Configuring Drive Parameters
20
The L100-M Series inverters have added the functions below to improve serial commu-
nications:
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–MFU2
–MFR2
Units
C_70 Data command method
Two option codes:
02 ... Digital operator
03 ... RS485
✘
02
02
—
SELECT REM
C_71 Communication speed
selection
Three option codes:
04 ... 4800 bps
05 ... 9600 bps
06 ... 19200 bps
✘
04
04
bps
BAU 4800bps
C_72 Node allocation
Set the address of the inverter
on the network.
Range is 1 to 32.
✘
01
01
—
ADDRESS 01
C_79 Communication error
response
Two option codes:
00 ... Trip
01 ... Continue operation
without tripping
✘
01
01
—
COM ERR TRP