Hitachi NE-S1 series Installation Manual Download Page 8

Chapter 2 

– Electromagnetically compatible installation of drives and drive systems

 

2-5 

Minimizing radiated interference 

 

The  frequency  inverter  of  series  NE-S1  meet  the  limits  of  EN61800-3,  C1/C2/C3,  for  radiated 
interference,  if  the  specified  line  filter  is  used  and  installation  is  performed  according  to  our 
instructions. 

The prerequisite is that all analog and digital control lines are laid shielded. 

With compact systems, if for example the frequency inverter  is  communicating  with  the  steering 
unit, in the same control cabinet connected at the same PE-Potential, the screen should be put on, 
on both sides with PE. 

With  branch  systems,  if  for  example  the  communicating  steering  unit  is  not  in  the  same  control 
cabinet and there is a distance between the systems, we recommend to put on the screen only on 
the side of the frequency inverter. If it is possible, direct in the cable entry section of the steering 
unit. This is very important, if there is a long distance between the system and you expect there can 
be different PE-Potential between the systems. 

You should allow the effective shield area of these lines to remain as large as possible; i.e., do not 
move  the  shield  further  away  than  absolutely  necessary.  The  distance  between  an  interference 
source and an interference sink (interference-threatened device) essentially determines the effects 
of the emitted interference on the interference sink. The interference field emitted by the frequency 
inverter  falls  sharply  with  increasing  distance.  Please  note  that  the  emitted  interference  field 
(frequency range 30 MHz - 1 GHz) of a drive (drive system) is measured at a distance of 10 m in 
accordance with EN61800-3. Every device placed closer than 10 m to a source of interference will 
thus  be  impacted  by  appreciably  higher  interference  amplitudes.  For  this  reason,  you  should  use 
only interference-free devices and maintain a minimum distance of 0.25 m from the drive. Devices 
which react sensitively to interference from electric and magnetic fields should be kept at least a 
distance of 0.25 m from the following components: 

 

Frequency inverter 

 

EMC input/output filters 

 

Input or output reactors/transformers 

 

Motor cable (even if shielded) 

 

External rheostat and its wiring (even if shielded) 

 

AC/DC commutator motors, including any attached separate fans 

 

DC intermediate circuit coupling/wiring (even if shielded) 

 

Connected inductors like relays, contactors, solenoid valves, brakes (even if shielded) 

Very  frequently,  interference  is  coupled  in  through  installation  cables.  You  can  minimize  this 
influence by laying interfering cables separately, a minimum of 0.25 m from cables susceptible to 
interference.  A  particularly  critical  point  is  laying  cables  parallel  over  larger  distances.  If  two 
cables intersect, the interference is smallest if they intersect at an angle of 90°. Cables susceptible 
to  interference  should  therefore  only  intersect  motor  cables,  intermediate  circuit  cables,  or  the 
wiring of a rheostat at right angles and never be laid parallel to them over larger distances. 

 

 

 

 

 

 

 

 

Summary of Contents for NE-S1 series

Page 1: ...Electromagnetically Compatible Installation Guide Book Inverter Series NE S1 Hitachi Europe GmbH ...

Page 2: ...ING RADIATED INTERFERENCE 2 5 USING EMC COMPLIANT CABLES 2 6 INSTALLING THE MOTOR CABLE 2 7 INSTALLING CONTROL AND SIGNAL LINES 2 7 SHIELDING AND GROUNDING FOR INSTALLATION IN SWITCH CABINETS 2 8 CHAPTER 3 INFLUENCE OF THE MOTOR CABLE LENGTH 3 1 CHAPTER 4 FURTHER NOTES 4 1 INFLUENCE OF GROUND FAULT MONITORING DEVICES 4 1 COMPONENTS SUSCEPTIBLE TO INTERFERENCE 4 1 CHAPTER 5 TECHNICAL SPECIFICATIONS...

Page 3: ...ls etc Ignore this and you may get an electric shock WARNING The protective conductor connection between filter and drive must be designed as a solid and permanent installation Plug in connections are not permissible WARNING The use of ground fault monitoring devices is not recommended Should they be compulsory in certain applications for safety reasons you should choose monitoring devices which a...

Page 4: ... drives very rapidly switch large currents and voltages to optimally supply connected electric motors They are thus major sources of interference generating both line conducted and radiated interference The additional use of line filters also called interference suppression filters and installation in a metal housing or a switch cabinet further improve the existing interference immunity For the be...

Page 5: ...t in the so called footprint style are fitted behind the respective frequency inverter and thus require no additional space for installation These filters are intended for installation in switch cabinets as standard Vertical mounting next to the frequency inverter is also possible Note All filters are designed for 50 60Hz Frequency Inverter Line Power spcification Line Filter NES1 002 004SBE 1 200...

Page 6: ...requency inverter or solely via cable shield is not permitted as protective conductor connection The filter must be solidly and permanently connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs You can achieve this by connecting it with a grounding conductor of at least 10mm2 connecting a second grounding conductor connected w...

Page 7: ... EN61800 3 Cable length Inverter carrier frequency Frequency inverter Category C1 1 25m Max 10kHz NES1 015 022HBE Category C2 50m Max 10kHz 1 The inverter needs to be installed in a metal cabinet to meet category C1 Otherwise category C2 Filter FPF 9340 10 SW Switch position 1 High leakage current EN61800 3 Cable length Inverter carrier frequency Frequency inverter Category C2 50m Max 10kHz NES1 0...

Page 8: ...rference field emitted by the frequency inverter falls sharply with increasing distance Please note that the emitted interference field frequency range 30 MHz 1 GHz of a drive drive system is measured at a distance of 10 m in accordance with EN61800 3 Every device placed closer than 10 m to a source of interference will thus be impacted by appreciably higher interference amplitudes For this reason...

Page 9: ...should be preferred when shielding is to be implemented The contact or transition resistance between the individual stranded conductors of the shielding The performance of the shielding improves if this resistance is kept as low as possible The following diagram shows the transfer impedance for various cable types By comparing the cables individual design the shielding effectiveness can be estimat...

Page 10: ...in the cable If the use of reactors contactors terminals or safety switches in the motor output is necessary i e if the shield must be interrupted then the unshielded section should be kept as small as possible It is better to install the reactor contactor terminal or safety switch in a metal housing with as much HF damping as possible The shield connection to the metal housing should again be mad...

Page 11: ...andard EN60204 1 Electrical Equipment of Industrial Machinery You get optimum EMC only if you properly arrange and mount the Hitachi frequency inverter the appropriate line filter and the other equipment which might be necessary on a metal mounting plate in accordance with the following mounting instructions The following figure shows a Hitachi inverter using a foot print filter NE S1 ...

Page 12: ...patible installation of drives and drive systems 2 9 The following figure shows the required EMC compliant connection to the motor good HF connection between heat sink and motor housing required EMC cable connection metall box U V W PE ...

Page 13: ...riggering of a ground fault monitoring device that may be present Long motor cables lead to thermal overload of the line filter due to the higher line conducted interference If a motor choke of appropriate size is used you have the following advantages It can counteract unwanted shut off due to overload described above The thermal load on the EMC line filter is reduced In multiple motor applicatio...

Page 14: ... monitoring devices which are suited for DC AC and HF ground currents In addition you should ensure that their responsiveness and time characteristics are adjustable so that a disturbance is not immediately caused the first time the frequency inverter is switched on Components susceptible to interference The following components must be classified as particularly susceptible to interference from e...

Page 15: ...Output cable 2x2 5 mm 2x2 5 mm 3x4 mm 3x2 5 mm 3x2 5 mm Weight in kg approx 0 5 1 0 0 9 0 7 1 2 Heat dissipation in W approx 2 5 10 4 7 1 Worst case states the leakage current for three phase filters in the worst of cases That means one phase is live and two phases of the feed line lead in are interrupted These maximum values are based on an operating voltage of 460 V ph ph 2 The normal leakage cu...

Page 16: ...Chapter Technical specifications and dimensions of NE S1 filter 5 2 FPF 9120 10 SW FPF 9120 14 SW FPF 9120 24 SW ...

Page 17: ...Chapter Technical specifications and dimensions of NE S1 filter 5 3 FPF 9340 05 SW FPF 9340 10 SW ...

Page 18: ...the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the value mentioned in the table below Inverter model AC DC reactor Norm Ssc Rsce ...

Reviews: