1
/14
TROUBLESHOOTING
!
[
]~ [
] Cooler Inlet Refrigerant Temperature Thermistor Abnormality
This alarm code is indicated when the thermistor resistance is out of range (72
Ω
≤
Resistance
≤
179 k
Ω
)
Is printed circuit board for relay
(PCB
D
) connector CN23Te2
correctly connected?
Plug, Wiring Repair
Disconnect connector and
measure resistance. Is the
resistance correct ?
Replace thermistor
Replace printed circuit
board for relay (PCB
D
)
Thermistor
resistance
(K
Ω
)
Temperature (°C)
Thermistor for Cooler Inlet Refrigerant
characteristics
No
Yes
No
Yes