Hitachi America Ltd. RCU SERIES
14
4.3 Control terminal specific
7
9
10
12
11,16
23
21
22
No
Content
RCU
operation signal
RCU
preparation of operation signal
External fault input signal
RCU
fault reset signal
Fault
A
contact output
Fault
B
contact output
Terminal
DI. 01
DI. 02
DI. 03
DI. 04
DI. COM
DO1. B
DO1. A
DO1. C
Signal
Contact Input 1
Contact Input 2
Contact Input 3
Contact Input 4
Contact input (common
terminal)
Contact output
1 (b-
contact
)
Contact output
1 (a-
contact
)
Contact
ouput
1 (
common
terminal
)
A, B
contact common terminal
AC 1A/250V
DC 1A/30V
Contact
Input
Contact
Output
Catalog
26
2
4
25
Healthy A
contact output
Healthy B
contact output
DO
2
. B
DO
2
. A
DO
2
. C
Contact output
1 (b-
contact
)
Contact output
1 (a-
contact
)
Contact output
1 (
common
terminal
)
A, B
contact common terminal
AC 1A/250V
DC 1A/30V
Contact
Output
Figure 4.2 Control terminal specific
Refer to figure 4.1 for basic connection.
The control cables should be at least 0.5mm
2
shielded cables. The maximum wire size fitting
in the terminals is 2.5mm
2
.
4.4 Terminal block and Screw type
(According to Mounting Dimension)
SIZE
Input/Output Wiring
Terminal Block type
Width
(inside)
Screw
type
Signed
Torque
(N
•m)
KE2P
KE3P
KE4P
12mm
M5
3~4
Table 4.1 RCU Terminal Block and Screw type