Power LED turned off
Procedure
1.
Is AC power being supplied?
• Yes: Check the power cables are connected properly and turn off the
main switch.
• No: Supply AC power to the storage system and restart the storage
system.
2.
Wait more than a minute and then set the main switch to on.
3.
Is the Power LED on at the controller?
• Yes: Go to step 5.
• No: Set the main switch to off.
4.
Contact your administrator. Go to step 6.
5.
Is the Ready LED on at the controller?
• Yes: Use the equipment in its current operational state, even if the
green Ready LED blinks fast.
• No: Use the following corrective action. See
or Ready LED went on and then off on page 390
.
Ready LED does not go on or Ready LED went on and then off
Procedure
1.
Is the controller Power LED on?
• Yes: Go to step 2.
• No: Go to step 4 in
POWER
LED does not go on.
2.
Is the
ALARM
LED on at the controller?
• Yes: See
ALARM
LED is on.
• No: Go to step 3.
3.
Turn off the main switch.
4.
Wait more than one minute, and then set the main switch to on.
5.
Is the Ready LED on at the controller?
• Yes: Continue to use the equipment. If the green Ready LED blinks
fast, the storage system is operational. Go to step 8.
• No: Go to step 8.
6.
Set the main switch to off.
7.
Contact your system administrator.
Alarm LED is on
Procedure
1.
Identify which component failed (see
Checking SIM alerts on page 381
).
390
Troubleshooting the storage system
Service Guide for VSP Gx00 and VSP Fx00 Models
Summary of Contents for Virtual Storage Platform F400
Page 4: ...4 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 22: ...22 Preface Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 106: ...106 Replacing storage system components Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 140: ...140 Replacing a fan Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 146: ... CBLM CBLH 146 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 160: ...160 Replacing a power supply Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 198: ...6 Click Block 198 Replacing cache memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 250: ...250 Replacing a SAS cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 260: ...260 Replacing cache flash memory Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 268: ...268 Replacing a LAN blade Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 278: ...278 Replacing a backup module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 284: ...284 Replacing a PCIe module Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 296: ...296 Replacing a PCIe cable connector Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 302: ...302 Replacing a PCIe cable Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 312: ...312 General maintenance Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 397: ...Warning labels on the storage system 397 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 405: ...Warning labels on the storage system 405 Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 412: ...412 Warning labels on the storage system Service Guide for VSP Gx00 and VSP Fx00 Models ...
Page 417: ...Service Guide for VSP Gx00 and VSP Fx00 Models ...