If the fuses burn, please call the service dealer. Please do not replace by yourself, as it may lead to electric
shock and other injuries.
(1) Remove the screws on the control box.
(2) Connect the power cord and earth wire to the main terminal.
(3) Connect the remote control wire to the subsidiary terminal box according to electric wiring diagram.
(4) Connect the power supply of the indoor and outdoor units to the main terminal.
(5) Tie the wire in the control box with the clamp tightly.
(6) After completing the wiring, seal the wiring hole with the sealing material ( with the lid) to prevent the
condensed water and insects entering the wiring space.
16
Installation and Maintenance
WARNING
6. Electrical Wiring
CAUTION
7. Attaching the Air Return Grille
·
·
·
When clamping the wiring, to prevent external pressure being exerted on the wiring connections,
use the clamping material and fix firmly as shown in the Fig.6.1.
When performing the wiring work, ensure that the wiring is proper and does not cause the control
box lid to open up, if so close the cover firmly. When attaching the control lid, make sure that the wires are
Outside the unit, keep the weak wiring (remote controller and transmission wiring) and strong wiring
(earth and power supply wiring) at least 50 mm away so that they do not pass through the same place
together. Proximity may cause electrical interference malfunction and breakage.
·
(1) Fix the air return grille onto the indoor unit with screws supplied as accessories (4 pieces).
(2) Close the air return grille.
This completes the unit installation work.
The air return grille must be attached when electric cabling work is completed.
not affected.