Item
Specification
Insulation withstand voltage
AC 1,500 V (100 mA, 1 min)
Insulation resistance
DC 500 V, 10 M Ω or more
Electrical specifications
Item
Controller
Drive tray
Input voltage (operable voltage
range) (V)
AC 200-240 +6%/-11%
SFF, LFF, FMD, and dense
intermix drive tray: AC 200-240
+6%/-11%
Frequency (Hz)
50/60 ±1
Number of phases, cabling
Single-phase with protective grounding
Steady-state current 100V/
200V
1
,
2
CBLM: 4.0x2
SFF drive tray: 2.4x2/1.2x2
LFF drive tray: 1.9x2/1.0x2
FMD drive tray: 2.6x2/1.3x2
Dense intermix drive tray: -/
3.0x2
Current rating of breaker/fuse
(A)
16.0
Heat value (normal) (kJ/h)
CBLM: 2160 or less
SFF drive tray: 1120 or less
LFF drive tray: 940 or less
FMD drive tray: 1520 or less
Dense intermix drive tray: 3460
or less
Steady-state power (VA/W)
3
CBLM: 1600/1560 or less
SFF drive tray: 480/460 or less
LFF drive tray: 380/350 or less
FMD drive tray: 520/490 or less
Dense intermix drive tray:
1200/1160 or less
Power consumption (VA/W)
CBLM: 640/600 or less
SFF drive tray: 320/310 or less
LFF drive tray: 280/260 or less
FMD drive tray: 440/420 or less
Dense intermix drive tray:
1000/960 or less
Notes:
1.
The power current of Nx2 described in this table is required for a single power unit.
2.
If one power unit fails, another power unit requires electric current for the two power units.
Therefore, plan the power supply facility so that the current-carrying capacity for one power
unit can provide the total capacity for two power units.
Storage system specifications
109
Hitachi Virtual Storage Platform G400, G600 Hardware Reference Guide
Summary of Contents for Virtual Storage Platform G400
Page 1: ...Hitachi Virtual Storage Platform G600 Hardware Reference Guide MK 94HM8022 05 June 2016 G400 ...
Page 6: ...6 Hitachi Virtual Storage Platform G400 G600 Hardware Reference Guide ...
Page 16: ...16 Preface Hitachi Virtual Storage Platform G400 G600 Hardware Reference Guide ...
Page 123: ...Hitachi Virtual Storage Platform G400 G600 Hardware Reference Guide ...