INDOOR UNIT

 WARNING

THE CHOICE OF MOUNTING SITE

 

(Please note the following matters and obtain permission from customer before installation.)

• The unit should be mounted at stable, non-vibratory location

which can provide full support to the unit.

 CAUTION

• No nearby heat source and no obstruction near the air

outlet is allowed.

• The clearance distances from top, right and left are

specified in figure below.

• The location must be convenient for water drainage and

pipe connection with the Outdoor unit.

• To avoid interference from noise, please place the unit and

its remote controller at least 1m from the radio and
television.

• To avoid any error in signal transmission from the remote

controller, please put the controller far away from high-
frequency machines and high-power wireless systems.

OUTDOOR UNIT

 WARNING

• The Outdoor unit must be mounted at a location which can

support heavy weight. Otherwise, noise and vibration will
increase.

 CAUTION

• Do not expose the unit under direct sunshine or rain.

Besides, ventilation must be good and clear of obstruction.

• The air blown out of the unit should not point directly to

animals or plants.

• The clearances of the unit from top, left, right and front are

specified in figure below. At least three of the above sides
must be open air.

• The installation height should be at least 2,300 mm or more

from the floor.

• Be sure that the hot air blown out of the unit and noise do

not disturb the neighbourhood.

• Do not install at a location where there is flammable gas,

steam, oil and smoke.

• The location must be convenient for water drainage.
• Place the Outdoor unit and its connecting cord at least 1 m

away from the antenna or signal line of television, radio or
telephone. This is to avoid noise interference.

Names of Indoor Components

The Length of Indoor Unit

Connecting Cord

above

0.9 m

above

1.6 m

Direction of Piping

Backward piping
from left

Connection

There are 6 directions allowed,
namely, backward piping,
backward piping from left,
horizontally piping from right,
horizontally piping from left,
vertically down from right, vertically
down from left.

1

2

Figure showing the Installation
of Indoor and Outdoor Unit.

above

50mm

 above 250mm

 above 100mm

about 300mm

about 0.45m

must not bend

The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)

• The refrigerating machine oil is

easily affected by moisture. Use
caution to prevent water from
entering the cycle.

• The difference in height between

the indoor and outdoor unit
should be kept below 5m.

• The connecting pipe, no matter

big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).

The connection of insulated drain
hose.
          Inner diameter 16mm

Please use insulated drain hose for
the indoor piping (commercial
product)

above 100mm

 above 400mm

 above 150mm

give clearance
as wide as
possible

above

200mm

Be sure to
completely
seal any gap
with putty.

Maximum pipe length 10m

When the power is
supplied from the
indoor unit, pull the
power cable from the
cable drawer at the
right or left side of
the indoor unit.

above 200mm

Cable drawer (right side)

2,300 mm or more

The clearances of the
unit from top, left, right
and front are specified
in figure below. At least
three of the above sides
must be open air.

Screw for Hanger

(

ĭ

4 . 1 x 3 2 )

AAA Size Battery

Hanger

Qty

No.

Component’s Name

1

6

2

Remote Controller

1

2

3

4

5

1

1

Drain Pipe

Dimension of Mounting

 Stand of the outdoor unit

(unit : mm)

500
750

50

330

310

290

500
698

45

300

282

257

(10GH5/10KH3)

(14GH5/14KH3)

The installation height of the indoor unit must be at least

 2300mm or more from the floor.

Summary of Contents for RAC-10GH5

Page 1: ...7 COOLING UNIT CONDENSING UNIT COOLING UNIT CONDENSING UNIT 13 648 1 100 5 05 1 090 5 00 2 50 3 0 8 530 11 942 WALL TYPE 1ij 230V 50 HZ DIMENSIONS mm TYPE MODEL POWER SOURCE COOLING CAPACITY HEADING CAPACITY RAS 10KH3 RAC 10KH3 RAS 14KH3 RAC 14KH3 780 3 58 770 3 54 2 80 9 554 5 4 0 505 30 17 RAS 14KH3 RAC 14KH3 RAC 14GH5 RAC 1 H3 4K RAS 14KH3 780 280 210 9 RAS 10GH5 RAC 10GH5 RAS 14GH5 RAC 14GH5 HO...

Page 2: ... 1 ...

Page 3: ... 2 ...

Page 4: ... 3 ...

Page 5: ... 4 ...

Page 6: ...RMOSTAT REMOTE CONTROL SWITCH LIQUID CRYSTAL 28 W ASL145SV C7LU YES YES NO NO NO NO YES NO WITHOUT REFRIGERANT BECAUSE COUPLING IS FLARE TYPE UNIT PIPES MAX 20m REFRIGERANT CHARGING VOLUME Refrigerant 410A RAC 10AH1 RAC 08AH1 RAC 14AH1 780g RAS 08AH1 RAS 10AH1 RAS 10GH5 RAS 10KH3 RAS 14GH5 RAS 14KH3 RAC 10GH5 RAC 10KH3 RAC 14GH5 RAC 14KH3 7 W 11 W YES YES YES YES YES NO NO NO 3 15 A NO NO 891WP 1A...

Page 7: ...us setting right after the power failure In case of the power failure during the use of timer mode Sleep Timer or ON OFF Timer timer mode is cancelled and the air conditioner stops operation Please reset the remote controller to restart the unit after the power has been restored RAS 14KH3 RAS 10GH5 RAS 14GH5 RAS 10KH3 RAS 14KH3 ...

Page 8: ......

Page 9: ......

Page 10: ...g g ...

Page 11: ......

Page 12: ...the horizontal air deflector within the adjusting range shown on the right When the operation is stopped the horizontal air deflector moves and stops at the position where the air outlet closes CAUTION In Cooling operation do not keep the horizontal air deflector swinging for a long time Some dew may form on the horizontal air deflector and dew may drop Adjustment of the conditioned air in the upw...

Page 13: ...he remote control if there is no response from the air conditioner unit and or the remote control has fading and dim displays the batteries in the remote control device need to be removde and replaced with new ones ...

Page 14: ......

Page 15: ......

Page 16: ...r purifying filter frame 2 Vacuum dust from the Pre filter and air purifying filter using vacuum cleaner If there is too much dust rinse under running tap water and gently brush it with soft bristle brush Allow filters to dry in shade 3 Re insert the air purifying filter to the filter frame Set the Pre filter with FRONT mark facing front and slot them into the original state After attaching the Pr...

Page 17: ...ly insert them into the holes Projection Flange Hole Remove the front panel and wash with clean water Wash it with a soft sponge After using neutral detergent wash thoroughly with clean water When front panel is not removed wipe it with a soft dry cloth Wipe the remote controller thoroughly with a soft dry cloth Wipe the water thoroughly If water remains at indicators or signal receiver of indoor ...

Page 18: ...LF YEARLY OR YEARLY CONTACT YOUR SALES AGENT OR SERVICE SHOP Is the earth line disconnected or broken Is the mounting frame seriously affected by rust and is the outdoor unit tilted or unstable Is the plug of power line firmly plugged into the socket Please ensure no loose contact between them ...

Page 19: ......

Page 20: ...oor Components The Length of Indoor Unit Connecting Cord above 0 9 m above 1 6 m Direction of Piping Backward piping from left Connection There are 6 directions allowed namely backward piping backward piping from left horizontally piping from right horizontally piping from left vertically down from right vertically down from left 1 2 Figure showing the Installation of Indoor and Outdoor Unit above...

Page 21: ...CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS 08AH1 RAS 10AH1 RAS 14AH1 RAS 10GH5 RAS 10KH3 INDOOR UNIT 220 HITACHI RAS 14GH5 RAS 14KH3 ...

Page 22: ...CONSTRUCTION AND DIMENSIONAL DIAGRAM OUTDOOR UNIT MODEL RAC 08AH1 RAC 10AH1 RAC 10GH5 RAC 10KH3 ...

Page 23: ... outlet Handle Holes for anchor bolt 2 ø12 x 6 slots for ø8 0 bolt for 2 ø8 0 bolt Notch for anchor bolt Fixing hole Drain hole Drain hole OUTDOOR UNIT More than 50 More than 100 More than 200 More than 300 Rear side Service space MODEL RAC 14AH1 RAC 14GH5 RAC 14KH3 ...

Page 24: ...H5 RAS 10KH3 RAS 14GH5 WM 566 WM 316 WA 175 19 RAS 10GH5 RAS 14GH5 RAS 14KH3 RAS 10GH5 RAS 10KH3 RAS 14GH5 RAS 14KH3 RAS 10KH3 RAS 14KH3 RA 10GH5 RA RA 14GH5 RA 14KH3 C C 10KH3 C C 6 8 11 WA 250 WM 448 WA 341 ...

Page 25: ... 20 RAC 10GH5 RAC 10KH3 RAC 14GH5 RAC 14KH3 AGS 08TV B7AT 220 240 220 240 3 72 3 60 2 45 2 92 AGS 08TV B7AT ...

Page 26: ...RAS RAC 10GH5 RAS 10KH C 10KH3 RAS 14GH5 RAC 14GH5 RAC 10GH5 RAC 10KH3 21 10GH5 3 RA RAS 1 H C 1 H3 3 RA 4K 4K 1 5 25 RAC 1 GH5 RAC 1 4 4KH3 ...

Page 27: ...1 685 625 5 1 32 5 5 1 1 0 1 8 8 8 8 52 1 52 1 52 1 52 1 2 5 1 2 5 1 1 225 1 02725 7 7 25 1 25 1 5 5 5 5 7 50 1 2 5 INDOOR UNIT OUTDOOR UNIT 872 6 3 02725 1 5 2 2 7 225 1 5 5 9 56 1 9 9 5 7 50 1 2 5 1 8 6 7 8 9 9 5 9 56 1 5 8 8 5 3 7 1 25 1 8 5 5 1 02725 287 225 2035 6625 9 5 51 51 22 RAS 10GH5 RAC 10GH5 RAS 14GH5 RAC 14GH5 RAS 10KH3 RAC 10K H3 RAS 1 H3 RAC 14K H3 4K ...

Page 28: ...12 6 6835 6625 9 5 6725 9 5 6725 1 5 1 5 0 55 7 0 7 0 7 0 7 0 7 0 7 f f f f f 3 725 9 9 9 9 5 5 7 55 3 7 8 5 32 5 5 555 03 09 5 0 9 6 6 6 0 4 795 795 7 0 9 3 0 7 5 3 6 55 5 0 7 51 9 8 1 16 6 6 8 1 16 55 55 55 0 7 55 55 251 1 1 1 55 55 55 55 1 1 1 1 1 1 1 211 725 6 3 6 5 3 6 3 9 3 9 3 9 6 5 3 9 3 9 855 17 5 7 1 4 7 4 4 51 51 60 60 1 8 67 6 0 2 26 66 3 6 3 86 55 55 55 55 üü 55 55 55 9 1 6 9 3 3 1 1 ...

Page 29: ... 24 ...

Page 30: ... 25 RAS 10GH5 RAS 10KH3 RAS 14GH5 RAS 14KH3 ...

Page 31: ... 26 ...

Page 32: ... 27 ...

Page 33: ... 28 ...

Page 34: ... 29 ...

Page 35: ... 30 ...

Page 36: ...RAS 10GH5 RAC 10GH5 31 RAS 10KH3 RAC 10KH3 ...

Page 37: ...RAS 14GH5 RAC 14GH5 32 9 52 11 9 52 3 8 3 8 RAS 14KH3 RAC 14KH3 9 52 11 9 52 3 8 3 8 ...

Page 38: ...0 24 22 17 18 201 16 19 23 14 10 11 9 21 1 8 12 13 7 3 15 ᄥః ಡ ᄥय Շನ ಁՇัէ ഄ ၇ၟ ส פ മ ᆑՎ ஜ ర ฑ පᄘ פ മ פ ั ഄ ၇ၟ 2 6 5 4 29 30 32 31 28 5 1 9 5 6 6 0 5 2 1 2 2 1 12 6 68335 6625 1 86 685 625 5 57 1 1 1 1 5 5 9 56 1 5 287 1 5 1 5 0 1 5 1 1 1 1 5 26 1 5 2 32 5 5 1 9 5 6725 9 5 6725 33 ...

Page 39: ...W O L F R I A L A I T N E G N A T 1 0 2 Y S S A T R O P P U S N A F 1 1 2 R R E V O C S 1 2 2 D N A B 1 3 2 R O T C E L F E D R I A L A C I T R E V 2 4 2 Y S S A T E N I B A C 1 5 2 R E V O C R E P P U 1 6 2 E T A L P G N I T N U O M 1 7 2 N O I T A C I D N I B W P 1 8 2 29 HWRAS 10GH5 A08 HWRAS 14GH5 A04 1 P W B MAIN R E V O C S T R A P C I R T C E L E 1 0 3 E T A L P S T R A P C I R T C E L E 1 ...

Page 40: ... O L F R I A L A I T N E G N A T 1 0 2 Y S S A T R O P P U S N A F 1 1 2 R R E V O C S 1 2 2 D N A B 1 3 2 R O T C E L F E D R I A L A C I T R E V 2 4 2 Y S S A T E N I B A C 1 5 2 R E V O C R E P P U 1 6 2 E T A L P G N I T N U O M 1 7 2 N O I T A C I D N I B W P 1 8 2 29 HWRAS 10GH5 A08 HWRAS 14GH5 A04 1 P W B MAIN R E V O C S T R A P C I R T C E L E 1 0 3 E T A L P S T R A P C I R T C E L E 1 1...

Page 41: ...RAC 10GH5 RAC 10KH3 36 31 ...

Page 42: ...P M O C 1 4 2 R E V O C R L O 1 5 2 1 6 2 HEAT INSULATOR PIPE 1 7 2 FAN MOTOR SUPPORT 1 8 2 SUPPORT PLATE 1 9 2 PARTITION 1 0 3 DRAIN PIPE 31 1 VALVE COVER RAC 10GH5 RAC 10KH3 RAC MES09HX001 RAC MES09HX002 HWRAC 10GH5A01 HWRAC 10GH5A02 HWRAC 10GH5A03 HWRAC 10GH5A04 HWRAC 10GH5A05 RAC MES09HX008 HWRAC 10GH5A06 HWRAC 10GH5A07 RAC MES09HX011 RAC MES09HX012 HWRAC 10GH5A08 RAC MES09HX014 HWRAC 10GH5A09...

Page 43: ...RAC 14GH5 RAC 14KH3 38 ...

Page 44: ...S S E R P M O C 1 4 2 R E V O C R L O 1 5 2 1 6 2 HEAT INSULATOR PIPE 1 7 2 FAN MOTOR SUPPORT 28 SUPPORT PLATE 1 9 2 PARTITION 1 0 3 HANDLE 1 1 3 DRAIN PIPE RAC MES14HX028 RAC MES14HX029 RAC MES14HX030 RAC MES14HX025 RAC MES14HX026 HWRAC 14GH5A12 HWRAC 14GH5A13 HWRAC 14GH5A10 HWRAC 14GH5A11 RAC MES14HX023 RAC MES14HX024 HWRAC 14GH5A08 HWRAC 14GH5A09 RAC MES14HX019 RAC MES14HX020 HWRAC 14GH5A07 RAC...

Page 45: ... 40 ...

Page 46: ... 41 ...

Page 47: ... 12 RAS 10GH5 RAC 10GH5 RAS 14GH5 RAC 14GH5 RAS 10KH3 RAC 10KH3 RAS 14KH3 RAC 14KH3 ...

Reviews: