17
Test Run Checklist
Customer Name: Seller: Check Date:
dd/MM/YY
Customer Address: Checked by:
Outdoor Unit Type: Outdoor Unit No. (YY/MM) ( / ) Compressor No.
Indoor
Unit
Type
Indoor
Unit
No.
Indoor
Unit
Type
Indoor
Unit
No.
Check items:
1. Indoor unit fan direction
Correct/Incorrect
2. Outdoor unit fan direction
Correct/Incorrect
3. Compressor noise
Yes/No
4. Operating for 20+ minutes
Yes/No
5. Air in and out temperature of each indoor unit
In:
No.1 DB / WB ºC
,
No.2 DB / WB ºC
,
Out:
DB / WB ºC
,
DB / WB ºC
,
6. Air in and out temperature of the outdoor unit
In: DB / WB ºC
Out: DB / WB ºC
7. Refrigerant temperature
Fluid pipe temperature: ºC
Compressor out temperature: ºC
8. Refrigerant pressure
Delivery pressure: MPaG
Intake pressure: MPaG
9. Voltage
Rated voltage: V
Operating voltage: L1-N V
,
L1-L2 V
Start voltage: V
10. Compressor input power and current
Power: kW
Current: A
11. Refrigerant filling level
Correct/Incorrect
12. Remote control functions
Correct/Incorrect
13. Protective device functions
Correct/Incorrect
14. System leakage check
Yes/No
15. Unit interior and exterior cleanliness
Yes/No
16. Unit covers locking status
Yes/No
17. Noise from unit covers
Yes/No
18. Outdoor unit filter cleanliness
Yes/No
19. Heat exchanger cleanliness
Yes/No
20. Outdoor unit interceptor valve status
Open/Close
21. Smooth drainage of condensate from the drain pipe
Yes/No