Hitachi RAC-60WPA Installation Manual Download Page 2

<

IA918:  A 

>

  You  may  not  be  able  to  close  the  side 

cover due to the connecting cord, under 
such  situation,  please  press  against  the 
wall  of  side  cover  to 

Þ

 x  it.

  Be  sure  that  the  hooks  (6  places)  are 

plugged  in.

  Otherwise, water leakage may occur and 

this  causes  short  circuit  or  faults.

Checking  for  the  electric  source  and  the  voltage  range

  Before  installation,  the  power  source  must  be  checked  and  necessary  wiring  work  must  be  completed.  To  make  the  proper 

wiring  capacity,  use  the  wire  gauges  list  below  for  the  lead-in  from  a  pole  transformer  and  for  the  wiring  from  a  switch  board 
of  fuse  box  to  the  outlet  in  consideration  of  the  locked  rotor  current.

  Investigate  the  power  supply  capacity  and  other  electrical  conditions  at  the  installation  location.

  Depending on the model of room air conditioner to be installed, request the customer to make arrangements for the necessary 

electrical  work  etc.

  The  electrical  work  includes  the  wiring  work  up  the  outlet.  In  localities  where  electrical  conditions  are  poor,  use  of  a  voltage 

regulation  is  recommended.

Wiring  Of  The  Outdoor  Unit

  Please  remove  the  side  cover  for  wire  connection.

!

C

O

N

N

EC

T

IO

N

 O

F

 PO

W

ER

 C

O

R

D

F

IN

A

L

 ST

A

G

O

F

 I

N

ST

A

L

L

A

T

IO

N

Insulation  And  Maintenance  Of  Pipe  Connection

1

  The  connected  terminals  should  be  completed  sealed  with 

heat  insulator  and  then  tied  up  with  rubber  strap.

  Please  tie  the  pipe  and  power  line  together  with  plastic  tape 

as  shown  in  the 

Þ

 gure  of  installation  of  both  the  indoor  and 

outdoor  units.  Then 

Þ

 x  their  position  with  holders.

  To  enchance  the  heat  insulation  and  to  prevent  water 

condensation, please cover the outdoor part of the drain hose 
and  pipe  with  insulation  pipe.

  Completely  seal  any  gap  with  putty.

    Installation  Of  Remote  Control

2

    Earth  Line  And  Circuit  Breaker

3

    Power  Source  And  Operation  Test

4

  The  remote  controller  can  be  placed  in  its  holder  which  is 

Þ

 xed  on  wall  or  beam.

  To  operate  the  remote  controller  at  its  holder,  please  ensure 

that the unit can receive signal transmitted from the controller 
at the place where the holder is to be 

Þ

 xed. The unit will beep 

when signal is received from the remote controller. The signal 
transmission  is  weaken  by  the 

ß

 orescent  light.  Therefore, 

during  the  installation  of  the  remote  control  holder,  please 
switch  on  the  light,  even  during  day  time,  to  determine  the 
mounting  location  of  the  holder.

CAUTION

!

  The  earth  line  terminal  of  the  outdoor  unit  is  below  the 

service  valve.

  To avoid short circuit, it is necessary to install circuit breaker 

depending  on  the  mounting  location  of  the  unit.

  Do  not  place  earth  line  near  the  following  objects:

  (1)  Water  pipe
  (2)  Gas  pipe  –  There  is  danger  of  catching 

Þ

 re.

  (3)  The earth line of lightning conductor and telephone —
   

short  circuit  may  occur  during  lightning.

Power  Source

WARNING

!

  Do  not  alter  the  plug  of  power  cord.

  Do  not  make  extension  to  the  power  cord.

CAUTION

!

  Please  use  a  new  socket. Accident  may  occur  due  to  the 

use  of  old  socket  because  of  poor  contact.

  Please  plug  in  and  then  remove  the  plug  for  2  –  3  times. 

This  is  to  ensure  that  the  plug  is  completely  plugged  into 
the  socket.

  Keep  additional  length  for  the  power  cord  and  do  not 

render  the  plug  under  external  force  as  this  may  cause 
poor  contact.

  Do  not 

Þ

 x  the  power  cord  with  U-shape  nail.

Operation  Test

  Please ensure that the air conditioner is in normal operating 

condition  during  the  operation  test.

  Explain to your customer the proper operation procedures 

as  described  in  the  user’s  manual.

Cable  length

up  to  15m
up  to  25m

Wire  cross-section

2.5mm

2

4.0mm

2

IMPORTANT

Fuse  Capacity

20A  time  delay  fuse

WARNING

How to Remove the Front Cover

  Open  the  cover        and  remove  the  screw.

  After open the front panel, remove the screw and open the 

cover      .

  Remove  the 

Þ

 lter,  release  the  axis  by  pulling  the  center 

portion  of  front  cover  in  the  direction  of  arrow      .

  Push  vertical  air  de

ß

 ector  handle  to  the  right  or  left  side.

  After raise the front cover from bottom side as    , release 

the  front  cover  by  pull  the  right  or  left  sides  as      .

How  to  Install  the  Front  Cover

  Insert  the  two  hooks        at  the  upper  side  certainly.

  Open  Front  Panel,  push  the  center  down  in  the  direction 

of  the  arrow  to  insert  the  axis  at  the  center  of  the  front 
cover  into  the  hook  at  the  outlet  frame.

  Fixed  the  screw  and  cover        and        .

1

6

2

3

4

5

1

6

  THIS APPLIANCE  MUST 

BE  EARTHED.

Procedures  of  Wiring

WARNING

!

Power  is  supplied  from  Outdoor  Unit

  The  naked  part  of  the  wire  core  should  be  10  mm  and 

Þ

 x  it  to  the  terminal  tightly.  Then  try  to  pull  the  individual 

wire  to  check  if  the  contact  is  tight.  Improper  insertion 
may  burn  the  terminal.

  Be  sure  to  use  only  power  cables  approved  from  the 

authorities  in  your  country.  For  example  in  Germany: 
Cable  type:  NYM  3x1.5mm2,  (fuse  =  20A  time  delay)

  Please refer to the installation manual for wire connection 

to  the  terminals  of  the  units.  The  cabling  must  meet  the 
standards  of  electrical  installation.

  There is a AC voltage of 220-240V between the L and N 

terminals. Therefore, before servicing, be sure to remove 
the plug from the AC outlet or switch off the main switch.

WARNING

!

Wiring  Of  The  Indoor  Unit

  For  wire  connection  of  the  Indoor  unit,  you  need  to  remove 

front  panel  and  electrical  cover.

  Method  to  remove  front  panel

  Refer  to  “How  to  Remove  The  Front  Cover”.

Method  to  remove  electrical  cover

  Remove  the  screw  and  electrical  cover.

  Insert the connecting cord (A,B,C,D) from the bottom of unit.

  Fixed  the  wire  to  terminal  wires 

Þ

 rmly  as  shown  in 

Þ

 gure  at 

right  side.

AUTO
RESTART
SWITCH

Electrical  cover

Screw

Power  line

Control  line

GRN  +  YEL

Indoor  Unit

GRN  +  YEL

Outdoor  Unit

Strip  wires

How  To  Connect  The  Optional  Parts

(RAC  Adapter,  Wired  Remote  Control)

[For all optional part, please refer catalog for part number]

Connection  to  the  electrical  box:

  Remove  the  cover  of  electrical  box.

  Connect the connector of wired remote controller to CN1102.

  Assemble  back  the  cover  of  electrical  box.

  Please refer to the respective user manual of wired remote 

controller  for  further  details.

  Please  be  careful  not  to  damage  lead  wires  by  edge  of 

plate  when  connecting  the  optional  parts.

[For all optional part, please refer catalog for part number]

As  for  connecting  to  H-Link,  a  separately  purchased 
RAC  Adapter  is  required.

  To install the wiring the electrical box cover must be opened.

  Connect  the  connector  of  RAC  adapter  to  CN1101.

  Assemble  back  the  cover  of  electrical  box.

  Please refer to the respective user manual of RAC Adapter 

for  further  details.

  Please  be  careful  not  to  damage  lead  wires  by  edge  of 

plate  when  connecting  the  optional  parts.

WIRED  REMOTE  CONTROLLER

H-LINK

CN1

101

CN1

102

Earth 
terminal

N

L

C D

O

U

T

D

O

O

R

 U

N

IT

  Please  mount  the  Outdoor  unit  on  stable  ground  to  prevent  vibration 

and  increase  of  noise  level.

  Decide  the  location  for  piping  after  sorting  out  the  different  types  of 

pipe  available.

  When  removing  side  cover,  please  pull  the  handle  after  undoing  the 

hook  by  pulling  it  downward.

Please  face  this  side  (suction 
side)  of  the  unit  to  the  wall.

Please  remove  side  cover 
when  connecting  the  piping 
and  connecting  cord.

Pull  downward

BASE

DRAIN  PIPE

CONDENSED WATER DISPOSAL OF OUTDOOR UNIT

Á

 

There  are  holes  on  the  base  of  Outdoor  unit  for  condensed 
water to exhaust.

Á

  In order to 

ß

 ow condensed water to the drain, the unit is installed on a 

stand or a block so that the unit is 100mm above the ground as shown 

Þ

 gure. Join the drain pipe to one hole.

Á

  At 

Þ

 rst insert one portion of the hook to the base (Portion A), then pull the 

drain pipe in the direction shown by the arrow while inserting the hook 
into the base. After installation, check whether the drain pipe cling to the 
base 

Þ

 rmly.

 

 

When Using and Installing In Cold Areas

 

When  the  air  conditioner  is  used  in  low  temperature  and  in  snowy 
conditions, water from the heat exchanger may freeze on the base surface 
to cause poor drainage. When using the air conditioner in such areas, do 
not install the bushings. Keep a minimum of 250mm between the drain 
hole and the ground. When using the drain pipe, consult your sales agent.

 

   For more details, refer to the installation Manual for Cold Areas.

Connect  the
earth  cord

A

B

C

D

After  remove  the  screw 
and  band,  put  the 
connecting  cords  and 

Þ

 x 

the  band  with  screw.

B

A

Wired  remote  controller

CN1102

RAC 

Adaptor 

cord

CN1101

The  remote  controller  must  be  slide  in
the  remote  controller  holder,  in  the  direction  as  shown  in 
the 

Þ

 gure,  until  it  hooks  at  the  lower  end  of  the  remote 

controller  holder.

Screw  (2  pieces)

Remote  Controller 
Holder

Remote  Controller

CAUTION

Outdoor  supply  cords  shall  not  be 
lighter than polychloroprene sheathed 

ß

 exible  cord  with  code  designation 

60245  IEC  57. 

      Preparation  of  Pipe

1

  Use  a  pipe  cutter  to  cut 

  the  copper  pipe.

  Jagged  edge  will  cause  leakage.

  Point  the  side  to  be  trimmed  downwards  during  trimming  to  prevent  copper 

chips  from  entering  the  pipe.

  Before 

ß

 aring,  please  put  on  the 

ß

 are  nut.

      Pipe  Connection

2

IN

ST

A

L

L

A

T

IO

N

 O

F

 R

EF

R

IG

ER

A

T

IN

G

 PI

PES 

A

N

D

 A

IR

 R

EMO

V

A

L

CAUTION

!

  Recommend  to  use 

R410A 

ß

 aring  tool.

CAUTION

!

In case of removing 

ß

 are nut of an Indoor unit, 

Þ

 rst remove a nut 

of small diameter side, or a seal cap of big diameter side will 

ß

 y 

out.  Prevent  water  from  entering  into  the  piping  when  working.

Trimming  tool

Copper  pipe

Die

Die

Copper  pipe

Flare  nut

Torque
wrench

Wrench

Removal  Of  Air  From  The  Pipe  And  Gas  Leakage  Inspection

Gas  Leakage  Inspection

Please use gas leakage detector to check if leakage occurs 
at  the  connection  of  Flare  nut  as  shown  on  the  right.

If gas leakage occurs, further tighten the connection to stop 
leakage.  (Be  sure  to  use  R410A  detector)

3

A

IR

 R

EMO

V

A

L

When  the  meter  reaches  -  101KPa 
(-76cmHg)  during  pumping,  fully 
tighten  the  shuttle.

Closed
R410A

Valve

Charge  hose

Vacuum  pump
adapter

When  pumping  starts,  slightly  loosen  the 

ß

 are  nut  to  check  of  air  sucked  in.  Then 

tighten  the 

ß

 are  nut.

Vacuum 
pump

Manifold  valve

Meter  showing  pressure

Valve

Procedures  of  using  Vacuum  Pump  for  Air  Removal

As  shown  in  right 

Þ

 gure,  remove  the  cap  of 

valve  core.  Then,  connect  the  charge  hose. 
Remove the cap of valve head. Connect the 
vacuum  pump  adapter  to  the  vacuum  pump 
and connect the charge hose to the adapter.

Fully  tighten  the  “Hi”  knob  of  the  manifold 
valve and completely unscrew the “Lo” knob. 
Run  the  vacuum  pump  for  about  10~15 
minutes, then completely tighten the “Lo” knob 
and  switch  off  the  vacuum  pump.

2

Completely  unscrew  the  spindle  of  the 
service  valve  (at  2  places)  in  anti-clockwise 
direction to allow the 

ß

 ow of refrigerant (using 

Hexagonal  Wrench  key).

Re-cap  the  service  valve  and  tighten  using 
wrench. Check the cap’s periphery if there is 
any gas leakage. The task is then completed.

Remove the charge hose and tighten the cap 
of  valve  core.  Check  the  cap’s  periphery  if 
there  is  any  gas  leakage. 

4

5

1

3

Cap  of  valve  head

Cap  of  valve  head

The  body  of 
service  valve

Hexagonal 
Wrench  Key

Cap  of  valve 
core

Outer
Diameter 
mm  (inch)

6.35  (1/4")

9.52  (3/8")

12.70  (1/2")

15.88  (5/8")

1.0  ~  1.5

1.0  ~  1.5

1.0  ~  1.5

1.0  ~  1.5

Clutch  type

A  (mm)

1.5  ~  2.0

1.5  ~  2.0

1.5  ~  2.5

1.5  ~  2.5

Wing  nut  type

Thickness

(mm)

0.8

0.8

0.8

1.0

0.0 

~

  0.5

0.0 

~

  0.5

0.0 

~

  0.5

0.0 

~

  0.5

Flare  tool  for  R410A

Clutch  type

Conventional 

ß

 are  tool

Outer

dia.of  pipe

6.35  (1/4")

9.52  (3/8")

12.70  (1/2")
15.88  (5/8")

6.35  (1/4")

9.52  (3/8")
12.7  (1/2")

Valve 

head  cap

Torque  N·m

(kgf 

·

  cm)

14.0  –  18.0  (140  –  180)

33.0  –  42.0  (330  –  420)
50.0  –  62.0  (500  –  620)
63.0  –  77.0  (630  –  770)

19.6  –  24.5  (200  ~  250)

19.6  –  24.5  (200  ~  250)
29.4  –  34.3  (300  –  350)

12.3  –  15.7  (125  ~  160)

Small  dia.  side

Large  dia.  side

Valve  core  cap

Small  dia.  side

Large  dia.  side