WARNING
Do not use a soldering iron with
transformer: Otherwise, thermal fuse
inside transformer will be blown.
DISCHARGE, PROCEDURE AND POWER SHUT OFF METHOD FOR
POWER CIRCUIT
Caution
Voltage of about 350 V is charged between the terminal of smoothing capacitors.
During continuity check for each circuit part of the outdoor unit, be sure to discharge the smoothing
capacitors.
Discharge Procedure
LEAD WIRE
RAC-18/25/35WP
E
MAIN P.W.B.
1. Turn off the power.
2. After power is turned off, wait for 10 minutes or more. Then, remove electrical parts cover
and apply soldering iron of 30 to 75 W for 15 seconds or more to IPM(24 ) and IPM(
terminals on the main P.W.B. as shown in the figure below, in order to discharge voltage
in smoothing capacitor.
SOLDERING IRON (30 TO 75W)
RAC-
50WP
20)
4
2/
E
LEAD WIRE
SOLDERING IRON (30 TO 75W)
42
Summary of Contents for RAC-18WPE
Page 13: ...WIRING DIAGRAM RAC 18 25 35WPE RAC 42 50WPE 13 ...
Page 14: ...MODEL RAC 18 25 35WPE 14 AX 16G814 ...
Page 15: ...MODEL RAC 42 50WPE 15 ...
Page 24: ...5 5 1 10 11 12 74 74 70 70 74 75 5 1 HIC P W B 74 70 75 24 ...
Page 26: ...2A Fuse DC300 330V 7 7 1 26 ...
Page 27: ...2A DC300 330V 60 100 27 ...
Page 28: ...L N 300 330 L N 42 50WPE 28 ...
Page 29: ...300 330 C021 C023 500 450V 16V R249 33 ACT IP CUT 30 29 ...
Page 33: ...5 5 1 74 74 70 70 74 75 5 1 HIC P W B 40 41 42 74 70 75 33 ...
Page 35: ...2A Fuse DC300 330V 7 1 7 35 ...
Page 36: ...2A DC300 330V 30 60 36 ...
Page 45: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 18 25 35WPE 45 ...
Page 46: ...SELF DIAGNOSIS LIGHTING MODE MODEL RAC 42 50WPE 46 ...
Page 60: ...RAC 18WPE RAC 25WPE RAC 35WPE RAC 42WPE RAC 50WPE JCH WH NO 0120E 60 ...