NJI-669(X) 

 Available combination of products 

Be sure to use basic units and programming software with software version as follows. 
Basic units and programming software with old version do not support OBV-AIG / AIOG / RTD. 

Series name 

Product name 

Software version 

MICRO-EHV+ 

Basic units 

Ver.3.5.3.44 or later

 

programming software HX-CODESYS 

V3.5 SP8 Patch 4 or later *1

 

*1  In the case of using these products, the XML file for these products is required for HX-CODESYS. This file will be 

included in HX-CODESYS V3.5 SP13 Patch2. If this file isn't installed in HX-CODESYS

, contact your local supplier 

for the XML file.

 

 

 Caution for wiring 

(1)  Shield 

Since analog signal is very sensitive, be sure to use shielded cable in order to protect from noise, and route the cable 
apart from other power/signal cables. 
Be sure to ground the shield at one end basically. But grounding at both ends or no grounding can be more effective 
depending on system environment. 

[OBV-AIG / AIOG] 

 

Grounding at the one end 

 

IN1+ to IN4+ 
OUT1+ / 2+ 

Sensor 

or 

Converter 

Shielded 

Shielded cable 
(Twisted cable) 

Analog I/O 

Option board 

IN1- to IN4- 
OUT1- / 2- 

 

 

[OBV-RTD (3-wire)] 

 

1A / 3A 

1b / 3b 

 

 

RTD 

(3-wire)

 

Shielded cable 
(Twisted cable) 

 

RTD Input 

Option board 

1B / 3B 

Grounding at the one end 

 

Shielded 

 

 

 

[OBV-RTD (2-wire)] 

 

Grounding at the one end 

 

1A to 4A 

1B to 4B 

 
 

RTD 

(2-wire)

 

 

Shielded 

 

Shielded cable 
(Twisted cable) 

 

RTD Input 

Option board 

 

 

*RTD (3-wire) is recommended for OBV-RTD. Because measured value with RTD (2-wire) includes ohmic value of cable 

as  error,  it  is  not  suitable  for measurement  required  accuracy.  Please  be  in  particular  careful  when  the  length  of  the 
cable is long. 

 

(2)  Short of analog output (OBV-AIOG) 

Analog outputs must not be short-circuit. Otherwise it causes malfunction.

 

Summary of Contents for MICRO-EHV+ OBV-AIG

Page 1: ... economic loss CAUTION Identifies information about practice or circumstances which may lead to personal injury property damage or economic loss Safety precautions DANGER Do not touch terminals while power is ON There is a risk of electric shock and or injury Appropriate emergency stop circuit interlock circuitry and similar safety measures should be added to the PLC system to ensure safety in the...

Page 2: ...ard OBV AIOG 2 Channels of analog input 2 Channels of analog output RTD input option board OBV RTD 4 Channels of RTD input 2 Channels for 3 wire Reference Manual Read the following application manual carefully to use the PLC safely and properly Be sure to keep the latest version Manual name Manual number MICRO EHV APPLICATION MANUAL NJI 611 X The postfix of the publication number is subject to cha...

Page 3: ...log input signals Please set these DIP switches before insertion of the option board 2 OBV AIOG part names and functions Model name OBV AIOG Mass 0 02 kg 0 04 lb Upper side Back side 1 Analog input output terminal 3 DIP switches 2 Connector to basic unit No Name Details 1 Analog input output terminal Terminals to connect analog input output signals Cable diameter Single wire 0 2 mm2 to 1 5 mm2 Str...

Page 4: ...es not work normally 1 Be careful that the setting of output is reverse to it of input about voltage current mode 2 All DIP switches are set voltage I O mode at the time of shipment from factory Switch No Setting Figure of setting Setting items OBV AIG OBV AIOG SW1 1 OFF 1 2 SW2 ON SW1 1 2 ON IN1 Voltage input IN1 Voltage input ON 1 2 SW2 ON SW1 1 2 ON IN1 Current input IN1 Current input SW1 2 OFF...

Page 5: ...t OUT1 OUT2 IN2 IN1 2 3 4 1 7 8 5 6 5 OUT1 CH1 output Internal circuit OUT1 OUT2 OUT1 OUT2 Voltage Current SW2 1 SW2 2 1 6 OUT1 CH1 output 7 OUT2 CH2 output 8 OUT2 CH2 output 1 An output method of this product is the method that current flows out from this product If current flows from the other equipment the error may become large by addition to output from this product So please confirm input ci...

Page 6: ...6 7 8 2 1b CH1 input 3 1B CH1 input B 4 NC 5 3A CH3 input A 6 3b CH3 input 7 3B CH3 input B 8 NC 4 OBV RTD terminal layout 2 wire Terminal layout No Signal Function Internal circuit RTD input 4B 4A 3B 3A 3B 3b 3A 2B 2A 1B 1A 1B 1b 1A 3 wire 2 wire 3 wire 2 wire 1 2 3 4 7 8 5 6 1 1A CH1 input A Internal circuit 1A 2A 1B 2B 0 49 mA Pt100 3A 4A 3B 4B 1 2 3 4 5 6 7 8 2 1B CH1 input B 3 2A CH2 input A ...

Page 7: ... Voltage output 0 to 10 V 0 to 4 000 Current output 0 to 20 mA 0 to 4 000 Accuracy 1 At 25 3 C 0 4 FS Temperature coefficient 0 01 C FS Conversion time 4 ms 1 to 20 2 channels Output load impedance Voltage output Min 1 k Current output 1 to 500 Max 10 V Cable Shielded cable length Max 20 m Isolation Channel internal circuit Isolated Between channels None isolated 1 e g Accuracy at 45 C in voltage ...

Page 8: ...cable apart from other power signal cables Be sure to ground the shield at one end basically But grounding at both ends or no grounding can be more effective depending on system environment OBV AIG AIOG Grounding at the one end IN1 to IN4 OUT1 2 Sensor or Converter Shielded Shielded cable Twisted cable Analog I O Option board IN1 to IN4 OUT1 2 OBV RTD 3 wire 1A 3A 1b 3b RTD 3 wire Shielded cable T...

Reviews: