background image

1.2 Safety Instructions 

 

!

 

DO NOT make any connections when the

 Regenerative Converter 

is 

connected to the main voltage or energized inverter DC bus.   

DO NOT make any measurements when the 

Regenerative Converter 

is 

connected to the main voltage and energized inverter DC bus. 

After disconnecting the main power, wait until the cooling fan stops and the 

indicator goes out. Wait a further 3 minutes before doing any work on the 

Regenerative Converter 

connections. Do NOT open the cover during this 

time.  

DO NOT make any voltage withstand tests on any parts of the 

Regenerative 

Converter

. Damage to the unit may result. 

DO NOT touch the integrated circuits or other components on the internal 

circuit boards. Static voltage discharge may destroy the components. 

Make sure that the cover of 

RCU

 

Regenerative Converter

 is closed before 

connecting the main voltage. 

 

 Ground                                       Warning Symbols 

The ground terminal of 

Regenerative Converter

 

must be connected to a proper ground. 

 

Grounding of the Regenerative Converter 

reduces the risk of high voltage shock, injury or 

death.  

Please observe special caution where the 

following warning symbols appear 

throughout this manual. 

  = Dangerous Voltage   

 = General Warning 

 

 

 

 

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for RCU- 2011

Page 1: ...truction Manual NOTE REFER ALSO TO APPLICABLE INVERTER INSTRUCTION MANUAL Hitachi America Ltd Manual Number HAL1057A May 2010 After reading this manual keep it handy for future reference Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 2: ...M 6 POWER AND CONTROL CONNECTIONS 7 CONTROL TERMINAL FUNCTIONS 8 POWER WIRING 9 DISPLAY 9 OUTPUT CURRENT AND LINE VOLTAGE WAVEFORMS 10 ELECTRICAL SPECIFICATIONS 10 DIMENSIONS 11 The contents of this manual are subject to change without notice May 2010 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 3: ...Revision History Rev A May 2010 Miscellaneous corrections throughout Added cooling clearance drawing Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 4: ...L1 S L2 T L3 and the inverter s DC Link P N 3 The voltage on the RCU components is extremely dangerous and may cause death or severe injury if you come in contact with it 4 The control I O terminals are isolated from the main voltage but the relay outputs and other I O terminals may have dangerous voltage connected even if the power is disconnected from the RCU Regenerative Converter 5 The install...

Page 5: ...nd tests on any parts of the Regenerative Converter Damage to the unit may result 6 DO NOT touch the integrated circuits or other components on the internal circuit boards Static voltage discharge may destroy the components 7 Make sure that the cover of RCU Regenerative Converter is closed before connecting the main voltage Ground Warning Symbols The ground terminal of Regenerative Converter must ...

Page 6: ...egenerative Converter can provide up to 40 energy savings by reclaiming that regenerative energy and feeding it back into the AC supply 3 Benefits The RCU Regenerative Converter reduces electric power consumption by returning the otherwise wasted energy to the AC power distribution network for use by other loads Because there is no heat generated by braking resistors the capacity of air conditioni...

Page 7: ...5 Power and Control Connections RCU Series Shielded Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 8: ...pered together regenerative operation automatically starts when the inverter s DC bus voltage is above the RCU operating voltage These jumper wires are factory pre installed for your convenience Output Signals Fault Relay This relay is activated when fault trip has occurred 21 A Regenerative Converter error A contact NO 22 B Regenerative Converter error B contact NC 23 COM Regenerative Converter e...

Page 9: ...3 phase main power Phase sequence Automatic recognition FG Earth 7 Display rdy Ready Regenerative Converter is ready 000 0 Current value during regeneration 000 0A F00 Fault Code Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 10: ...Hz Efficiency Over 95 Operating Voltage DC LINK Automatically set by input voltage Display and Protection Display ready regenerative current fault codes Protection Overheat Over current Arm short Over Voltage Low voltage and Phase Error etc Filter Built in reactor and noise filter Wiring Input R S T DC Bus P N Ground Environmental Conditions Operation 10 C to 40 C Storage 20 C to 65 C 90 relative ...

Page 11: ...10 Dimensions 11 kW and 15 kW Models Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 12: ...Dimensions cont d 22 kW and 30 kW Models Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Page 13: ...ounting clearances shown below to allow adequate air flow for cooling of the units b a a c Distance mm a a2 b c 30 10 160 80 a2 is the distance between adjacent RCUs Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...