2.2  IMPORTANT NOTICE

The supplementary information about the purchased products 
is supplied in a CD-ROM, which can be found bundled with the 
outdoor unit. In case that the CD-ROM is missing or it is not 
readable, please contact your HITACHI dealer or distributor.
PLEASE READ THE MANUAL AND THE FILES ON THE 
CD-ROM CAREFULLY BEFORE STARTING WORK ON THE 
INSTALLATION OF THE AIR CONDITIONING SYSTEM. Failure 
to observe the instructions for installation, use and operation 
described in this documentation may result in operating failure 
including potentially serious faults, or even the destruction of the 
air conditioning system.
This manual should be considered as a permanent part of the 

air conditioner. This manual gives a common description and 
information for this air conditioner which you operate as well as 
for other models.

Refer to the models codification to confirm the main 

characteristics of your system.
Verify, in accordance with the manuals which appear in the 

outdoor and indoor units, that all the information required for the 

correct installation of the system is included and correspond to 
your air conditioner model. If this is not the case, contact your 
distributor.

If you have any questions, contact your service contractor of 

HITACHI.

2.3  ADDITIONAL INFORMATION ABOUT SAFETY

!

D A N G E R

•  HITACHI is not able to foresee all the circumstances which may 

result in a potential danger.

•  Do not pour water into the indoor or outdoor unit. These products 

are equipped with electrical parts. If water contacts with electrical 

components then it will cause a serious electrical shock.

•  Do not handle or adjust the safety devices inside the indoor and 

outdoor units. The handling or adjustment of these devices may 

result in serious accident.

•  Do not open the service cover or access the indoor or outdoor 

units without disconnecting the main power supply.

•  In case of fire Turn OFF the main switch, put out the fire at once 

and contact your service contractor.

•  This  air  conditioner  is  equipped  with  a  high  pressure  vessel 

under  PED  (Pressure  Equipment  Directive).  The  pressure 

vessel  has  been  designed  and  tested  before  shipment 

according  to  PED.  Also,  in  order  to  prevent  the  system  from 

an  abnormal  pressure,  a  high  pressure  switch,  which  needs 

no  field  adjustment,  is  utilized  in  the  refrigeration  system. 

Therefore,  this  air  conditioner  is  protected  from  abnormal 

pressures. However, if abnormally high pressure is applied to 

the  refrigeration  cycle  including  the  high  pressure  vessel(s), 

it  will  result  in  serious  injury  or  death  due  to  explosion  of 

the  pressure  vessel.  Do  not  apply  a  pressure  higher  than  the 

following pressure to the system, by modifying or changing the 

high pressure switch.

•  Do not handle, modify or change the high pressure switch in the 

air conditioning unit. If abnormally high pressure is applied to the 

elements in the air conditioning unit refrigerant cycle, including 

the  high  pressure  vessels,  these  could  explode  resulting  in 

serious injury or loss of life.

Location

Structure

Accumulator

Compressor

High pressure switch

Contact point 

Pressure detected

Connected to the electrical wire

The label for the vessel under PED 

are attached on the high pressure 

vessel. The pressure vessel capacity 

and vessel category are indicated on 

the vessel.

The high pressure switch is indicated 

on the electrical wiring diagram in the 

outdoor unit as HPS connected to printed 

circuit board (PCB) in the outdoor unit.

Start-up and Operation: 

Check to ensure that all the stop 

valves are fully opened and no obstacle exists at the inlet/outlet 
sides before start-up and during the operation.

Maintenance:

 Periodically check the high pressure side 

pressure. If the pressure is higher than the maximum allowable 
pressure, stop the system and clean the heat exchanger or 
remove the cause.

Refrigerant

Maximun allowable 

pressure (MPa)

High pressure switch 

cut-out value (MPa)

R410A

4.15

4.00 ~ 4.10

!

C A U T I O N

•  Check for refrigerant leakage in detail. It may hinder respiration as the 

gas displaces the air in the room. Also harmful gases would occur if a 

fire were being used in the room.

•  Fit the indoor unit, the outdoor unit, the remote control and the cable 

at a minimum of 3 meters away from sources where electromagnetic 

waves radiate directly towards the electrical box and the components 

of the unit, such as medical equipment. Electronic noise may result in 

the incorrect operation of the unit.

•  Do not use sprays, such as insecticides, varnishes or enamels or any 

other inflammable gas within a meter of the system.

•  If the circuit breaker or supply fuse of the unit comes on frequently, 

stop the system and contact the service suppler.

•  Do not place any foreign material (branches, sticks, etc.) in the air 

inlet or outlet of the unit. These units are fitted with high speed fans 

and contact with any object is dangerous.

•  This  appliance  must  be  used  only  by  adult  and  capable  people, 

having  received  the  technical  information  or  instructions  to  handle 

this appliance properly and safely.

•  The  air  conditioning  system  should  only  be  installed,  carry  out 

maintenance or inspection by qualified personnel, with the necessary 

resources,  tools  and  equipment,  who  are  familiar  with  the  safety 

procedures required to successfully carry out the installation.

•  Children should be supervised to ensure that they do not play with 

the appliance.

•  This air conditioner has been designed for standard air conditioning 

for human beings. For use in other applications, please contact your 

HITACHI dealer or service contractor.

?

N O T E

•  The air in the room should be renewed and the room ventilated every 

3 or 4 hours.

•  The  system  fitter  and  specialist  shall  provide  anti-leak  safety  in 

accordance with local regulations.

SAFETY

PMML0511 rev.1 - 06/2019

20

Summary of Contents for RAS-4-6FSVNME

Page 1: ...ON MANUAL MANUAL DE INSTRUCCIONES BEDIENUNGSANLEITUNG MANUEL D UTILISATION MANUALE DI ISTRUZIONI MANUAL DE INSTRUÇÕES BRUGSANVISNING INSTALLATIEHANDLEIDING INSTALLATIONSHANDBOK ΕΓΧΕΙΡΊΔΙΟ ΟΔΗΓΙΏΝ РЪКОВОДСТВО С УКАЗАНИЯ NÁVOD K POUŽITÍ KASUTUSJUHEND HASZNÁLATI ÚTMUTATÓ INSTRUKCIJU ROKASGRĀMATA NAUDOJIMO VADOVAS INSTRUKCJA OBSŁUGI MANUAL DE INSTRUCȚIUNI РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ...

Page 2: ......

Page 3: ...ile per eventuali errori di stampa che esulano dal proprio controllo Português As especificações apresentadas neste manual estão sujeitas a alterações sem aviso prévio de modo a que a HITACHI possa oferecer aos seus clientes da forma mais expedita possível as inovações mais recentes Apesar de serem feitos todos os esforços para assegurar que todas as especificações apresentadas são correctas quais...

Page 4: ...āvāt jaunākās inovācijas Lai gan tiek pieliktas visas pūles nodrošinot ka visas specifikācijas ir pareizas drukāšanas kļūdas ir ārpus HITACHI kontroles HITACHI nevar būt atbildīga par šīm kļūdām Lietuvių Šio vadovo specifikacijos gali būti keičiamos be įspėjimo kad HITACHI galėtų pateikti savo klientams paskutines naujoves Nors dedamos visos pastangos siekiant užtikrinti kad visos specifikacijos b...

Page 5: ...i effetti negativi sull ambiente e sulla salute e favorisce il riciclo dei materiali di cui è composta l apparecchiatura Non tentate di smontare il sistema o l unità da soli poichè ciò potrebbe causare effetti dannosi sulla vostra salute o sull ambiente Vogliate contattare l installatore il rivenditore o le autorità locali per ulteriori informazioni Lo smaltimento abusivo del prodotto da parte del...

Page 6: ...sējošo vielu eļļu un citām sastāvdaļām kas atrodas gaisa kondicionētājā tā demontāža saskaņā ar piemērojamiem noteikumiem jāveic profesionālam uzstādītājam Sazinieties ar attiecīgajām iestādēm lai saņemtu plašāku informāciju ĮSPĖJIMAS Pasibaigus eksploatacijos laikui šis produktas neturi būti maišomas su buitinėmis atliekomis ir turi būti išmetamas laikantis aplinkosaugos požiūriu tinkamų vietinių...

Page 7: ...mento globale GWP R410A 2088 Le Tn di CO2 equivalente di gas fluorurati ad effetto serra contenuti si calcola dal GWP indicato Carica Totale in kg indicato nella etichetta del prodotto e diviso per 1000 Português Em conformidade com a Regulamentação da UE Nº 517 2014 sobre determinados gases fluorados com efeito de estufa é obrigatório preencher a etiqueta afixada na unidade com a quantidade total...

Page 8: ...0A ir fluorētas siltumnīcefekta gāzes uz kurām attiecas Kioto protokola globālās sasilšanas potenciāls GWP R410A 2088 Ietverto fluorētu siltumnīcefektu izraisošo gāzu CO2 ekvivalents Tn tiek aprēķināts GWP kopējā uzpilde kg kas norādīta produkta etiķetē dalot ar 1000 Lietuvių Pagal ES Nr 517 2014 reglamentą dėl tam tikrų fluorintų šiltnamio efektą sukeliančių dujų įrenginio etiketėje privaloma užp...

Page 9: ...tità sull etichetta con inchiostro indelebile Quantità già caricata Carica aggiuntiva Carica totale e t CO2 2 Collocare l adesivo plastico di protezione consegnato assieme al Manuale Vedere Figura n 2 Português Instruções para preencher a etiqueta F Gas Label 1 Anote as quantidades na etiqueta com tinta indelével Carga de fábrica Carga adicional Carga total e t CO2 2 Coloque o adesivo plástico de ...

Page 10: ...óban mellékelve Lásd a 2 ábrát Latviešu Norādījumi kā aizpildīt F gāzes etiķeti 1 Etiķeti ar neizdzēšamu tinti aizpildiet ar dzesētājvielas daudzumu Uzpilde rūpnīcā Papildu uzpilde Kopējā uzpilde un t CO2 2 Uzlīmējiet uz F gāzes etiķetes iekļauta plastmasas maisiņā ar rokasgrāmatu plastmasas aizsargplēvi Skatīt attēlu Nr 2 Lietuvių Instrukcijos F dujų etiketės užpildymui 1 Užpildykite etiketėje ne...

Page 11: ...i denne ve jledning Denne installations og betjeningsvejledning gælder kun RAS FS V X NME enheder kombineret med HITACHI System Free indendørsenheder CODERING VAN DE MODELLEN Belangrijke opmerking Controleer aan de hand van de modelnaam welk type air conditioner u heeft hoe de naam wordt afgekort en hoe ernaar wordt verwezen in deze instructie handleiding Deze installatie en bedieningshandleiding ...

Page 12: ...ual de instalare și operare se referă numai la unitățile RAS FS V X NME combinate cu unități interioare HITACHI System Free КОДИФИКАЦИЯ МОДЕЛЕЙ Важное примечание Пожалуйста проверьте в соответствии с названием модели который является вашим типом кондиционера как он сокращен и указан в настоящей инструкции Данное Руководство по установке и эксплуатации относится только к блокам RAS FS V X NME в соч...

Page 13: ... RAS 4 6 FSVNME 1 2 3 4 11 6 7 8 9 10 5 12 13 14 15 16 18 19 20 16 17 21 11 11 ...

Page 14: ... RAS 4 6 FSNME 1 2 3 4 11 6 7 8 9 10 5 12 13 14 15 16 18 19 20 16 17 21 11 11 ...

Page 15: ... RAS 8 12 FSXNME 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 18 20 21 22 10 16 11 23 SVG RVR2 RVR1 SVA MVB MV1 ...

Page 16: ...AGGIO 11 Cablaggio elettrico 12 MESSA IN ESERCIZIO 13 PRINCIPALI DISPOSITIVI DI SICUREZZA ÍNDICE 1 INFORMAÇÃO GERAL 2 SEGURANÇA 3 ANTES DE UTILIZAR A UNIDADE 4 Acessórios fornecidos de fábrica 5 Transporte e manuseamento 6 INSTALAÇÃO DAS UNIDADES 7 NOME DAS PEÇAS 8 Trabalho de instalação da tubagem 9 Carga de refrigerante 10 TUBAGEM DE DESCARGA 11 Ligações elétricas 12 COLOCAÇÃO EM FUNCIONAMENTO 1...

Page 17: ...tēšana un apstrāde 6 IERĪČU UZSTĀDĪŠANA 7 DETAĻU NOSAUKUMS 8 cauruļvadu darbs 9 Dzesētājvielas uzpilde 10 DRENĀŽAS CAURUĻVADI 11 Elektroinstalācija 12 NODOŠANA EKSPLUATĀCIJĀ 13 GALVENĀS DROŠĪBAS IERĪCES INDEKSAS 1 BENDROJI INFORMACIJA 2 SAUGUMAS 3 PRIEŠ PALEIDIMĄ 4 Gamykliniai priedai 5 Transportavimas ir tvarkymas 6 ELEMENTŲ MONTAVIMAS 7 DALIŲ PAVADINIMAI 8 vamzdžių darbai 9 Aušinimo medžiagos už...

Page 18: ......

Page 19: ...protection and safety devices of air conditioners It may also cause lubrication failure of the sliding part of the compressor due to deterioration of refrigerant oil In particular hydrocarbon refrigerants such as propane R441A R443A GF 08 etc are not allowed since these are combustible and may cause major accidents such as fire and explosion in case of improper handling Once a non specified refrig...

Page 20: ...air conditioning unit If abnormally high pressure is applied to the elements in the air conditioning unit refrigerant cycle including the high pressure vessels these could explode resulting in serious injury or loss of life Location Structure Accumulator Compressor High pressure switch Contact point Pressure detected Connected to the electrical wire The label for the vessel under PED are attached ...

Page 21: ...2 OD19 05 ID22 2 25 4 Liquid pipe OD9 52 ID12 7 Name Qty Comments Ring core only for RAS 4 6 FSVNME 2 Yellow for L N wire Green for Earth wire Cable tie only RAS 4 6 FSVNME 2 For attaching the ring core Declaration of conformity 1 Transparent label 1 For attaching in the refrigerant label Installation and operation manual 1 Installation and operation unit instructions CD ROM 1 Installation and ope...

Page 22: ...hall be collected after cleaning Install the outdoor unit with sufficient clearance around it for operation and maintenance as shown in the next figures avoid obstacles that may hamper air intake Pay attention not to clamp cables when attaching the service cover to avoid electric shock or fire Aluminium fins have very sharp edges Pay attention to the fins to avoid injury 7 NAME OF PARTS 7 1 RAS 4 ...

Page 23: ...installation 200 300 50 100 A L B 200 mm minimum of the back space is acceptable when the right and left sides are open Keep both right and left sides without obstacles Multiple installation two units or more 300 100 A B L 100 Keep both right and left sides without obstacles When subject to direct sunlight on the back wall ensure the length B be 500 or greater Obstacles on upper side Single instal...

Page 24: ...s Multiple installation two units or more 100 A 150 A L B H Serial installation allowed up to two units Keep both right and left sides without obstacles Obstacles beside the unit Without obstacles on upper side Single installation 500 L 100 500 50 L Obstacles on upper side 500 1000 100 L 500 1000 50 L NAME OF PARTS PMML0511 rev 1 06 2019 24 ...

Page 25: ...unit Obstacles on outlet side Single Installation Multiple Installation 300 1000 C 300 1000 C 100 Close the part C not to allow the outlet air bypassed Install to avoid the drain water from upper unit falling on the lower unit Serial side way installation allowed but leave open both right and left sides Serial multiple Installation in Multiple Rows 600 A 4000 L L L L A A A 600 3000 Allow approx 10...

Page 26: ...Rubber Material Field Supplied Right side mm Left side Right side A B C A B C RAS 4 6 FS V NME 1109 116 30 1109 116 75 RAS 8 12 FSXNME 1173 110 34 5 1173 110 75 7 4 3 Suspending the unit Ensure that wall can resist the outdoor unit weight indicated in specification label plate It is recommended to select each foot support to bear the full weight of the unit in order to consider stress fatigue appl...

Page 27: ...hall not contact directly to the pipes a For the front and side piping Side piping hole Side piping hole Front piping hole RAS 4 6 FS V NME RAS 8 12 FSXNME b For the downward piping Gas piping Knock out hole Bottom base Liquid piping Gas piping Liquid piping Gas piping RAS 4 6 FS V NME RAS 8 12 FSXNME c For the rear side piping Rear Cover RAS 4 6 FS V NME RAS 8 12 FSXNME Caution For RAS 8 12 FSXNM...

Page 28: ...19 05 ID22 2 Gas pipe ø22 2 field supplied not used 1 2 3 Accessory pipe OD9 52 ID12 7 Accessory pipe OD19 05 ID25 4 Gas pipe ø25 4 field supplied Liquid pipe ø12 7 field supplied not used Heat recovery 8HP 10HP 1 2 3 Liquid pipe ø9 52 field supplied Gas pipe ø19 05 field supplied Accessory pipe OD19 05 ID15 88 Gas pipe ø15 88 field supplied 1 2 3 Gas pipe ø22 2 field supplied Gas pipe ø19 05 fiel...

Page 29: ...ver 70 m for RAS 4 6 FS V NME or over 100 m for RAS 8 12 FSXNME the pipe size of liquid line of the main pipe should be increased by one size with reducers field supplied Pipe diameter after first branch or between multi kits Total indoor unit capacity after the first branch HP Gas Liquid 4 6 ø15 88 ø9 52 6 8 99 ø19 05 ø9 52 9 11 99 ø22 20 ø9 52 12 15 6 ø25 40 ø12 70 Note If the multi kit size is ...

Page 30: ...o the same size as the main pipe diameter Pipe diameter for 2 pipes between CH Box and multi kit or between multi kits Total indoor unit capacity after the first branch HP Gas low pressure Liquid 6 ø15 88 ø9 52 6 8 99 ø19 05 ø9 52 9 11 99 ø22 20 ø9 52 12 15 6 ø25 40 ø12 70 Pipe diameter between multi kit and IU or between CH Box and IU Indoor unit capacity HP Gas Liquid 0 4 1 5 ø12 70 ø6 35 2 ø12 ...

Page 31: ...kg is required according to piping length Ensure that the total additional refrigerant charge quantity should not exceed the max additional charge quantity shown in the table below Model Refrigerant charge before shipment W0 kg Maximum additional charge kg RAS 4FS V NME 3 7 9 3 RAS 5FS V NME 4 1 8 9 RAS 6FS V NME 4 1 8 9 RAS 8FSXNME 4 2 26 1 RAS 10FSXNME 5 5 26 1 RAS 12FSXNME 5 5 26 1 Determine th...

Page 32: ...ss 1 Insert the rubber cap into the drain boss up to the extruded portions 2 Insert the boss into the unit base and turn approximately 40 degree counterclockwise 3 Drain boss is 32 mm O D 4 A drain pipe should be field supplied NOTE Do not use this drain boss set in a cold area because the drain water may freeze This drain boss is not sufficient to collect all the drain water If collecting drain w...

Page 33: ...system are very close together induction in the wiring may arise due to a rapid change in the electricity consumption of the above consumers and their start up The power supply line of the unit must have an exclusive power control switch and a certified protective circuit breaker All the electric components in the installation main power switches circuit breakers earth leakage breakers wiring conn...

Page 34: ...X TB3 TB4 PCB1 IU 4 6 5 3 7 8 9 10 A B C D TB3 TB4 PCB2 4 6 5 3 7 8 9 10 E F G H TB3 TB4 PCB3 4 6 5 3 7 8 9 10 I J K L 1 2 TB2 TB3 TB4 PCB1 4 6 5 3 7 8 A B C WC WC WC WC WC CH AP08MSSX CH AP12MSSX R L1 S L2 TB3 TB4 PCB4 4 6 5 3 7 8 9 10 M N O P CH AP16MSSX B B IU IU IU IU IU IU IU IU IU OU PS D OU G G OU 1 ELB Earth leakage breaker G CH Box 2 CB Circuit breaker WC Wired controler 3 S Main switch O...

Page 35: ...allowed impedance Zmax of the system at the connection point of the user s power supply as per EN61000 3 11 MODEL Zmax Ω RAS 4 6 FSVNME 0 24 Harmonics In relation to EN61000 3 2 and EN 61000 3 12 the situation of harmonics for each model is as follows MODELS SITUATION REGARDING IEC 61000 3 2 AND IEC 61000 3 12 Ssc xx MODELS Ssc xx KVA Complying with IEC 61000 3 2 professional use RAS 4 6 FSNME Com...

Page 36: ... Pipe length shorter than 5m Pipe length longer than 30m Control supporting existing piping Function selection setting mode External input output setting mode DSW3 supply voltage and system setting Setting not required 4HP 3 phase 5HP 3 phase 6HP 3 phase DSW4 RSW1 refrigerant system setting Setting required Set all the IU and the OU belonging to the same refrigerant cycle with the same cycle numbe...

Page 37: ... required Factory setting DSW6 function setting low ambient setting Setting required Factory setting Cooling operation under low load operation Note Make sure to apply snow protection hood DSW7 supply voltage and system setting Setting required Factory setting 400 V Heat recovery system Heat pump system DSW8 high static pressure mode setting Setting required Factory setting HSP setting NOTE When a...

Page 38: ...d control circuit wiring Only for RAS 4 6 FSVNME Cord clamp for fixing power source wiring and control circuit wiring RAS 4 6 FSNME 3N 400V 50Hz Wind the wire 3 times Cable tie Ring core Green Cable tie Wind the wire 4 times RAS 4 6 FSVNME 1N 230V 50Hz 11 4 2 For RAS 8 12 FSXNME 3 R S T MP N 1 2 Detail of terminal block for power source and control circuit 3N 400V 50Hz Cord clamp for fixing power ...

Page 39: ...smission 1 and 2 Where the total insulation resistance of the unit is below 1 MΩ the compressor insulation resistance may be low due to the refrigerant held in the compressor This may occur if the unit is not used for long periods Disconnect the compressor cables and measure the insulation resistance of the compressor If the resistance value is greater than 1 MΩ the insulation fault has occurred i...

Page 40: ...emains enabled when the compressor is at a standstill Model RAS 4 6 FSVNME RAS 4 6 FSNME RAS 8 12 FSXNME For Compressor Pressure Switches Automatic Reset Non Adjustable each one for each compressor High Cut Out MPa 4 15 Cut In MPa 3 20 Fuse capacity 1N 230V 50Hz A 50 3N 400V 50Hz A 32 50 Oil heater capacity W 24 24 40 8 x3 CCP Timer Non Adjustable Setting Time min 3 For Fan Module Fuse capacity 2 ...

Reviews: