16 DRAIN PIPING
Perform drain piping work and attach the insulations before
refrigerant piping work.
D A N G E R
Do not put the drain pipe for the indoor unit into the drainage trench
ZKHUHFRUURVLYHJDVHVRFFXU2WKHUZLVHSRLVRQRXVJDVHVÀRZLQWR
the room, which may cause poisoning.
1
The position of the drain pipe connection is shown in the
IROORZLQJ¿JXUH
27
4
359
65
(mm)
Air panel (Option)
Drain pipe
Drain pipe connection
(Polyvinyl chloride pipe/VP25)
2
Prepare a polyvinyl chloride pipe with a 32mm outer
GLDPHWHUIRUGUDLQSLSLQJ>93EDVHGRQ-,6.LV
recommended].
3
Connecting Drain Pipe
a.
Connect the factory-supplied drain hose to the drain
pipe connection with the polyvinyl chloride adhesive.
When cleaning the connection surface, applying the
adhesive, inserting, retaining and curing the pipe, refer
to information given by the adhesive manufacturer. The
adhesive Eslon Nº 73 (Sekisui Chemical Co. Ltd) is
recommended.
b.
Insert the drain hose completely. If it is not inserted
properly, or if it is twisted, water leakage may occur.
Twisted, incompletely insertion
Insert completely and properly
Drain hose
(Accessory)
Drain pipe
connection
Incorrect
Correct
c.
Attach the factory-supplied hose clamp to the vinyl tape
(white) attached to the drain hose. The hose clamp
shall be 20mm away from the end face of the drain
hose. Then tighten the hose clamp to make sure that it
LVDSSUR[LPDWHO\PPLQOHQJWKIURPWKHVFUHZWRWKH
HGJHRIWKHKRVHFODPSDVVKRZQLQWKHIROORZLQJ¿JXUH
20+5mm
Hose band (accessory)
Tightening torque: 3.0-3.5N.m
Vinyl tape (white)
Drain pipe connection
Drain hose (accessory)
Tightening torque: 3.0-3.5N.m
Min.
28mm
For checking drainage
(transparent)
Use vinyl chloride
type adhesive
Elbow or Vinyl chloride VP25
(Field-supplied)
N O T E
•
,I FRQQHFWLQJ WKH IDFWRU\VXSSOLHG GUDLQ KRVH WR WKH GUDLQ SLSH
FRQQHFWLRQ ZLWKRXW DGKHVLYH IRU IXWXUH UHORFDWLRQ IROORZ WKH
SURFHGXUHEDQGF
•
8VHWKHIDFWRU\VXSSOLHGGUDLQKRVHDQGWKHKRVHFODPS2WKHUV
PD\FDXVHZDWHUOHDNDJH
•
'RQRWEHQGRUWZLVWWKHIDFWRU\VXSSOLHGGUDLQKRVH,WZLOOFDXVH
ZDWHUOHDNDJH
•
'RQRWDSSO\DQH[FHVVLYHIRUFHWRWKHGUDLQSLSHFRQQHFWLRQ,W
FRXOGFDXVHDGDPDJH
4
On-site Drain Piping Work
a.
Connect the factory-supplied drain hose to the drain pipe
connection using the polyvinyl chloride adhesive.
b.
When cleaning the connection surface, applying the
adhesive, inserting, retaining and curing the drain pipe,
refer to information given by the adhesive manufacturer.
c.
The drain piping shall be installed on a downward slope
RIWRDVVKRZQLQWKH¿JXUHEHORZ
d.
Install the support parts at an interval of 1m to 1.5m in
order not to bend the drain pipe.
e.
Install the drain hose horizontally or slightly on an upward
slope to prevent air pockets from forming inside it. If air
SRFNHWVIRUPWKHGUDLQZDWHUZLOOÀRZEDFNLQWRWKHXQLW
which could cause an abnormal noise and leakage to the
room when the unit operation is stopped.
Drain hose
Install the drain hose horizontally or
with an upward slope
ENGLISH
DRAIN PIPING
PMML0416A rev.0 - 12/2015 - P5415720
23