Fan speed availability according to the selected external static pressure
According to the selected of External Static Pressure configuration (through the optional function C5) the fan speeds available in the
Remote Control Switch are the ones show as example in the following pictures.
External Static Pressure (Pa)
High static pressure (SP-01)
External Static Pressure (Pa)
Standard static pressure (SP-00)
External Static Pressure (Pa)
Low static pressure (SP-02)
High H / High
Med
Low
Upper ESP limit
Lower ESP limit
High H / High
Med
Low
Upper ESP limit
Lower ESP limit
High H
High / M
ed
Low
Upper ESP limit
Lower ESP limit
Air flow (m³/min)
Air flow (m³/min)
Air flow (m³/min)
?
N O T E
"High H" speed available only with PC-ARFP(1)E remote control switch.
5 REFRIGERANT PIPING
5.1 PIPING CONNECTION
RPI-(4.0~6.0)FSRE
PIPING CONECTION
Dimension (mm)
Gas pipe
a1
b1
c1
87
246
90
Liquid pipe
a2
b2
c2
87
186
68
Drain pipe
a3
b3
c3
214
169
66
5.2 PIPE SIZE SELECTION
Models
Pipe Size (mm)
Gas Piping Liquid Piping
Drain Piping
RPIH-(4.0~6.0)FSRE
Ø15.88 (5/8)
Ø12.7 (3/8)
Ø32 (Outer) VP25
REFRIGERANT PIPING
PMML0529 rev.1 - 02/2021
9