Temperature Calibration
To verify the temperature measurement, if you work with a
PT100 Temperature Sensor
to
take the chambers temperature, you will need a
Temperature Calibration Kit
supplied by
Hitec as additional part; its part number is
DABS-CKTP
. This Calibration can be made once
a year on a regular maintenance.
You have to switch OFF and ON the equipment to enter in the
“Local Mode”, and to plug the
Calibrator on the PT100 plug on the terminal.
Open the DADS Terminal box and get access to behind the display.
Proceed as described:
Switch the Calibrator to A and it must blink between 0 / 1 on terminal display, if
needed adjust the Potentiometer R4003;
Switch the Calibrator to B and it must be at ±4000 on terminal display, if needed
adjust with Potentiometer R4001;
Figure 18
– Temperature
Calibration Kit