Notes:
(1) Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto and when the compressor speed (P section) due to temperature difference between setting
temperature (including the correction shift only) and room temperature is CMAX or higher.
(2) Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3°C (thermo off) and iii) when room temperature
has achieved setting temperature –1°C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change
operation mode.
(3) During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3°C. After thermo off, operation continue in Fuzzy control mode.
(4) Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5) During normal cooling mode, compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP. No time constrain if indoor tem-
perature is higher than CLMXTP.
(6) When fan is set to “Hi”, compressor rpm will be limited to CSTD.
(7) When fan is set to “Med”, compressor rpm will be limited to CJKMAX.
(8) When fan is set to “Lo”, compressor rpm will be limited to CBEMAX.
(9) During Cool Dashed, when room temperature reaches set temperature –1°C compressor rpm is actual rpm x DWNRATEC.
2
,for RAK-15Q PB,RAK-18/ 25/ 50RPB only
37
Summary of Contents for RAC-35WPC
Page 23: ...23 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 27: ...27 ...
Page 30: ...WIRING DIAGRAM RAK 35RPC RAK 50RPC 30 ...
Page 32: ...CIRCUIT DIAGRAM MODEL WIRED REMOTE CONTROL SEND RAK 35RPC RAK 50RPC POWER FOR CLEANNESS 32 ...
Page 63: ...64 63 ...
Page 66: ...35 and page 36 66 ...
Page 68: ...5 68 3 ...
Page 69: ...69 ...