HITACHI  SPLIT-UNIT  AIR  CONDITIONER 

INSTALLATION  MANUAL

    +    –    Screwdriver     

  Measuring  Tape     

  Knife

  Saw  

 ø 65mm Power Drill  

 Allen Key (      4mm)

  Wrench  (14,  17,  19,  22mm)

  Gas  Leakage  Detector       

  Pipe  Cutter

  Plastic  Tape       

  Pliers       

  Flare  Tool

  Carefully  read  through  the  procedures  of  proper 

installation  before  starting  installation  work.

  The sales agent should inform customers regarding 

the  correct  operation  of  installation.

Tools  Needed  For  Installation  Work

SAFETY  PRECAUTION

  Read  the  safety  precautions  carefully  before  operating  the  unit.

  The  contents  of  this  section  are  vital  to  ensure  safety.  Please  pay  special  attention  to  the  following  sign.

  

WARNING  ........  Incorrect  methods  of  installation  may  cause  death  or  serious  injury.

  

CAUTION  .........  Improper  installation  may  result  in  serious  consequence.

 

Be  sure  that  the  unit  operates  in  proper  condition  after  installation.  Explain  to  customer  the  proper  way  of 
operating  the  unit  as  described  in  the  user’s  guide.

The  Choice  of  Mounting  Site 

  (Please  note  the  following  matters  and  obtain  permission  from  customer  before  installation).

WARNING

  The  unit  should  be  mounted  at  stable,  non-vibratory  location 

which  can  provide  full  support  to  the  unit.

WARNING

  The  outdoor  unit  must  be  mounted  at  a  location  which  can  sup-

port  heavy  weight.  Otherwise,  noise  and  vibration  will  increase.

CAUTION

  No  nearby  heat  source  and  no  obstruction  near  the  air  outlet  is 

allowed.

  The  clearance  distances  from  top,  right  and  left  are  speci

Þ

 ed  in 

Þ

 gure  below.

  The  location  must  be  convenient  for  water  drainage  and  pipe 

connection  with  the  Outdoor  unit.

  To  avoid  interference  from  noise  please  place  the  unit  and  its 

remote controller at least 1m from the radio, television and inverter 
type 

ß

 uorescent  lamp.

  To avoid any error in signal transmission from the remote controller, 

please put the controller far away from high-frequency machines 
and  high-power  wireless  systems.

  The  installation  height  of  indoor  unit  must  be  2.3m  or  more  in  a 

non  public  area. 

CAUTION

  Do  not  expose  the  unit  under  direct  sunshine  or  rain.  Besides, 

ventilation  must  be  good  and  clear  of  obstruction.

  The air blown out of the unit should not point directly to animals 

or  plants.

  The  clearances  of  the  unit  from  top,  left,  right  and  front  are 

speci

Þ

 ed  in 

Þ

 gure  below. At  least  three  of  the  above  sides  must 

be  open  air.

  Be  sure  that  the  hot  air  blown  out  of  the  unit  and  noise  do  not 

disturb  the  neighbourhood.

  Do not install at a location where there is 

ß

 ammable gas, steam, 

oil  and  smoke.

  The  location  must  be  convenient  for  water  drainage.

  Place  the  outdoor  unit  and  its  connection  wire  at  least  1m  away 

from  the  antenna  or  signal  line  of  television,  radio  or  telephone. 
This  is  to  avoid  noise  interference.

IN

D

O

O

R

 U

N

IT

Names  of  Indoor  Components

Direction  of  Piping

Figure  showing  the  Installation  of  Indoor  and 
Outdoor  Unit.

  The  difference  in  height 

between  the  indoor  and 
outdoor  unit  should  be 
kept  below  5m.

  The  connecting  pipe, 

no  matter  big  or  small, 
should  all  be  insulated 
with  insulation  pipe  and 
then wrapped with plastic 
tape.  (The  insulator  will 
deteriorate  if  it  is  not 
wrapped  with  tape).

The connection of insulated 
drain  hose.

Please  use  insulated  drain 
hose  for  the  indoor  piping 
(commercial  product).

O

U

T

D

O

O

R

 U

N

IT

Be  sure  to 
completely 
seal  any 
gap  with 
putty.

T h e r e   a r e   4   d i r e c t i o n s  
allowed,  namely,  horizontally 
perpendicular  to  the  unit, 
vertically  down  from  right, 
horizontally out from right and 
horizontally  out  to  left.
Don't form the piping downward 
at  the  left  of  the  unit.

Installation of Mounting Plate, Wall Penetration and Installation of Protection Pipe

1

CAUTION

  The draining of the water container inside the indoor unit can be done from the left. 

Therefore the mounting plate must be 

Þ

 xed horizontally or slightly tilted towards the 

side of drain hose. Otherwise, condensed water may over

ß

 ow the water container.

Direct  Mounting  On  The  Wall

  Please  use  hidden  beams  in  the  wall  to  hold  the  mounting  plate.

Wall  Penetration  and  Installation  of  Protection  Pipe

  Drill  a  ø  65mm  hole  on 

wall  which  is  slightly  tilted 
towards  the  outdoor  side. 
Drill the wall at a small angle.

  Cut  the  protection  pipe 

a c c o r d i n g   t o   t h e   w a l l 
thickness.

  Empty  gap  in  the  sleeve 

of  protection  pipe  should 
be  completely  sealed  with 
putty  to  avoid  dripping  of 
rain  water  into  the  room.

      Installation  of  the  Indoor  Unit

2

VERTICALLY  DOWNWARD  PIPING

    Preparation

  Connect  connecting  cord.

  Pull  out  the  pipe,  connecting  cord  and  drain  hose.

    Installation

  The  upper  part  of  the  indoor  unit  is  hanged  on  the  mounting  plate.

  The projection at the lower part of the indoor unit is hooked onto the mounting plate.

Please  pull  the  lower 
part  of  the  indoor  unit 
outwards  to  check  if  the 
unit  is  hooked  onto  the 
mounting plate. Improper 
installation  may  cause 
vibration  and  noise.

CAUTION

HORIZONTAL  PIPING

    Preparation

Change  of  Drain  Hose  and  Installation  Procedures.

  Exchange the location of drain hose and drain cap during horizontal piping as shown 

in 

Þ

 gure  below.  Be  sure  to  plug  in  the  drain  hose  until  the  insulating  material  folds 

upon  itself.

  Please  use  pliers  to  pull  out  the  drain  cap.

  (This  is  an  easier  way  to  remove  the  drain  cap).

Horizontal  &  Downward  Piping  –  Making  Openings

  During  horizontal  or  downward  piping,  use  a  knife  to  cut 

openings  as  shown  in 

Þ

 gure.  Then  smoothen  the  edges 

of  openings  with  a 

Þ

 le.

CAUTION

  The  rubber  strap  used  for 

Þ

 xing  the  insulator  should 

not be tied with great force. 
Otherwise, this will damage 
heat insulation and causes 
water  condensation.

CAUTION

  Please 

Þ

 x  in  the  plastic 

core  after 

ß

 aring  to  avoid 

plastic  chips  entering  the 
pipes.

CAUTION

You are free to choose the side (left or right) for the installation of drain 
hose.  Please  ensure  the  smooth 

ß

 ow  of  condensed  water  of  the  indoor 

unit  during  installation.  (Carelessness  may  result  in  water  leakage.)

CAUTION

Be  sure  that  the 
drain  hose  is  not 
loosely connected 
or  bent.

<

IA918:  A 

>

Be sure that the wire is not 
in  contact  with  any  metal 
in  the  wall.  Please  use 
the protection pipe as wire 
passing through the hollow 
part  of  the  wall  so  as  to  
prevent  the  possibility  of 
damaged  by  mouse.

CAUTION

    Installation  of  Drain  Hose

3

IN

D

O

O

R

 U

N

IT

Screw  for  Remote 
Controller  Holder

( 3 . 1 x 1 6 )

AAA  Size  Battery

Remote  Controller  Holder

Mounting  Plate

Qty

No.

Component’s  Name

1

6

1

2

2

Remote  Controller

Air  Purifying  Filter

!

!

!

!

!

!

!

!

!

!

!

!

!

  Remove  the  cap  for  drain  hose  installation

CAUTION

Condensed  water  may  leak  out  if  not  inserted  properly.

!

  Transform  the  piping  while  holding  down  the  lower 

portion  of  pipe-support  by  hand.

Dimension  of  Mounting  Stand

of  the  outdoor  unit

(unit  :  mm)

Indoor  Unit

Outdoor  Unit

 

RAK-60PPA 

      RAC-60WPA

1

2

3

4

5

6

7

1

2

WARNING

!

CAUTION

!

 

A  circuit  breaker  or  fuse  (20A  time  delay)  must  be  installed.  Without  a  circuit  breaker  or  fuse  the  danger  of  electric  shock  
exists.

 

A  main  switch  with  a  contact  gap  of  more  than  3mm  has  to  be  installed  in  the  power  supply  line  to  the  outdoor  unit.

  Do  not  install  the  unit  near  a  location  where  there  is 

ß

 ammable  gas.  The  outdoor  unit  may

 

catch 

Þ

 re  if 

ß

 ammable  gas  leaks  around  it.

  Please  ensure  smooth 

ß

 ow  of  water  when  installing  the  drain  hose.

  Piping  shall  be  suitable  supported  with  a  maximum  spacing  of  1m  between  the  supports.

 

Please  request  your  sales  agent  or  quali

Þ

 ed  technician  to  install  your  unit.  Water  leakage,  short  circuit  or 

Þ

 re  may  occur  if 

you  do  the  installation  work  yourself.

  Please  observe  the  instructions  stated  in  the  installation  manual  during  the  process  of  installation.  Improper  installation  may 

cause  water  leakage,  electric  shock  and 

Þ

 re.

  Make  sure  that  the  units  are  mounted  at  locations  which  are  able  to  provide  full  support  to  the  weight  of  the  units.  If  not, 

the  units  may  collapse  and  impose  danger.

  Observe  the  rules  and  regulations  of  the  electrical  installation  and  the  methods  described  in  the  installation  manual  when 

dealing  with  the  electrical  work.  Use  power  cables  approved  by  the  authorities  of  your  country.

  Be  sure  to  use  the  speci

Þ

 ed  wire  for  connecting  the  indoor  and  outdoor  units.  Please  ensure  that  the  connections  are  tight 

after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating 
and 

Þ

 re.

  Please use the speci

Þ

 ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock 

and 

Þ

 re  may  occur.

  Be  sure  to  use  the  speci

Þ

 ed  piping  set  for  R410A.  Otherwise,  this  may  result  in  broken  copper  pipes  or  faults.

  When  installing  or  removing  an  air  conditioner,  do  not  allow  air  or  moisture  to  remain  in  the  refrigeration  cycle.  Otherwise, 

pressure  in  the  refrigeration  cycle  may  become  abnormally  high  so  that  a  rupture  may  be  caused.

  Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with 

Þ

 re, a poisonous 

gas  may  occur.

  After  completion  of  installation  work,  check  to  make  sure  that  there  is  no  refrigeration  gas  leakage.  If  the  refrigerant  gas 

leaks  into  the  room,  coming  into  contact  with 

Þ

 re  in  the  fan-driven  heater,  space  heater,  etc.,  a  poisonous  gas  may  occur.

  Unauthorized  modi

Þ

 cations  to  the  air  conditioner  may  be  dangerous.  If  a  breakdown  occurs  please  call  a  quali

Þ

 ed  air 

conditioner  technician  or  electrician.  Improper  repairs  may  result  in  water  leakage,  electric  shock  and 

Þ

 re,  etc.

3

Bush

Names  of  Outdoor  Components

Qty

No.

Item

Drain  Pipe

1

8

9

Bush

1

10

Procedures  of  Installation  and  Precautions

  Procedures  to 

Þ

 x  the  mounting  plate.

1. Drill  holes  on  wall. 

  2.Fix  the  mounting  plate  on

  (As  shown  below) 

      wall  with  4.1  x  32  screw

    

    (As  shown  in 

Þ

 gure  below)

  Procedures  to 

Þ

 x  the  holder  of  remote  control.

1. Drill  holes  on  wall.
  (As  shown  below)

Plug

Connecting 
cords,  pipe  and 
drain  hose  must 
be  laid  together 
with  Vinyl  tape.

Mounting  plate

Drain  Hose

Protection  Pipe

Refrigerating 
Pipe

Connecting 
Cord

Lift  the  body 
of  the  unit 
upwards  and 
then  force  it 
downwards.

Mounting  plate

Projection

Hook

INSTALLATION  OF  REFRIGERATING  PIPES AFTER  CONNECTION

  The  refrigerating  pipes  should  be  adjusted  to 

Þ

 t 

into  the  hole  on  the  wall  and  then  ready  for  further 
connection.

  The terminals of 2 connected pipes must be covered 

with insulator used for terminal connection. Then the 
pipes  are  wrapped  with  insulation  pipe.

  Connect the connecting cord after removing electrical 

cover. (Refer to “CONNECTION OF POWER CORD”)

  After  adjustment, 

Þ

 t  the  connecting  cord  and  pipes 

into  the  space  available  under  the  indoor  unit.  Use 
holder  to  hold  them  tight.

Drain hose

Connecting cord

Pipe

THE  CONNECTION  OF  REFRIGERATING  PIPE  DURING  THE 
INSTALLATION  OF  INDOOR  UNIT

Preparation  To  Install  Refrigerating  Pipes

  The  refrigerating  pipes  and  connecting  cord 

transform  and  are  attached.

  The  end  of  the  refrigerating  pipes  are  at  locations 

marked  with  “ 

     

  ”  symbol.

    Installation

Hang the Indoor unit onto the mounting plate. Use the temporary 
stand  at  the  back  of  the  Indoor  unit  to  push  its  lower  part 
15cm  forwards.

  Place  the  drain  hose  through  the  hole  on  the  wall.

  Wrap  the  refrigerating  pipes  with  insulation  pipe  after 

connecting  refrigerating  pipe.

  Connect the connecting cord after removing electrical cover. 

(Refer  to  “Connection  of  Power  Cord”)

  After adjustment, the connecting cord and refrigerating pipes 

are  placed  into  the  space  available  under  the  Indoor  unit.

  The projection of Indoor unit must hook to the mounting plate.

Heat  insulation 
pipe

Connecting  cord

Refrigerating  pipe

Protection  pipe

Pull  this  to  the  front 
during the connection 
of  refrigerating  pipes 
to  ease  task.

Drain  hose

Connecting  cord

Connected 
section