Control Logic Signal Specifications
Oper
ations
and Monitor
ing
4–6
Control Logic Signal Specifications
Specifications for the logic connection terminals are in the following table:
Note 1:
The two terminals [L] are electrically connected together inside the inverter.
Note 2:
We recommend using [L] logic GND (to the right) for logic input circuits and
[L] analog GND (to the left) for analog I/O circuits.
Note 3:
Default relay N.O./N.C. configuration is reversed. See page
Relay contacts
Logic inputs
Analog
inputs
Analog
output
Logic
outputs
12 11
1
2
3
4
5
L
L
H O OI
AM
CM2
PCS
AL2
AL0
AL1
The control logic connectors are located just
behind the front housing cover. The relay contacts
are just to the left of the logic connectors.
Connector labeling is shown below.
Terminal Name
Description
Ratings
[PCS]
+24V for logic inputs
24VDC, 30 mA max. (do not short to terminal L)
[1], [2], [3], [4], [5]
Discrete logic inputs
27VDC max. (use PCS or an external supply refer-
enced to terminal L)
[L] (right) *1
GND for logic inputs
sum of input [1]—[5] currents (return)
[11], [12]
Discrete logic outputs
50mA maximum ON state current,
27 VDC maximum OFF state voltage
[CM2]
GND for logic outputs
100 mA: sum of 11 and 12 currents (return)
[AM]
Analog voltage output
0 to 10VDC, 1mA maximum
[L] (left) *2
GND for analog signals
sum of OI, O, H, and AM currents (return)
[OI]
Analog input, current
4 to 19.6 mA range, 20 mA nominal,
input impedance 250
Ω
[O]
Analog input, voltage
0 to 9.8 VDC range, 10VDC nominal,
input impedance 10 k
Ω
[H]
+10V analog reference
10VDC nominal, 10 mA max
[AL0]
Relay common contact
250 VAC, 2.5A (R load) max.,
250 VAC, 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min.
30 VDC, 3.0A (R load) max.
30 VDC, 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.
[AL1] *3
Relay contact, normally open
[AL2] *3
Relay contact, normally
closed