AIR-TO-AIR UNITS – COMPACT HORITZONTAL INVERTER
ACHIA / ACHIBA
11.14 207434 Rev.103
serie INVERTER
601
741
901
NOMINAL ELECTRICAL SPECIFCATIONS FOR COOLING STANDARD CONDITIONS (3)
Power supply
400/3/50 + N
400/3/50 + N
400/3/50 + N
Input Capacity (cooling)
kW
8,7
11,8
14,8
Current input (cooling)
A
13,4
18,2
22,3
Indoor airflow
m
3
/h
2.800
3.600
4.400
NOMINAL ELECTRICAL SPECIFCATIONS FOR COOLING STANDARD CONDITIONS (4)
Power supply
400/3/50 + N
400/3/50 + N
400/3/50 + N
Input Capacity (cooling)
kW
8,2
10,6
14,1
Current input (cooling)
A
12,7
16,9
21,7
Indoor airflow
m
3
/h
3.600
4.600
5.500
(1) Cooling: Compressor frequency: 80Hz. Outdoor dry temperature: 35 °C. Indoor Dry / Wet air temperature: 27ºC / 19 °C. Indoor airflow: Low.
(2) Heating: Compressor frequency: 80Hz. Outdoor dry /wet air temperature: 7ºC / 6 °C. Indoor dry temperature: 20 °C. Indoor airflow: Medium.
(3) Cooling maximum: Compressor frequency: 120Hz. Outdoor dry temperature: 35 °C. Indoor Dry / Wet air temperature: 27ºC / 19 °C. Indoor airflow: Medium
(4) Heating maximum: Compressor frequency: 120Hz. Outdoor dry /wet air temperature: 7ºC / 6 °C. Indoor dry temperature: 20 °C. Indoor airflow: High
• Indoor drainage (of condensate water) has a 3/4” MPT
connection.
• Condensate drain line diameter should be equal or larger
than the unit connection depending on line length and
general building configuration.
• Drainage line should have a minimum inclination of 2% for
proper water evacuation.
• When drainage line is exposed to temperatures below
0ºC, it is necessary to provide thermal insulation or
electrical heating wire to avoid water freezing and tube
damages
• It is advisable to install a trap with proper dimensions.
• Air duct dimensions will be determined according to the airflow and available static pressure.
• Ducts must be designed by qualified technical people.
• Use ducts made of non-inflammable materials in order to avoid any emission of gas in case of fire. It is advisable to use
metal plate duct with insulation.
• Use flexible ducts to connect air ducts into the unit and thus avoid vibration and noise transmission.
AIR DUCTS
DRAINAGE