PAGE:7/30
G
raph 1 图 1
P1 P2 P3 P4 P5 P6 P7 P8
Condensing temperature
70
℃
25
℃
10
℃
10
℃
65
℃
80
℃
80
℃
80
℃
Evaporation Temperature
25
℃
25
℃
10
℃
-30
℃
-30
℃
-10
℃
-5
℃
15
℃
6 Current limitation
Current peak among motor terminals(include instantaneous current peak)should be
below d
emagnetizing current
in order to prevent magnet in motor from demagnetization.
7 Pressure difference between suction and discharge
In all allowable rotational speed range, the difference of pressure should be more than
0.39MPa{4kgf/cm
2
}. But if there is no problem of noise when assembled in air conditioner,
it can also below this value.