3 General data
General specifications
TCGB0136 rev.1 - 05/2021
39
3
UTOPIA IVX Prime with R410A refrigerant for single phase units
OUTDOOR UNITS
RAS-4HVNP2E
RAS-5HVNP2E
RAS-6HVNP2E
Power supply
-
1~ 230V 50Hz
1~ 230V 50Hz
1~ 230V 50Hz
Nominal cooling capacity
kW
10.0
12.5
14.0
Nominal heating capacity
kW
11.2
14.0
16.0
Minimum - Maximum connectable indoor units
-
1 - 4
1 - 4
1 - 4
Minimum - Maximum connected capacity
%
90% - 115%
90% - 115%
90% - 115%
Noise level cooling (sound pressure) (night mode)
dB(A)
54 (51)
56 (51)
56 (51)
Noise level heating (sound pressure)
dB(A)
54
56
56
Noise level (sound power)
dB(A)
70
72
72
Air flow (cooling / heating)
m
3
/min
80
80
80
Dimensions (H x W x D)
mm
1140 x 950 x 370
1140 x 950 x 370
1140 x 950 x 370
Net weight
kg
84
84
84
Recommended circuit breaker
A
25
25
25
Maximum current
A
22.5
22.5
22.5
Running current cooling
A
13.6
18.5
23.7
Running current heating
A
12.4
16.4
17.6
Size of power cable (according to EN 60335-1)
quantity x
mm
2
3 x 6.0
3 x 6.0
3 x 6.0
Size of transmission cable between indoor unit and
outdoor unit
quantity x
mm
2
2 x 0.75
2 x 0.75
2 x 0.75
Piping diameter (liquid / gas)
mm (inch)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Ø9.52 (3/8) /
Ø15.88 (5/8)
Minimum piping length
m
5
5
5
Maximum piping length (chargeless)
m
20
20
20
Maximum piping length
m
75
75
75
Height difference (higher OU / lower OU)
m
30 / 20
30 / 20
30 / 20
Refrigerant
-
R410A
R410A
R410A
Refrigerant charge before shipment
kg
3.2
3.2
3.2
Additional refrigerant charge needed
g/m)
60
60
60
Compressor type
-
Rotative DC
Inverter driven
Rotative DC
Inverter driven
Rotative DC
Inverter driven