  is  steered  by  the  programme  code,  which  can  be  modified  from  the 
keyboard or an outside computer. 
 

Relay 5 

Relay 4 

Display 

X.7  X.6  X.5  X.4  X.3  X.2  X.1  X.0 

K45=>00000000 

 

X

.7 – not used  

X.6 – switches relay 5 to parallel mode 
X.5 – switches relay 5 to timing mode (time in min.) 
X.4 - switches relay 5 to temperature control mode 
X.3 – not used 
X.2 – switches relay 4 to maximum temperature control mode 
X.1 – switches relay 4 to timing mode (time in sec.) 
X.0 – switches relay 4 to temperature control mode 
 
Values X.7 – X.1 can be entered only as 0 or 1. Value 0 switches the respective mode off, whereas 
value 1 switches it on. 
Programming of the operating mode is being carried out by entering value 0 or 1 in the consecutive 
fields. A blinking cursor will be visible on the display under the first digit possible to alter. (K45=> _ -
------ ) 
“_” indicates current position of the cursor 
Any improper values of the programming code K45 will be automatically deleted. 

Reviews: