Do not operate for 5 minutes
or more.
Cautions
1. Applying power directly to the outdoor unit will cause a rush current to stress the outdoor unit.
Therefore, if the indoor unit is not out of order, do not use the method descried in 2).
2. Before making the connections, be sure to turn off the breaker.
3. Do not under any circumstances run the product for more than 5 minutes.
4. Doing work with the compressor connector removed will cause the LD301 to blink 4 times.
It will not start.
5. For another test run, turn off the breaker and turn it back on. (The test switch is accepted only
once after power-on. After operation by remote control, it is not accepted.)
6. When the operation with the test switch is over, turn off the breaker and set the connectors back.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
1. Connect the large dia. pipe side and small dia. pipe side service valve using a pipe.
Parts to be prepared
(1) Reducing union
(6.35 mm)
3/8” (9.52 mm)
(2) Copper pipe (1/4” and 3/8”)
Connect the small diameter service
valve and the large diameter service
valve using the reducing union and
copper pipe as shown on the right.
Charge refrigerant of 300g
after vacuuming (
1
)
The operation method is the same as “How to operate using the connector to servicing the outdoor unit”.
1
The charging amount of 00g is equivalent to the load in normal operation.
Do not operate for more than 5
minutes
Large dia. service valve
Reducing union
(1/4” and 3/8”)
Copper pipe
(1/4”)
Small diameter
service valve
Reversing
valve
Compressor
Outdoor unit
RAC-25/35WSE
RAC-50WSE
3
1/4”
1/4
1/4
1/4
1/4
135
Summary of Contents for RAC-25WSE
Page 35: ...MODEL RAC 50WSE 35 ...
Page 39: ...MODEL RAC 25WSE RAC 35WSE OUTDOOR UNIT 39 ...
Page 40: ...MODEL RAC 50WSE OUTDOOR UNIT 40 ...
Page 42: ...MODEL RAK 25 35 50PSEW RAK 25 35 50PSES 42 ...
Page 43: ...MODEL RAC 25WSE RAC 35WSE 43 ...
Page 44: ...MODEL RAC 50WSE 44 ...
Page 67: ...DESCRIPTION OF MAIN CIRCUIT OPERATION RAK 25 35 50PSEW RAK 25 35 50PSES 67 ...
Page 73: ...10 10 10 10 10 DSW1 73 ...
Page 79: ...RL1 RL1 RL2 5 5 5 5 79 ...
Page 85: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 85 ...
Page 87: ...2A Fuse DC300 330V 7 7 1 87 ...
Page 88: ...2A DC300 330V 60 100 88 ...
Page 89: ...L N 300 330 L N 50WSE 89 ...
Page 90: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 90 ...
Page 94: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 94 ...
Page 96: ...2A Fuse DC300 330V 7 1 7 96 ...
Page 97: ...2A DC300 330V 30 60 97 ...
Page 107: ...92 107 ...
Page 109: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 25 35WSE 109 ...
Page 110: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50WSE 110 ...